Laserfiche WebLink
S ingle F am'ly Dwelling <br /> Plan Revie Comments <br /> 1. F.F.E. Shall be a minimum of 8" above the r ad elevation and a engineered site plan. <br /> 2. Lots shall be graded to comply with R401.3 of the F.B.C.. <br /> 3. Compaction test required if 24" or more of ill dirt is brought in at any one place. <br /> 4. Tie in survey required before pouring concr te. <br /> 5. Driveways require a R.O.W. use permit. <br /> 6. All setbacks shall be met. <br /> 7. All property markers shall be uncovered an marked at time of first inspection. <br /> 8. All A.D.A. requirements shall be met. <br /> 9. No electric, plumbing,mechanical, or frami g shall be covered without an inspection and <br /> approval first. <br /> 10. All Garages shall comply with section R30 .2 of the F.B.C. (Fire Separation). <br /> 1 l. Appliances shall not be installed in a locati n where subject to mechanical damage unless <br /> protected by approved barriers. M303.4 of he F.B.0 <br /> 12. Water heaters shall comply with section P6 7.3 of the .F.B.0 <br /> 13. Foundation supports for A/C units shall be aised at least 3" above finished grade. M1308.1 <br /> 14. Return air in all bedrooms. F.B.C. M1620. <br /> 15. Smoke detectors are to be installed in accor ance with R313.1 of the F.B.C. <br /> 16. All glazing requirements are to be in accor ance with R308.4 of the F.B.C. <br /> 17. All means of egress are to be in accordance with R311 of the F.B.C. <br /> 18. "Green gypsum board" shall not be used as a backer in showers or tubs. R702.4.2 F.B.C. <br /> 19. Combination-type AFCI breakers are requi d at all locations requiring a AFCI type breaker. <br /> 20. Carbon monoxide alarms will be required i new construction that uses fossil-burning heating <br /> or appliances or an attached garage. They s all be installed in accordance with the F.B.C. <br /> 21. All plumbing, mechanical, and electrical sh 11 be separate from unit to unit. This includes all <br /> underground plumbing and electric. <br /> 22. A112008 N.E.C. Codes will be enforced. <br /> 23. Tamper- Resistant Receptacles in accordan e with 406.11 of the 2008 N.E.0 <br /> 22. In accordance with the Land Development ode, lots shall be sodded before final at least 10 <br /> feet around the structure. <br /> F.F.E.-Finished Floor Elevation <br /> F.B.C- Florida Building Code (2010) <br /> R.O.W.-Right Of Way <br /> A.D.A.-Americans with Disabilities Act <br /> N.E.C.-National Electric Code(2008) <br />