GENERAL NOTES: <br />THIS BUILDING HAS BEEN DESIGNED TO CONFORM TO THE 2020 FLORIDA BUILDING CODE <br />7 TH EDITION <br />ARKAY ENGINEERING, INC.; A REGISTERED, LICENSED, FLORIDA PROFESSIONAL STRUCTURAL <br />ENGINEERING COMPANY, HAS APPLIED 'RATIONAL ANALYSIS" FOR THE STRUCTURAL DESIGN <br />OF THIS STRUCTURE. <br />THE BUILDING (INCLUDING ALL COMPONENTS AND CLADDINGS) SHALL BE DESIGNED FOR THE <br />FOLLOWING SUPERIMPOSED LOADS: <br />FLOOR: <br />LIVE LOAD - 50 P.S.F. <br />DEAD LOAD - 10 P.S.F. <br />ROOF - <br />LIVE LOAD (TRUSS TOP CHORD) - 20 P.S.F. <br />DEAD LOAD (TRUSS TOP CHORD) - 10 P.S.F. <br />DEAD LOAD (TRUSS BOTTOM CHORD) - 10 P.S.F. <br />ASSUMED TRUSS SELF WEIGHT (DEAD LOAD) - 7 P.S.F. <br />WIND' <br />BUILDING IS DESIGNED TO CONFORM TO ASCE 7-16, CHAPTERS 26 THRU 31; PER 2020 FLORIDA <br />BUILDING CODE, 7 TH EDITION - SECTION R301.2.1.1. AND 2020 FLORIDA BUILDING <br />CODE 7 TH EDITION SECTION 1609 <br />WIND DESIGN ASSUMPTIONS: <br />BUILDING EXPOSURE - B <br />BUILDING RISK CATEGORY - II <br />MEAN ROOF HEIGHT 30' OR LESS <br />HEIGHT & EXPOSURE ADJUSTMENT <br />COEFFICIENT = 1.0 <br />ENCLOSED BUILDING <br />INTERNAL PRESSURE COEFFICIENT = +/- 0.18 <br />WIND SPEED SHOWN AT THE BOTTOM RIGHT <br />CORNER OF THIS SHEET <br />ALL STRUCTURAL ELEMENTS, EXTERIOR <br />WALLS AND INTERIOR WALLS SHALL BE <br />TYPE V CONSTRUCTION PER FBC 602.5 <br />SOIL BEARING & COMPACTION: <br />COMPONENT & CLADDING WIND LOADS <br />ALL OTHER <br />BUILDING <br />ROOF OVERHANG <br />COMPONENT <br />20NE <br />LOADS <br />LOADS <br />1 <br />N/A <br />+32.3/-35.3 <br />2 <br />-65.7 <br />+32.31-56 2 <br />3 <br />-110.6 <br />+32.3/-89.0 <br />4 <br />N/A <br />t 35.3/-38.2 <br />11 <br />N/A <br />+35.3/A7.2 <br />THESE PLANS WERE DRAWN BASED UPON AN ALLOWABLE SOIL BEARING CAPACITY OF 2,000 P S F. <br />(MINIMUM). THE CONTRACTOR/PROPERTY OWNER ARE RESPONSIBLE FOR VERIFYING THAT THE SOIL <br />ON THE SITE IS PROPERLY PREPARED & COMPACTED SUCH THAT IT CAN SUPPORT A 2,000 P.S.F. <br />FOUNDATION LOADING. <br />ARKAY ENGINEERING, INC.; A REGISTERED, LICENSED, FLORIDA PROFESSIONAL STRUCTURAL <br />ENGINEERING COMPANY; DESIGNED THESE FOUNDATIONS WITHOUT VISITING THE CONSTRUCTION SITE <br />NOR PERFORMING ANY SOIL TESTING. <br />ARKAY ENGINEERING, INC. SHALL NOT BE RESPONISIBLE FOR THE SITE SOILS ABILITY TO SUPPORT <br />THE BUILDING LOADS. <br />FOUNDATIONS & SLAB -ON -GRADE: <br />BUILDING SITE SHALL BE SCRAPED TO REMOVE ALL ORGANIC MATERIALS WITHIN THE BUILDING AREA. <br />ANY ADDITIONAL FILL PLACED ON THE BUILDING PAD AREA, SHALL BE COMPACTED <br />SUCH THAT IT CAN ADEQUATELY SUPPORT A 2,000 P.S.F. FOUNDATION LOADING. <br />SLAB SHALL BE PLACED OVER A 6 MIL VAPOR BARRIER ON CLEAN, ADEQUATELY <br />COMPACTED AND TERMITE POISONED SOIL. <br />CONCRETE UTILIZED IN THE FOUNDATIONS AND SLABS SHALL HAVE A MINIMUM 28 DAY <br />COMPRESSIVE STRENGTH OF 2,500 P.S.I. <br />REINFORCING STEEL SHALL BE GRADE 40 MINIMUM AND IDENTIFIED IN ACCORDANCE <br />WITH ASTM A-615. LAP SPLICES, WHERE REQUIRED, SHALL BE A MINIMUM OF 25' <br />FOR #5 REBAR, 30" FOR #6 REBAR & 35" FOR #7 REBAR. <br />PLANS ARE ENGINEERED FOR A MAXIMUM STEMWALL HEIGHT OF 4 COURSES (AFTER <br />FINAL SITE GRADING) THE CONTRACTOR OR BUILDING OWNER SHALL DETERMINE THE <br />EXACT STEMWALL HEIGHT BASED UPON SITE CONDITIONS PRIOR TO POURING THE FOUNDATION <br />AND CONTACT ARKAY ENGINEERING WHEN MORE THAN 4 COURSES ARE REQUIRED. <br />A FOUNDATION SURVEY SHALL BE PERFORMED AND A COPY OF THE SURVEY SHALL BE ON THE <br />SITE FOR THE BUILDING INSPECTORS USE, OR ALL PROPERTY MARKERS SHALL BE EXPOSED AND <br />A STRING STRETCHED FROM MARKER TO MARKER TO VERIFY THE REQUIRED BUILDING SETBACKS. <br />MASONRY WALLS: <br />CONCRETE MASONRY UNITS SHALL BE HOLLOW UNIT MASONRY IN ACCORDANCE WITH ASTM C-90 <br />AND SHALL HAVE A MINIMUM F'M OF 1,500 P.S.I. <br />MORTAR SHALL CONFORM TO ASTM C-270 AND SHALL BE EITHER TYPE M OR S. <br />REINFORCING STEEL SHALL BE GRADE 40 MINIMUM AND IDENTIFIED IN ACCORDANCE <br />WITH ASTM A-615. LAP SPLICES, WHERE REQUIRED, SHALL BE A MINIMUM OF 25" <br />FOR #5 REBAR, 30" FOR #6 REBAR & 35" FOR #7 REBAR. <br />GROUT FOR THE POURED CELLS AND LINTELS SHALL HAVE A MAXIMUM COURSE AGGREGATE SIZE <br />OF 3/8', PLACED AT AN 8 TO 11 INCH SLUMP AND HAVE A MINIMUM 28 DAY COMPRESSIVE STRENGTH <br />OF 2,500 P.S.I. (WHEN TESTED PER ASTM C-1019), <br />PROVIDE CLEAN -OUT OPENINGS (12 SO IN_) IN CELLS CONTAINING SPLICED REINFORCEMENT, WHEN <br />THE GROUT POUR EXCEEDS 5 FEET IN HEIGHT. <br />TIMBER MATERIALS <br />ALL TIMBER MATERIALS SHALL BE AS FOLLOWS: <br />ALL LUMBER IN CONTACT WITH MASONRY WILL BE PRESSURE TREATED <br />MATERIALS <br />INTERIOR STUD WALLS TO BE OF 2 X 4 #2 SPRUCE OR BETTER WITH SINGLE 2 X 4 P.T. <br />PINE BOTTOM PLATE AND SINGLE 2 X 4 #2 SPRUCE TOP PLATE WITH STUDS SPACED <br />MAXIMUM 24" OC. WALLS TO HAVE 112" GYPSUM BOARD EACH SIDE, WITH WALLS AT <br />GARAGE TO HAVE MINIMUM R-11 INSULATION <br />SOIL TERMITE TREATMENT: <br />TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED TERMITICIDES, INCLUDING PESTICIDES <br />APPLIED TO SOIL, OR WOOD, BAITING SYSTEMS, OR OTHER APPROVED PROTECTION LABELED FOR <br />USE AS A PREVENTATIVE TREATMENT TO NEW CONSTRUCTION. <br />A "CERTIFICATE OF COMPLIANCE" SHALL BE ISSUED TO THE BUILDING DEPARTMENT BY A LICENSED <br />PEST CONTROL COMPANY BEFORE A "CERTIFICATE OF OCCUPANCY" WILL BE ISSUED. THE CERTIFICATE <br />SHALL STATE <br />"THE BUILDING HAS RECEIVED A COMPLETE TREATMENT FOR THE PREVENTION OF SUBTERRANEAN <br />TERMITES. THE TREATMENT IS IN ACCORDANCE WITH THE RULES AND LAWS OF THE FLORIDA <br />DEPARTMENT OF AGRICULTURE AND CONSUMER SERVICES-" <br />IF A REGISTERED TERMITICIDE BAIT SYSTEM IS TO BE USED FOR SUBTERRANEAN TERMITE PREVENTION, <br />DO NOT APPLY. A SIGNED FIVE YEAR CONTRACT FROM THE ISSUE <br />OF THE CERTIFICATE OF OCCUPANCY ASSURING INSTALLATION, MAINTENANCE AND MONITORING OF THE <br />BAITING SYSTEM SHALL BE PROVIDED TO THE BUILDING OFFICIAL PRIOR TO THE SLAB POUR_ THE SYSTEM <br />MUST BE INSTALLED PRIOR TO FINAL BUILDING APPROVAL. <br />INITIAL SOIL POISONING TREATMENT SHALL BE DONE AFTER ALL EXCAVATION, <br />BACKFILLING & COMPACTION ARE COMPLETE <br />ANY SOIL DISTURBED AFTER THE INITIAL TREATMENT SHALL BE RE -TREATED <br />(INCLUDING ANY BOXED OR FORMED AREAS) - <br />BOXED AREAS IN THE CONCRETE SLAB FOR INSTALLATION OF TRAPS SHALL BE MADE <br />WITH PERMANENT METAL OR PLASTIC FORMS. PERMANENT FORMS MUST BE OF AN <br />ADEQUATE SIZE & DEPTH TO ELIMINATE ANY DISTURBANCE OF THE SOIL AFTER THE <br />INITIAI TREATMFNI. <br />A MINIMUM 6 MIL VAPOR BARRIER MUST BE INSTALLED TO PROTECT AGAINST RAINFALL <br />DILUTION. IF RAINFALL OCCURS BEFORE VAPOR BARRIER PLACEMENT, RE -TREATMENT <br />SHALL BE REQUIRED <br />ANY CONCRETE OVERPOUR, MORTAR OR STUCCO MATERIALS ALONG THE FOUNDATION PERIMETER <br />MUST BE REMOVED PRIOR TO EXTERIOR SOIL TREATMENT <br />EXTERIOR SOIL TREATMENT MUST BE APPLIED UNDER ALL EXTERIOR CONCRETE OR GRADE <br />WITHIN 12 INCHES OF THE STRUCTURE SIDE WALLS <br />AN EXTERIOR VERTICAL CHEMICAL BARRIER SHALL BE INSTALLED AFTER CONSTRUCTION IS <br />COMPLETE (INCLUDING LANDSCAPING AND IRRIGATION). ANY SOILS DISTURBED AFTER THE <br />VERTICAL BARRIER IS APPLIED, SHALL BE RE -TREATED. <br />CONDENSATE AND ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST 12 INCHES AWAY FROM THE <br />BUILDING SIDEWALLS (PER FBC R318). <br />AFTER ALL WORK IS COMPLETED, ANY LOOSE WOOD AND FILL MUST BE REMOVED FROM BELOW <br />AND WITHIN 12 INCHES OF THE BUILDING. THIS SHALL INCLUDE ALL GRADE STAKES, TUB TRAP BOXES <br />FORMS, SHORING AND ANY OTHER CELLULOSE CONTAINING MATERIALS. <br />THE DISTANCE FROM THE EXTERIOR WALL COVERING (EXCEPTIONS: PAINT AND DECORATIVE <br />CEMENTITIOUS FINISHES