Laserfiche WebLink
FIRE ALARM SYSTEMS - TECHNICAL SPECIFICATIONS <br />PART I GENERAL <br />1.1 SUMMARY <br />A. THIS SECTION COVERS THE FIRE ALARM SYSTEM INCLUDING INITIATING DEVICES, NOTIFICATION <br />APPLIANCES, CONTROLS, AND SUPERVISORY DEVICES. <br />B. WORK COVERED BY THIS SECTION INCLUDES THE FURNISHING OF LABOR, EQUIPMENT, AND MATERIALS <br />FOR INSTALLATION OF THE FIRE ALARM SYSTEM AS INDICATED ON THE DRAWINGS AND <br />SPECIFICATIONS. <br />C. THE FIRE ALARM SYSTEM SHALL CONSIST OF ALL NECESSARY HARDWARE EQUIPMENT AND SOFTWARE <br />PROGRAMMING TO PERFORM THE FOLLOWING FUNCTIONS: <br />1. FIRE ALARM AND DETECTION OPERATIONS. <br />2. CONTROL AND MONITORING OF FIRE SUPPRESSION SYSTEMS, AND OTHER EQUIPMENT AS INDICATED <br />IN THE DRAWINGS AND SPECIFICATIONS. <br />1.2 ACCEPTABLE MANUFACTURER <br />A. FIRE-LITES, OR EQUAL BY SIMPLEXGRINNEL, NOTIFIER, EDWARDS SYSTEM TECHNOLOGY, AND SILENT <br />KNIGHT. <br />1.3 RELATED DOCUMENT <br />A. THE SYSTEM AND ALL ASSOCIATED OPERATIONS SHALL BE IN ACCORDANCE WITH THE FOLLOWING: <br />1. THE FLORIDA BUILDING CODE 2020. <br />2. FLORIDA FIRE PREVENTION CODE, 6TH EDITION. <br />3. NFPA 72 (2013), NATIONAL FIRE ALARM CODE. <br />4. NFPA 70, NATIONAL ELECTRICAL CODE (2017) <br />5. NFPA 101, LIFE SAFETY CODE (2015) <br />6. LOCAL JURISDICTIONAL ADOPTED CODES AND STANDARDS. <br />7. ADA ACCESSIBILITY GUIDELINES. <br />1.4 SYSTEM DESCRIPTION <br />A. THE SYSTEM AND ALL ASSOCIATED OPERATIONS SHALL BE IN ACCORDANCE WITH THE FOLLOWING: <br />1. PROVIDE A COMPLETE, NON -CODED, ADDRESSABLE, MICROPROCESSOR -BASED FIRE ALARM SYSTEM <br />WITH INITIATING DEVICES, NOTIFICATION APPLIANCES, AND MONITORING AND CONTROL DEVICES. A <br />SYSTEM GENERAL ALARM SHALL INCLUDE: <br />a. INDICATION OF ALARM CONDITION AT THE FACP AND ANNUNCIATOR(S). <br />b. IDENTIFICATION OF THE DEVICE OR ZONE THAT IS THE SOURCE OF THE ALARM AT THE FACP. <br />c. UNLOCKING OF DESIGNATED DOORS. <br />d. NOTIFYING THE LOCAL FIRE DEPARTMENT. <br />e. INITIATION OF ELEVATOR RECALL IN ACCORDANCE WITH ASME/ANSI A17.3, WHEN SPECIFIED <br />DETECTORS OR SENSORS ARE ACTIVATED. <br />2. SUPERVISORY OPERATIONS: UPON ACTIVATION OF A SUPERVISORY DEVICE SUCH AS FIRE PUMP <br />POWER FAILURE, PUMP RUNNING, PHASE REVERSAL, LOW AIR PRESSURE SWITCH, AND TAMPER <br />SWITCHES, THE SYSTEM SHALL OPERATE AS FOLLOWS: <br />a. ACTIVATE THE SYSTEM SUPERVISORY SERVICE AUDIBLE SIGNAL AND ILLUMINATE THE LED AT THE <br />CONTROL UNIT. <br />b. RECORD THE EVENT IN THE FACP HISTORICAL LOG. <br />c. TRANSMISSION OF SUPERVISORY SIGNAL TO REMOTE CENTRAL STATION. <br />d. RESTORING THE CONDITION SHALL CAUSE THE SUPERVISORY LED TO CLEAR AND RESTORE THE <br />SYSTEM TO NORMAL. <br />3. IF THE "ALARM SILENCE" BUTTON IS PRESSED, ALL AUDIBLE AND VISIBLE ALARM SIGNALS SHALL <br />CEASE OPERATION. <br />a. THE "SYSTEM RESET" BUTTON SHALL BE USED TO RETURN THE SYSTEM TO ITS NORMAL STATE. <br />DISPLAY MESSAGES SHALL PROVIDE OPERATOR ASSURANCE OF THE SEQUENTIAL STEPS ("IN <br />PROGRESS", "RESET COMPLETED") AS THEY OCCUR. THE SYSTEM SHALL VERIFY ALL CIRCUITS OR <br />DEVICES ARE RESTORED PRIOR TO RESETTING THE SYSTEM TO AVOID THE POTENTIAL FOR <br />RE -ALARMING THE SYSTEM. THE DISPLAY MESSAGE SHALL INDICATE "ALARM PRESENT, SYSTEM <br />RESET ABORTED." <br />b. SHOULD AN ALARM CONDITION CONTINUE, THE SYSTEM WILL REMAIN IN AN ALARMED STATE. <br />4. THE "SYSTEM RESET" BUTTON SHALL BE USED TO RETURN THE SYSTEM TO ITS NORMAL STATE. <br />DISPLAY MESSAGES SHALL PROVIDE OPERATOR ASSURANCE OF THE SEQUENTIAL STEPS ("IN <br />PROGRESS", "RESET COMPLETED") AS THEY OCCUR. THE SYSTEM SHALL VERIFY ALL CIRCUITS OR <br />DEVICES ARE RESTORED PRIOR TO RESETTING THE SYSTEM TO AVOID THE POTENTIAL FOR <br />RE -ALARMING THE SYSTEM. THE DISPLAY MESSAGE SHALL INDICATE "ALARM PRESENT, SYSTEM <br />RESET ABORTED. <br />5. A MANUAL EVACUATION (DRILL) SWITCH SHALL BE PROVIDED TO OPERATE THE NOTIFICATION <br />APPLIANCES WITHOUT CAUSING OTHER CONTROL CIRCUITS TO BE ACTIVATED. <br />a. OPENING OF AN INITIATING OR NOTIFICATION APPLIANCE CIRCUIT WIRING SHALL CAUSE THE <br />AUDIBLE SIGNALS TO VOICE ANNOUNCE THE TROUBLE CONDITION. <br />b. POWER REQUIREMENTS. <br />- THE CONTROL UNIT SHALL RECEIVE AC POWER VIA A DEDICATED CIRCUIT BREAKER. <br />- THE SYSTEM SHALL BE PROVIDED WITH SUFFICIENT BATTERY CAPACITY TO OPERATE THE ENTIRE <br />SYSTEM UPON LOSS OF NORMAL AC POWER IN A NORMAL SUPERVISORY MODE FOR A PERIOD <br />OF 24 HOURS WITH15 MINUTES OF ALARM OPERATION AT THE END OF THIS PERIOD. THE <br />SYSTEM SHALL AUTOMATICALLY TRANSFER TO BATTERY STANDBY UPON POWER FAILURE. ALL <br />BATTERY CHARGING AND RECHARGING OPERATIONS SHALL BE AUTOMATIC. <br />1.5 QUALITY ASSURANCE <br />A. TINSTALLER QUALIFICATIONS: A FACTORY AUTHORIZED INSTALLER SHALL PERFORM THE WORK OF THIS <br />SECTION. <br />B. EACH AND ALL ITEMS OF THE FIRE ALARM SYSTEM SHALL BE LISTED AS A PRODUCT OF A SINGLE <br />FIRE ALARM SYSTEM MANUFACTURER UNDER THE APPROPRIATE CATEGORY BY UNDERWRITERS <br />LABORATORIES, INC. (UL), AND SHALL BEAR