Walgreens 5604-R14 June 24,2014 <br /> Unit Dimensions -3-10 Ton R-410A PKGD Unitary C 'oling Rooftop <br /> Item: A5 Qty: 1 Tag(s): RTU 5 <br />' 'ELECTRICAL/ ENERAL DATA <br /> 'GENERAL�2��4��6� WITH HEATER <br /> Model: 7HC060F Oversized Motor Heater kW Rating '9.0/12.0 <br /> Unit Operating Voltage: '187-253 Stage: 2 <br /> Unit Primary Vollage: 208 MCA: �N/A MCa 40.8l45.6 <br /> Unit Secondary Voltage 230 MFS: N/A MFS 45.0/50.0 <br /> Unit Hertz: 60 MCB: N/A MCB 45.0/50.0 <br /> Unit Phase: 3 <br /> SEER '15.0 <br /> Slandard Motor Field Installed Oversized Motor Oversized Motor Field Installed Oversized Motor <br /> MCA. �30.0 MCA: 'N/A MCA: �N/A MCA 'N/A <br /> MFS: 45.0 MFS: N/A MFS: N/A MFS: N/A <br /> MCB: 45.0 MCB: N/A MCB: N/A MCB: N/A <br /> INDOOR MOTOR <br /> Standard Motor Oulsized Motor Field Installed Oversized Motor <br /> Number 1 Number � /A Number �N/A <br /> Horsepower 1.0 Horsepower: /A Horsepower N/A <br /> Motor Speed(RPM): — Motar Speed(RPM): /A Mator Speed(RPM): N/A <br /> Phase: 1 Phase: /A Phase: N/A <br /> Full Load Amps: 7.6 Full Load Amps: �/A Full Load Amps: N/A <br /> Locked Rotor Amps: — Locked Rotor Amps: /A Locked Rotor Amps: N/A <br /> COMPRESSOR Circuit 1/2 OUTDOOR MOTOR <br /> I Number � Number. � <br /> Harsepower. 4�3 Horsepower. 0.40 <br /> Phase: 3 Motor Speed(RPM): 1075 <br /> Rated Load Amps: 15�9 Phase: 3 <br /> Locked Rotor Amps: 10�0 Full Load Amps: 2.5 <br /> Locked Rotor Amps: 6.6 <br /> POWEREXHAUSTACCESSORY �3� FILTERS REFRIGERANT (2� <br /> (Field Installed Power Exhaust) <br /> Type �R1310 <br /> Phase: 'N!A Type; `j'hrowaway <br /> Horsepower. N/A Fumished: es Factory Charge <br /> Mator Speed(RPM): N/A Number Circuit#1 �6.1 Ib <br /> Full Load Amps: N/A Recommended 6"x25'k2" Circuit#2 N/A <br /> LockedRotorAmps: N/A <br /> NOTES: <br /> 1.Maximum(HACR)Circuit Breaker sizing is for installations in the United States only. <br /> 2.Refrigeranl charge is an approximate value.For a more precise value,see unit nam plate and service instructions. <br /> 3.Value does not include Power Exhaust Accessory. <br /> 4.Value includes oversized motor. <br /> 5.Value does not include Power Exhaust Accessory. <br /> 6.EER is rated at AHRI conditions and in accordance with DOE test procedures. <br /> FLD=Fumished by Trane U S.Inc./Installed by Equipr�lent Submiftal Page 18 of 30 <br /> Others <br />