a <br />FIRE ALARM SPECIFICATIONS & GENERAL NOTES <br />FIRE ALARM SYSTEM TESTING, INSPECTION, INSTRUCTION <br />r_ <br />E <br />I. GENERAL SCOPE: <br />A. THIS PROJECT WILL REQUIRE THE INSTALLATION OF A SILENT KNIGHT 6808 ADDRESSABLE FIRE ALARM SYSTEM FOR A 3 - STORY SELF STORAGE FACILITY. AS INDICATED ON THESE PLANS A <br />NON-PROPRIETARY SYSTEM SHALL BE INSTALLED. THE FIRE ALARM SYSTEM SHALL MONITOR THE FIRE SPRINKLER SYSTEMS, BDA SYSTEM, AND INTERFACE WITH THE ELEVATORS FOR ELEVATOR <br />RECALL AND SHUT DOWN AS REQUIRED BY NFPA 72, <br />11. REQUIREMENTS <br />A. THE INSTALLATION SHALL CONFORM TO THE INTENT OF NFPA 72 (2016 ED.), FLORIDA FIRE PREVENTION CODE (2020 ED.), THESE PLANS, AND APPLICABLE REFERENCED DOCUMENTS. <br />B. SECONDARY POWER SHALL CONSIST OF RECHARGEABLE BATTERIES HAVING A CAPACITY TO POWER THE ALARM SYSTEM FOR A PERIOD OF 24 HOURS IN A STANDBY MODE AND OPERATE ALL <br />NOTIFICATION APPLIANCES FOR 5 MINUTES AT THE END OF THE 24 HOUR PERIOD. <br />C. ALL CIRCUITS SHALL BE "POWER LIMITED". THE CIRCUIT TYPES SHALL BE INSTALLED AS INDICATED BELOW: <br />SIGNALING LINE LOOP: CLASS "B" <br />INITIATION DEVICE CIRCUITS (IDC'S): CLASS "B" <br />NOTIFICATION ALARM CIRCUITS (NAC'S): CLASS "B" <br />D. WALL -MOUNTED NOTIFICATION HORN/STROBES ARE TO BE MOUNTED SO THAT THE ENTIRE LENS OF THE DEVICE IS NO LESS THAT 80" AFF AND NO GREATER THAN 96" AFF. CEILING -MOUNTED <br />NOTIFICATION DEVICES ARE TO BE MOUNTED AT A MAXIMUM HEIGHT OF 30 FT. (AS INDICATED ON THE PLANS) <br />E. ALL NEW PULL STATIONS SHALL BE INSTALLED AT 48 INCHES ABOVE THE FINISH FLOOR. <br />F. ALL WIRING CONNECTIONS ARE TO BE IN SINGLE, DOUBLE, TRIPLE OR 4 INCH ELECTRICAL BOXES, AS NEEDED. WIRING CONNECTIONS OUTSIDE OF ELECTRICAL BOXES WILL NOT BE ALLOWED. <br />G. ALL WIRING ON THE INITIATION AND NOTIFICATION CIRCUITS ARE SUPERVISED POWER LIMITED. <br />H. SURGE SUPPRESSION DEVICES SHALL BE INSTALLED ON ALL CIRCUITS THAT ENTER OR EXIT THE BUILDING. TYPICAL DEVICES ARE LISTED BELOW: <br />PANEL POWER: DITEK MODEL DTK-120HW, EDCO (OR EQUAL) <br />INITIATING CKTS: DITEK MODEL DTK-2LVLP-F, EDCO (OR EQUAL) <br />PHONE LINES: DITEK MODEL DTK-MRJ3ISXCPWP, EDCO (OR EQUAL) <br />I. STROBE CIRCUITS SHALL BE SYNCHRONIZED EITHER THROUGH THE MAIN FACP OR SEPARATE SYNCHRONIZATION MODULES (AS NECESSARY). <br />J. FIRE ALARM PATHWAY SURVIVABILITY REQUIRED FOR THIS PROJECT (NFPA 72, CHAPTER 12): <br />PATHWAY LEVEL 1 REQUIRED FOR: <br />PANEL POWER CONDUCTORS (120 VAC) <br />NETWORK\COMMUNICATIONS BETWEEN PANELS <br />PATHWAY LEVEL 0 REQUIRED FOR: <br />SIGNALING LINE LOOP CIRCUITS (SLC) <br />INITIATION DEVICE CIRCUITS (IDC) <br />NOTIFICATION APPLIANCE CIRCUITS (NAC) <br />DEVICE POWER TO NOTIFICATION OR INITIATION DEVICES <br />111. CONDUIT AND WIRE <br />A. CONDUIT: <br />1. CONDUIT INSTALLATION SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC), LOCAL