THE "UL" LABEL. <br />1.6 MAINTENANCE SERVICE <br />A. MAINTENANCE SERVICE CONTRACT: PROVIDE MAINTENANCE OF FIRE ALARM SYSTEMS AND EQUIPMENT <br />FOR A PERIOD OF 12 MONTHS, USING FACTORY -AUTHORIZED SERVICE REPRESENTATIVES. <br />B. BASIC SERVICES: SYSTEMATIC, ROUTINE MAINTENANCE VISITS ON A QUARTERLY BASIS AT TIMES <br />SCHEDULED WITH THE OWNER. IN ADDITION, RESPOND TO SERVICE CALLS WITHIN 24 HOURS OF <br />NOTIFICATION OF SYSTEM TROUBLE. ADJUST AND REPLACE DEFECTIVE PARTS AND COMPONENTS WITH <br />ORIGINAL MANUFACTURER'S REPLACEMENT PARTS, COMPONENTS, AND SUPPLIES. <br />C. ADDITIONAL SERVICES: PERFORM SERVICES WITHIN THE ABOVE 12-MONTH PERIOD NOT CLASSIFIED AS <br />ROUTINE MAINTENANCE OR AS WARRANTY WORK WHEN AUTHORIZED IN WRITING. COMPENSATION FOR <br />ADDITIONAL SERVICES MUST BE AGREED UPON IN WRITING PRIOR TO PERFORMING SERVICES. <br />FIRE ALARM SYSTEMS - TECHNICAL SPECIFICATIONS CONT. <br />SYMBOL <br />LEGEND <br />PART I) - EXECUTION <br />SYMBOL <br />DESCRIPTIONS <br />1. ALL WORK SHALL BE INSTALLED AS SHOWN, AND IN ACCORDANCE WITH NFPA 70, NFPA 72, <br />FACP <br />FIRE ALARM CONTROL <br />NFPA 101, FLORIDA FIRE PREVENTION CODE, 6TH EDITION, AND IN ACCORDANCE WITH THE <br />PANEL <br />MANUFACTURER'S DIAGRAMS AND RECOMMENDATIONS. <br />FAA <br />FIRE ALARM ANNUNCIATOR PANEL <br />2. CONTROL PANEL SHALL BE LOCATED BETWEEN 12 TO 78 INCHES AFF. <br />O <br />ADDRESSABLE PULL STATION <br />3. DETECTORS SHALL BE LOCATED AT LEAST 12 INCHES FROM ANY PART OF ANY LIGHTING <br />FIXTURES, 3 FEET FROM DIFFUSERS OF AIR HANDLING SYSTEMS AND CEILING FANS. <br />OD <br />DUCT MOUNTED SMOKE DETECTOR WITH RELAYS rOR AHU <br />SHUTDOWN. PROVIDE REMOTE WALL MOUNTED LEI) PILOT <br />4. NOTIFICATION APPLIANCES SHALL BE MOUNTED AT 80 INCHES AFF. <br />INDICATOR LIGHT AND SOUNDER WITH NAMEPLATE, <br />5. ACCEPTANCE TEST: DO NOT PERFORM ACCEPTANCE TESTING UNTIL THE CERTIFICATE OF <br />(4) <br />ADDRESSABLE HEAT DETECTOR <br />COMPLETION IS SUBMITTED TO THE OWNER. THE RECOMMENDED TESTS LISTED IN NFPA 72 <br />SHALL BE CONSIDERED MANDATORY AND SHALL BE USED TO VERIFY THAT PREVIOUS <br />O <br />ADDRESSABLE SMOKE DETECTOR <br />DEFICIENCIES HAVE BEEN CORRECTED. COMPLETE AND SUBMIT THE NFPA 72, INSPECTION <br />AND TESTING FORM. THE TEST SHALL INCLUDE ALL REQUIREMENTS OF NFPA 72 AND THE <br />® <br />STROBE <br />FOLLOWING: <br />A. TEST OF EACH FUNCTION OF THE CONTROL PANEL. <br />HORN/STROBE <br />B. TEST OF EACH CIRCUIT IN BOTH TROUBLE AND NORMAL MODES. <br />® <br />MONITOR