LESS THAN 5/8 INCH THICK ADHERED DIRECTLY ONTO THE FOUNDATION <br />WALL) AND FINAL EARTH GRADE SHALL NOT BE LESS THAN 6 INCHES TO ALLOW FOR INSPECTION <br />FOR FUTURE TERMITE INFESTATIONS <br />TRUSSES <br />IF THE CONTRACTOR, TRUSS MANUFACTURER OR ANY OTHER DESIGN PROFESSIONALS REVISE THE <br />TRUSS SYSTEM LAYOUT FROM THOSE SHOWN ON THESE PLANS T_ L HANSON & ASSOCIATES IS <br />REQUIRED TO REVIEW ALL FINAL CONSTRUCTION DOCUMENTS FOR COMPLIANCE WITH THE DESIGN <br />INTENT PRIOR TO COMMENCEMENT OF THE PROJECT. <br />EXTERIOR WINDOWS & DOOR ASSEMBLIES: <br />ALL EXTERIOR WINDOW & GLASS DOORS SHALL BE TESTED IN ACCORDANCE WITH ANSI/AMMA/NWWDA <br />101/IS2 STANDARDS AND BEAR AN AMMA OR WDMA LABEL IDENTIFYING THE MANUFACTURER, <br />PERFORMANCE CHARACTERISTICS AND APPROVED PRODUC I I ES I ING EN 11 I Y. <br />ALI. MULLIONS AND ADJACENT DOORIWINDOW ASSEMBLIES SHALL BE TESTED OR ENGINEERED TO <br />TRANSFER 1.5 TIMES THE DESIGN LOADS TO THE ROUGH OPENING SUBSTRATE. <br />INSTALL ALL WINDOW & DOOR ASSEMBLIES PER THE MANUFACTURERS ANCHORING RECOMMENDATIONS <br />TO ACHIEVE THE DESIGN PRESSURES SPECIFIED. <br />ELECTRICAL, PLUMBING & MECHANICAL <br />IN ACCORDANCE WITH CHAPTER 471.003(2)(1) OF THE FLORIDA ADMINISTRATIVE CODE, ELECTRICAL, <br />PLUMBING AND MECHANICAL SYSTEMS SHALL BE DESIGNED BY THE RESPECTIVE CONTRACTORS TO <br />MEET ALL APPLICABLE CODES. THE ELECTRICAL, PLUMBING AND MECHANICAL SYSTEMS DRAWN HEREON <br />ARE BASED UPON A DESIGN PROVIDED BY THE OWNER TO ADDRESS HIS/HER REQUIREMENTS. <br />ALL ELECTRICAL OUTLETS IN BATHROOMS, KITCHEN, GARAGE AND AT <br />EXTERIOR LOCATIONS SHALL BE WIRED INTO A GROUND -FAULT INTERRUPTER "GFI" CIRCUIT. <br />ALL ELECTRICAL OUTLETS IN HABITABLE SPACES SHALL BE WIRED INTO AN ARC -FAULT INTERRUPTER <br />SAFETY GLAZING: <br />THE FOLLOWING SHALL BE CONSIDERED SPECIFIC HAZARDOUS LOCATIONS FOR THE PURPOSES OF <br />GLAZING PER THE FLORIDA BUILDING CODE, RESIDENTIAL - SECTION R308: <br />(1) GLAZING IN SWINGING DOORS, FIXED AND SLIDING PANELS OF SLIDING DOOR <br />ASSEMBLIES. <br />(2) GLAZING IN DOORS AND ENCLOSURES FOR HOT TUBS, WHIRLPOOLS, SAUNAS, STEAM <br />ROOMS, BATHTUBS, AND SHOWERS. GLAZING IN ANY PORTION OF A BUILDING WALL <br />ENCLOSING THESE COMPARTMENTS WHERE THE BOTTOM EDGE OF THE GLAZING IS LESS <br />THAN 60 INCHES ABOVE THE DRAIN INLET. <br />(3) GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL ADJACENT A DOOR WHERE <br />THE NEAREST VERTICAL EDGE IS WITHIN A 24 INCH RADIUS OF THE DOOR IN A <br />CLOSED POSITION AND WHOSE BOTTOM EDGE IS LESS THAN 60 INCHES ABOVE THE <br />FINISHED FLOOR