AND STATE REQUIREMENTS. <br />2. CONDUIT FILL WILL NOT EXCEED 40 PERCENT OF INTERIOR CROSS SECTIONAL AREA WHERE THREE OR MORE CABLES ARE CONTAINED WITHIN A SINGLE CONDUIT. <br />3. CABLE MUST BE SEPARATED FROM ANY OPEN CONDUCTORS OF POWER, OR CLASS 1 CIRCUITS, AND SHALL NOT BE PLACED IN ANY CONDUIT, JUNCTION BOX OR RACEWAY CONTAINING THESE <br />CONDUCTORS. <br />B. WIRE: <br />1. ALL FREE -WIRED FIRE ALARM WIRING SHALL BE FPL TYPE CABLE. WIRING INSTALLED IN CONDUIT SHALL BE A MINIMUM OF THHN. UNDERGROUND WIRE SHALL BE INSTALLED IN <br />CONDUIT AND SHALL BE A MINIMUM OF THWN. <br />2. WIRING WILL BE IN ACCORDANCE WITH LOCAL, STATE AND NATIONAL CODES (E.G., NEC ARTICLE 760). THE NUMBER AND SIZE OF CONDUCTORS SHALL BE AS INDICATED ON THESE PLANS, <br />BUT SHALL NOT BE LESS THAN #18 AWG FOR INITIATING DEVICE CIRCUITS (INCLUDING SIGNALING LINE CIRCUITS) AND #16 AWG FOR NOTIFICATION DEVICE CIRCUITS. <br />3. ALL FIELD WIRING OF INITIATION AND NOTIFICATION CIRCUITS ARE TO BE COMPLETELY SUPERVISED BY END OF LINE DEVICES, PER THE MANUFACTURER'S LITERATURE. <br />4. HORIZONTAL WIRE RUNS ABOVE CEILINGS: HORIZONTAL WIRE RUNS IN AREAS CONTAINING DROP CEILINGS MAY BE 'FREE -WIRED' IF SUPPORTED BY THE BUILDING STRUCTURE. LAYING WIRE ON <br />THE CEILING OR INADEQUATE SUPPORT OF WIRING FROM THE STRUCTURE WILL NOT BE ALLOWED. <br />5. VERTICAL AND HORIZONTAL WIRE RUNS IN OPEN STRUCTURE AREAS: ALL WIRING IN "OPEN STRUCTURE AREAS" ON THIS PROJECT SHALL BE INSTALLED IN CONDUIT. <br />6. VERTICAL WIRE RUNS: VERTICAL WIRE RUNS TO DEVICES, PANELS, ANNUNCIATORS, ETC. SHALL BE INSTALLED IN CONDUIT PER THE NATIONAL ELECTRICAL CODE. <br />C. TERMINAL BOXES, JUNCTION BOXES AND CABINETS: ALL BOXES AND CABINETS SHALL BE UL LISTED FOR THEIR USE AND PURPOSE. <br />D. THE FIRE ALARM CONTROL PANEL IS TO BE CONNECTED TO A SEPARATE DEDICATED BRANCH CIRCUIT, MAXIMUM 20 AMPERES. THIS CIRCUIT SHALL BE LABELED AT THE MAIN POWER <br />DISTRIBUTION PANEL AS FIRE ALARM. FIRE ALARM CONTROL PANEL PRIMARY POWER WIRING SHALL BE 12 AWG. THE CONTROL PANEL ',CABINET SHALL BE GROUNDED SECURELY TO <br />EITHER A COLD WATER PIPE OR GROUNDING ROD. A 120 VOLT SURGE SUPPRESSER SHALL BE INSTALLED ON THE AC POWER AND GROUNDED PRIOR TO ENTERING THE FIRE ALARM <br />CONTROL PANEL. THE BREAKER FOR THE ALARM CIRCUIT SHALL BE RED IN COLOR, OR PAINTED RED, SHALL BE ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL, AND SHALL BE <br />IDENTIFIED WITH A PERMANENT LABEL AS "FIRE ALARM CIRCUIT". THE LOCATION OF THE DISCONNECTING MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM CONTROL <br />UNIT VIA A LABEL INSIDE THE FACP COVER. <br />IV. EXECUTION <br />A. INSTALLATION: <br />1. INSTALLATION SHALL BE IN ACCORDANCE WITH THE NEC, NFPA 72, LOCAL AND STATE CODES, AS SHOWN ON THE DRAWINGS, AND AS RECOMMENDED BY THE MAJOR