MODULE <br />C. TEXTS OF EACH ALARM INITIATING DEVICES IN BOTH NORMAL AND TROUBLE CONDITIONS. <br />® <br />RELAY <br />D. TESTS OF EACH CONTROL CIRCUIT AND DEVICE. <br />® <br />FLOW SWITCH <br />E. TESTS OF EACH ALARM NOTIFICATION APPLIANCE. <br />® <br />TAMPER SWITCH <br />F. TESTS OF THE BATTERY CHARGER AND BATTERIES. <br />G. COMPLETE OPERATIONAL TESTS UNDER EMERGENCY POWER SUPPLY. <br />H. VISUAL INSPECTION OF WIRING CONNECTIONS. <br />I. OPENING THE CIRCUIT AT EACH ALARM INITIATING DEVICE AND NOTIFICATION APPLIANCE <br />TO TEST THE WIRING SUPERVISORY FEATURE. <br />J. GROUND FAULT. <br />K. SHORT CIRCUIT FAULTS. <br />L. STRAY VOLTAGE. <br />GENERAL NOTES: <br />1. PROVIDE AN ADDRESABLE FIRE ALARM SYSTEM FOR THIS PROJECT. CONTRACT DRAWINGS <br />SHOW LAYOUTS BASED ON TYPICAL FIRE ALARM DEVICES/EQUIPMENT. THE CONTRACTOR <br />SHALL CHECK THE LAYOUT BASED ON ACTUAL DEVICES/EQUIPMENT TO BE PROVIDED AND <br />MAKE NECESSARY REVISIONS. PROVIDE ALL FIRE ALARM EQUIPMENT, DEVICES, WIRING, <br />CONDUIT, AND ASSOCIATED COMPONENTS FOR COMPLETE INSTALLATIONS. <br />2. ALL CONDUIT SHALL BE IN MINIMUM 1 /2" UNLESS NOTED OTHERWISE AND CONDUCTORS <br />SHALL BE COPPER. CONDUCTORS SHALL BE SIZED PER MANUFACTURER'S <br />RECOMMENDATIONS. ALL CONDUCTORS SHALL BE IN CONDUIT. <br />3. CONDUIT FOR THE FIRE ALARM SYSTEM SHALL BE COMPLETELY INDEPENDENT OF ALL OTHER <br />WIRING. <br />4. AUDIBLE DEVICES SHALL BE WIRED INDEPENDENTLY FROM VISUAL DEVICES. SILENCING OF <br />AUDIBLE DEVICES SHALL NOT DE -ACTIVATE FLASHING STROBES UNTIL ALARM CONDITION IS <br />CLEARED. <br />5. EQUIPMENT AND DEVICES FOR THE FIRE ALARM SYSTEM SHALL BE LISTED AS A PRODUCT <br />OF A SINGLE FIRE ALARM SYSTEM MANUFACTURER UNDER THE APPROPRIATE CATEGORY BY <br />UNDERWRITERS LABORATORIES, INC. (UL), AND SHALL BEAR THE "UL" LABEL. <br />6. SPLICING OF CONDUCTORS ARE NOT ALLOWED INSIDE THE FACP. <br />7. VISUAL OR AUDIBLE/VISUAL DEVICES SHALL BE MOUNTED AT 80" TO 96" AFF TO THE <br />BOTTOM OF THE DEVICE PER NFPA 72. <br />8. AUDIBLE DEVICES SHALL BE MOUNTED AT A MINIMUM OF 90" AFF TO TOP OF DEVICE AND <br />NO MORE THAN 6" FROM TOP OF DEVICE TO CEILING PER NFPA 72. <br />9. MANUAL PULL STATION SHALL NOT BE LESS THAN 3'-6" AND NOT MORE THAN 4'-6" FROM <br />OPERABLE PART OF DEVICE TO FINISHED FLOOR PER NFPA 72. <br />10. SMOKE DETECTORS SHALL BE LOCATED AT MAXIMUM 15'-0" AWAY FROM WALL AND 3'-0" <br />AWAY FROM HVAC DUCT SUPPLY DIFFUSER. <br />11. ALL FIRE ALARM PULL STATIONS SHALL BE LOCATED WITHIN 5'-0" OF EXIT