OR WALKING SURFACE. <br />(4) GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL, OTHER THAN THOSE LOCATIONS <br />DESCRIBED IN ITEMS (2) AND (3) ABOVE THAT MEETS ALL OF THE FOLLOWING <br />CONDITIONS: <br />A) EXPOSED AREA OF AN INDIVIDUAL PANE GREATER THAN 9 SQ. FT. <br />B) BOTTOM EDGE LESS THAN 18 INCHES ABOVE THE FLOOR. <br />C) TOP EDGE GREATER THAN 36 INCHES ABOVE THE FLOOR. <br />D) ONE OR MORE WALKING SURFACES WITHIN 36 INCHES HORIZONTALLY OF THE <br />PLANE OF THE GLAZING. <br />REFER TO THE FLORIDA BUILDING CODE, RESIDENTIAL - SECTION R308 FOR ADDITIONAL AREAS <br />THAT MAY BE CONSIDERED A HAZARDOUS LOCATION FOR THE PURPOSE OF GLAZING. <br />BUILDING DESIGNS <br />13821 U.S. HWY 98 BY PASS DADE CITY, FLORIDA 33523 <br />OFFICE 352-523-2077 <br />SHELL OFFICE BUILDING <br />6638 DAIRY ROAD <br />ZEPHYRHILLS, FLORIDA <br />JOB SITE LOCATION MAP <br />FLORIDA FIRE PREVENTION CODE 7TH EDITION <br />7 TH EDITION 2020 FLORIDA BUILDING CODE <br />7 TH EDITION 2020 FLORIDA ACCESSIBILITY CODE <br />BUILDING HAS WOOD ROOF SYSTEM <br />LIGHT FRAME CONSTRUCTION SIGN REQUIRED <br />BUILDING DATA <br />TOTAL AREA 3242.2 SO. FT. <br />USE AND OCCUPANCY: BUSINESS GROUP B <br />CONSTRUCTION TYPE : VB <br />FIRE PROTECTION : NON SPRINKLED <br />RYMAN CONSTRUCTION INC <br />36413 STR RD 54 <br />ZEPHYRHILLS, FL 33541 <br />OFFICE 813-782-0825 <br />6001u_1 <br />REVIEW DATE:_�_�_2, / <br />CITY OF ZEPHYRHILLS <br />BUILDING OFFICIAL <br />PLAN INDEX <br />SITE PLAN BY OTHERS <br />SHEET B 1: BUILDING FLOOR PLAN <br />WINDOW AND DOOR SCHEDULE <br />FLORIDA PRODUCT APPROVAL <br />SHEET B 2: BUILDING ELEVATIONS <br />SHEET B 3: BUILDING FOUNDATION PLAN <br />DECK FOUNDATION PLAN <br />LINTEL DETAIL <br />LINTEL CHART <br />DOOR BUCK DETAIL <br />WINDOW BUCK DETAIL <br />SHEET B 4: WALL SECTION DETAILS A & B <br />DECK FRAMING PLAN <br />DECK CUT SECTION DETAIL <br />SOFFIT DETAIL <br />WINDOW FLASHING DETAIL <br />PLYWOOD DETAIL <br />SHEET B 5: ROOF TRUSS PLAN <br />TRUSS BRACE DETAIL <br />VALLEY FRAMING DETAIL <br />FLASHING DETAIL <br />SHEET E 1 : ELECTRICAL PLAN <br />RISER DETAIL <br />ELECTRICAL LEGEND <br />ALL WORK SHALL COMPLY WITH PREVAILING <br />CODES FLORIDA BUILDING CODE, <br />NATIONAL ELECTRIC CODE, <br />AND THE CITY OF ZEPHYRHILLS <br />ORDINANCES <br />AFKAY EN(SINEERING INC,. <br />structural engineers <br />1955 E. Edgewood Drive, Lakeland FI 33803 <br />Phone 863-688-6500 Fax 863-688-655-1 <br />State of Florida Certificate of Authorization " E86341 <br />Richard L Kiddey P.E_ - Florida License M 31296 <br />ARKAY JOB # 19870 <br />