EQUIPMENT <br />MANUFACTURER. <br />2. DURING CONSTRUCTION MEASURES SHALL BE TAKEN TO IPROTECT SMOKE DETECTORS FROM CONTAMINATION AND PHYSICAL DAMAGE UNTIL CONSTRUCTION ACTIVITIES ARE COMPLETE. <br />V. PROGRAMMING <br />1. A BASELINE PROGRAMMING MATRIX HAS BEEN INCLUDED ON THESE PLANS. <br />2. ALL SMOKE DETECTORS SHALL BE PROGRAMMED FOR ALARM VERIFICATION. <br />VI. TESTING & FINAL INSPECTION <br />1. SEE "FIRE ALARM SYSTEM TESTING, INSPECTION, INSTRUCTION" NOTES ON THIS SHEET FOR MINIMUM REQUIREMENTS. <br />VII. SYSTEM MONITORING <br />1. ALARM, SUPERVISORY, AND TROUBLE SHALL BE MONITORED VIA A REMOTE SUPERVISING STATION, AS INDICATED ON THESE PLANS. <br />VIII. GENERAL <br />1. THE VOLTAGE DROP CALCULATIONS SHOWN ON THE PLANS ARE BASED ON THE CIRCUIT ROUTING SHOWN. MAJOR CHANGES TO THE CIRCUIT ROUTING SHOWN MAY NEED TO BE JUSTIFIED BY <br />THE FIRE ALARM CONTRACTOR WITH ADDITIONAL CALCULATIONS. <br />2. THE ALARM CONTRACTOR WILL BE REQUIRED TO SUBMIT A "RECORD OF COMPLETION", PER NFPA 72, TO THE OWNER PRIOR TO FINAL PAYMENT. <br />3. THE FIRE ALARM CONTRACTOR IS REQUIRED TO MAINTAIN A COMPLETE AND ACCURATE AS -BUILT DRAWING SET. UPON FINAL COMPLETION OF THE PROJECT, THE FIRE ALARM CONTRACTOR SHALL <br />SUPPLY THE OWNER WITH AN AS -BUILT SET. AS-BUILTS SHALL INDICATE ALL CHANGES TO THE ORIGINAL LAYOUT INCLUDING, BUT NOT <br />NECESSARY LIMITED TO, AS -BUILT DEVICE LOCATIONS, PANEL LOCATIONS, CIRCUIT ROUTING, CONDUIT ROUTING, JUNCTION BOX LOCATIONS, PANEL CIRCUIT BREAKER LOCATIONS, ETC. <br />4. ALL CONDUIT AND WIRING PENETRATIONS THROUGH FIRE RATED BARRIERS (INCLUDING WALLS AND FLOORS), AND SMOKE BARRIERS THAT EXTEND FROM FLOOR TO CEILING, SHALL BE SEALED <br />WITH A UL LISTED FIRESTOPPING PENETRATION SYSTEM. THE MINIMUM PENETRATION RATING FOR FIRE RATED BARRIERS SHALL MATCH THE RATING OF THE WALL \ FLOOR \ BARRIER. SMOKE <br />BARRIERS SIMPLY NEED TO BE SEALED TO PREVENT THE PASSAGE OF SMOKE THROUGH THE ASSEMBLY. <br />5. PRIOR TO FINAL PROJECT COMPLETION, ALL DEVICES SHALL BE LABELED ON THEIR EXTERIOR HOUSING SO THAT THE DEVICE NUMBER CAN BE DETERMINED BY VISUAL INSPECTION. ALL FIRE <br />ALARM DEVICES, INCLUDING BUT NOT LIMITED TO DETECTORS, MODULES, HORNS, SPEAKERS, AND STROBES, $HALL HAVE A LABEL AFFIXED TO THEIR FRONT SURFACE. THESE LABELS SHALL <br />CONFORM TO THE FOLLOWING: <br />I. THE LABELS SHALL HAVE LETTERS AT LEAST 1/4" HIGH. <br />II. THE LABELS SHALL MATCH THE DEVICE NUMBER SHOWN ON THE AS -BUILT DRAWINGS. <br />111. THE LABELS SHALL BE IDENTICAL TO THE DEVICE NUMBER PROGRAMMED INTO AND DISPLAYED ON THE FACP AND ALL REMOTE ANNUNCIATORS. <br />AT THE FINAL INSPECTION A FACTORY TRAINED REPRESENTATIVE OF THE INSTALLER SHALL DEMONSTRATE THAT THE SYSTEMS FUNCTION PROPERLY IN EVERY RESPECT. ALL TESTING SHALL <br />BE COMPLETED IN ACCORDANCE WITH NFPA 72. THE LOCAL FIRE AUTHORITY HAVING