Laserfiche WebLink
Materials Used <br /> Only R-Valuc RValuc Thickness ConducNvity Dcnsity SpecificHcat <br /> Mat No Acronym Description Uscd [h.sf.FBtu] [ft] [Btu/h.ft.F] �Ib/ct] [Btu/ib.F� <br /> 187 Mat1187 GYP OR PLAS No 0.4533 0.0417 0.0920 50.00 0.2000 <br /> BOARD,1/2IN <br /> 178 Mat1178 CARPET W/RUBBER PAD Yes 1.2300 ❑ <br /> 265 Mat1265 Soil,1 ft No 2.0000 1.0000 0.5000 100.00 0.2000 ❑ <br /> 48 Mat148 6 in.Heavyweight concrete No 0.5000 0.5000 1.0000 140.00 0.2000 ❑ <br /> 268 Mat1268 0.625"stucco No 0.1302 0.0521 0.4000 16.00 0.2000 ❑ <br /> 42 Mat142 8 in.Lighlweight concrete No 2.0212 0.6670 0.3300 38.00 0.2000 ❑ <br /> block <br /> 269 Mat1269 .75"ISO BTWN24"oc No 2.2321 0.0625 0.0280 4.19 0.3000 ❑ <br /> 23 Matl23 6 in.Insulation No 20.0000 0.5000 0.0250 5.70 0.2000 ❑ <br /> 4 Matl4 Steel siding No 0.0002 0.0050 26.0000 480.00 0.1000 ❑ <br /> 271 Mat1271 2x4@24"oc+Rl l Batt No 10.4179 �0.2917 0.0280 7.11 0.2000 ❑ <br /> 94 Matl94 BiJILT-UP ROOFING,3/8IN No 0.3366 0.0313 0.0930 70.00 0.3500 ❑ <br /> Constructs Used <br /> No Name Simple Masslcss Conductancc Heat Capacity Density RValue <br /> Construct Construct �Btu/h.sf.F� [Btu/sf.F� [Ib/cf] [h.sf.FBtu� <br /> 1011 5/8"stucco/8"CMLT/3/4"ISO No No - 0.21 5.73 34.65 4.8 ❑ , <br /> BTWN24"oc/.5"Gyp <br /> Laycr Matcrial Matcrial Thickness Framing <br /> No. [ft] Factor � <br /> 1 268 0.625"stucco 0.0521 0.000 ❑ <br /> 2 42 8 in.Lightweight concrete block 0.6670 0.000 ❑ <br /> 3 269 .75"ISO BTWN24"oc 0.0625 0.000 ❑ <br /> 4 187 GYP OR PLAS BOARD,1/2IN 0.0417 0.000 ❑ <br /> I <br /> 12/22/2014 EnergyGaugc SummiK�v5.00 8 <br /> ,. , <br />