DOORS. <br />12. AUDIBLE ALARM SHALL PRODUCE A SOUND THAT EXCEEDS THE PREVAILING EQUIVALENT <br />SOUND LEVEL IN THE ROOM OR SPACE BY AT LEAST 15 dBA OR EXCEEDS ANY MAXIMUM <br />SOUND LEVEL WITH A DURATION OF 60 SECONDS BY 5 dBA, WHICHEVER IS LOUDER. <br />SOUND LEVELS FOR ALARM SIGNALS SHALL NOT EXCEED 115 dBA. CONTRACTOR SHALL <br />ADJUST POWER TAPS AND/OR PROVIDE ADDITIONAL MASS NOTIFICATION SPEAKERS AS <br />NECESSARY TO MEET THIS REQUIREMENT. <br />13. PROVIDE CONDUCTOR INTEGRITY MONITORING FOR ALL NOTIFICATIONS DEVICES. <br />14. PROVIDE SURGE PROTECTION FOR THE FIRE ALARM CONTROL PANEL AND INSTALLED IN <br />ACCORDANCE WITH NFPA 70 & 72. INSTALL SURGE PROTECTION IN A 6" SQ. JUNCTION <br />BOX. PROVIDE LOW VOLTAGE SURGE PROTECTION FOR ALL FIRE ALARM SIGNALS WIRING <br />ENTERING OR LEAVING THE BUILDING. <br />15. ALL NEW FIRE ALARM DEVICES MAY BE ADJUSTED TO SUIT FIELD CONDITIONS. <br />�Q <br />�p <br />ap <br />Y uj <br />p0 <br />r <br />a <br />00 <br />U. <br />U. <br />v� <br />z <br />0 <br />a. <br />w <br />0 <br />U <br />N <br />O <br />N <br />0 <br />ITH CORPORATION <br />10450 BLOOMFIELD HILLS DRIVE <br />SEFFNER, FLORIDA 33584 <br />PHONE: 813.312.3070 <br />FL CA: #32733 <br />TO THE BEST OF MY KNOWLEDGE, <br />THE SPECIFICATIONS AND PLANS <br />SHOWN HEREIN COMPLY WITH THE <br />APPLICABLE MINIMUM BUILDING <br />CODES IN EFFECT AT THIS TIME. <br />THIS DRAWING AND ALL <br />INFORMATION CONTAINED HEREIN <br />IS THE EXCLUSIVE PROPERTY OF <br />ITH CORPORATION, AND IS NOT TO <br />BE COPIED OR USED IN ANY WAY <br />WITHOUT THE EXPRESS WRITTEN <br />CONSENT OF ITH CORPORATION. <br />AND MUST BE RETURNED UPON <br />REQUEST. THIS DRAWING IS NOT <br />FOR GENERAL USE OR <br />PUBLICATION, ALL RIGHTS <br />RESERVED. <br />U <br />Z <br />W <br />LO <br />W U) <br />W m M O <br />U <br />0 CO vi <br />W O w <br />0 <br />IJ o U) <br />Q ~ J <br />LL O? <br />W cD <br />mCO <br />LL H CL m <br />V <br />Z <br />/. a <br />V 0 <br />a � <br />> GO <br />t/� m LL <br />J °z -j <br />_ _J <br />OC Q . _ <br />Q w } <br />a W o IL <br />_ <br />W r-. W <br />N LL M N <br />IRVING HO, PE <br />No.852 •* <br />8/ 1882021 <br />���• STATE OF •��� <br />�i'A�••F4ORIDP•' �L+ <br />IONALV <br />FL PE: #85232 <br />REVISIONS Q <br />1 <br />2 <br />3 <br />4 <br />5 <br />6 <br />JOB NO: 21034 <br />DRAWN BY: ITH <br />DESIGNED BY: ITH <br />ISSUE DATE: 06-22-21 <br />SHEET TITLE: <br />FIRE ALARM <br />SYMBOL LEGEND <br />& NOTES <br />SHEET NUMBER <br />FA-1 <br />