<br /> TABLE 2B:STEEL oe CONCRETE DECKS-NEW CONSTRUCTION,REROOF(TenR-OFF)oR RECOVER
<br /> SYSTEM TYPE C-1:MECHANICALLY ATTACHED INSULATION,BONDED ROOF COVER
<br /> System Deck Top Insulation Layer
<br /> Base Insulation Layer e Fasteners Attach Roof Cover/Adhesive MDP(psf)
<br /> No. (See Note 1) Typ
<br /> Min.22 ga.,type B, (Optional)One or more layers,any Min.2-inch Polyisocyanurate MP-H,H- VersiFleece/FAST 100 or FAST 100
<br /> SC-72 Grade 33 steel or min. combination,loose laid Shield,SecurShield,H-Shield CG See Note 2 1 per 4 ft� LV,max.12-inch o.c. -45.0*
<br /> 2,500 psiconcrete
<br /> Min.22 ga.,type B, (pptional)One or more layers,any Min.2-inch SecurShield HD Composite,H- Z VersiFleece/FAST 100 or FAST 100 ,
<br /> SC-73 Grade 33 steel or min. See Note 2 1 per 4 ft -45.0
<br /> 2,500 psi concrete combination,loose laid Shield HD Composite LV,max.12-inch o.c.
<br /> Min.22 ga.,type B, Min.1.5-inch thick,one or more VersiFleece/FAST 100,FAST 100 LV,
<br /> SC-74 Grade 33 steel or min. layers,any combination,loose laid Min 0.25-inch Dens Deck Prime See Note 2 1 per 2.0 ftZ max.12-inch o.c. -45.0*
<br /> 2,500 psi concrete
<br /> Min.22 ga.,type B, Min.1.5-inch thick,one or more VersiFleece/FAST 100,FAST 100 LV,
<br /> SC-75 Grade 33 steel or min. layers,any combination,loose laid Min 0.5-inch Dens Deck Prime See Note 2 1 per 2.0 ftZ Flexible FAST,max.12-inch o.c. -45.0*
<br /> 2,500 psiconcrete
<br /> Min.1.5-inch Polyisocyanurete MP-
<br /> Min.22 ga.,type B, H,MP-N or MP-W,H-Shield, VersiFleece/Flexible FAST,max.4
<br /> SC-76 Grede 33 steei or SecurShield,H-Shield CG,ENRGY 3 Min.0.5-inch SecurShield HD Plus See Note 2 1 per 4 ft' inch o.c.or full coverage -45.0*
<br /> structural concrete or ACFoam II _
<br /> Min.1.5-inch Polyisocyanurate MP-
<br /> Min.22 ga.,type B, H,MP-N or MP-W,H-Shield, Z VersiFleece/Flexible FAST,max.4
<br /> SC-77 Grede 33 steel or SecurShield,H-Shield CG,ENRGY 3 Min.0.5-inch SecurShield HD Plus See Note 2 1 per 1.78 ft inch o.c.or full coverage -60.0
<br /> structural concrete or ACFoam II
<br /> Min.22 ga.,type B, Min.1.5-inch thick,one or more Z VersiFleece/FAST 100,FAST 100 LV,
<br /> SC-78 Grade 33 steel or min. layers,any combination,loose laid Min 7/16-inch APA or TECO rated OSB See Note 2 1 per 1.9 ft Flexible FAST,full coverage -75.0
<br /> 2,500 psi concrete
<br /> Min.22 ga.,type B, Min.1.5-inch thick,one or more Min 0.5-inch SECUROCK Gypsum-Fiber 2 VersiFleece/FAST 100,FAST 100 LV,
<br /> SC-79 Grade 33 steel or min. See Note 2 1 per 1 ft ribbons max.4-inch o.c.or full -82.5
<br /> 2,500 psi concrete layers,any combination,loose laid Roof Board
<br /> coverage
<br /> Min.22 ga.,type B, 1 per 1.9 ftZ
<br /> Min.1.5-inch thick,one or more VersiFleece/Aqua Base 120 BA,
<br /> SC-80 Grade 33 steel or min. layers,any combination,loose laid Min 15/32-inch OSB See Note 2 (Carlisle SWF- HydroBond Water-Based -82'S
<br /> 2,500 psi concrete Z��)
<br /> �pe B Min.1.5-inch Polyisocyanurate MP-
<br /> Min.22 ga., H,MP-N or MP-W,H-Shield, VersiFleece/Flexible FAST,ribbons
<br /> SC-81 Grade 33 steel or SecurShield,H-Shield CG,ENRGY 3 Min.0.5-inch SecurShield HD Plus See Note 2 1 per 133 ftZ max.4-inch o.c.or full coverage -112.5
<br /> structural concrete orACFoam II
<br /> Min.22 ga.,type B, (Optional)One or more layers,any 2 VersiFleece/FAST 100,FAST 100 LV,
<br /> SC-82 Grade 33 steel or min. �ombination,loose laid Min 2-inch SecurShield,H-Shield CG See Note 2 1 per 1 ft ribbons max.4-inch o.c.or full -135.0
<br /> 2,500 psi concrete coverege
<br /> Exterior Research and Design,LLC.d/b/a Trinity� ERD Evaluation Report C35230.11.10-RS for FL14207-R6
<br /> Certificate of Authorization lt9503 Revision 5:06/19/2014
<br /> Prepared by: Robert Nieminen,PE-59166 Appendix 1,Page 13 of 36