JURISDICTION, OR THEIR ASSIGNED REPRESENTATIVE, SHALL WITNESS THE SYSTEM TESTING. <br />FIRE ALARM SYSTEM TESTING <br />A. PROVIDE THE SERVICE OF A COMPETENT, FACTORY -TRAINED ENGINEER OR TECHNICIAN AUTHORIZED BY THE MANUFACTURER OF THE FIRE ALARM EQUIPMENT TO TECHNICALLY <br />SUPERVISE AND PARTICIPATE DURING ALL OF THE ADJUSTMENTS AND TESTS FOR THE SYSTEM. REPRESENTATIVE MUST BE STATE CERTIFIED FIRE ALARM CONTRACTOR/INSTALLER. <br />1. BEFORE ENERGIZING THE CABLES AND WIRES, CHECK FOR CORRECT CONNECTIONS AND TEST FOR SHORT CIRCUITS, GROUND FAULTS, CONTINUITY, AND INSULATION. <br />2. CLOSE EACH SPRINKLER SYSTEM FLOW VALVE AND VERIFY PROPER SUPERVISORY ALARM AT THE FACP. <br />3. VERIFY ACTIVATION OF ALL FLOW SWITCHES. <br />4. OPEN INITIATING DEVICE CIRCUITS AND VERIFY THAT THE TROUBLE SIGNAL ACTUATES. <br />5. OPEN AND SHORT SIGNALING LINE CIRCUITS AND VERIFY THAT THE TROUBLE SIGNAL ACTUATES. <br />6. OPEN AND SHORT INDICATING APPLIANCE CIRCUITS AND VERIFY THAT TROUBLE SIGNAL ACTUATES. <br />7. GROUND ALL CIRCUITS AND VERIFY RESPONSE OF TROUBLE SIGNALS. <br />8. CHECK PRESENCE AND AUDIBILITY OF TONE AT ALL ALARM NOTIFICATION DEVICES. <br />9. CHECK EACH STROBE DEVICE TO VERIFY THAT THE SELECTABLE STROBE OUTPUT HAS BE SET AT THE PROPER CANDELA RATING, AS SHOWN ON THE PLANS. <br />10. CHECK INSTALLATION, SUPERVISION, AND OPERATION OF ALL INTELLIGENT SMOKE DETECTORS USING THE WALK TEST. <br />11. POWER LOSS TESTING SHALL BE PERFORMED IN ACCORDANCE WITH NFPA 72. TEST LOSS OF PRIMARY POWER AND SYSTEM RESPONSE, AS REQUIRED BY NFPA 72 (2016), <br />CHAPTER 14. <br />12. EACH OF THE ALARM CONDITIONS THAT THE SYSTEM IS REQUIRED TO DETECT SHOULD BE INTRODUCED ON THE SYSTEM. VERIFY THE PROPER RECEIPT AND THE PROPER <br />PROCESSING OF THE SIGNAL AT THE FACP AND THE CORRECT ACTIVATION OF THE CONTROL POINTS. <br />13. WHEN THE SYSTEM IS EQUIPPED WITH OPTIONAL FEATURES, THE MANUFACTURER'S MANUAL SHOULD BE CONSULTED TO DETERMINE THE PROPER TESTING PROCEDURES. THIS IS <br />INTENDED TO ADDRESS SUCH ITEMS AS VERIFYING CONTROLS PERFORMED BY INDIVIDUALLY ADDRESSED OR GROUPED DEVICES, SENSITIVITY MONITORING, VERIFICATION <br />FUNCTIONALITY AND SIMILAR. <br />14. FINAL TESTING SHALL BE IN THE PRESENCE OF THE LOCAL FIRE MARSHALL, OR FIRE INSPECTOR, AND WARRANTY SHALL BEGIN ON DATE OF ACCEPTANCE BY LOCAL FIRE <br />MARSHALL. <br />FINAL INSPECTION <br />A. AT THE FINAL INSPECTION A FACTORY TRAINED REPRESENTATIVE OF THE MANUFACTURER OF THE [MAJOR EQUIPMENT SHALL DEMONSTRATE THAT THE SYSTEMS FUNCTION PROPERLY <br />IN EVERY RESPECT. REPRESENTATIVE SHALL BE A STATE CERTIFIED FIRE ALARM CONTRACTOR/INSTALLER. <br />INSTRUCTION <br />A.PROVIDE INSTRUCTION, AS REQUIRED, FOR OPERATING THE SYSTEM. "HANDS-ON" DEMONSTRATION OF THE OPERATION OF ALL SYSTEM COMPONENTS SHALL BE PROVIDED. <br />B. THE CONTRACTOR, AND/OR THE SYSTEMS MANUFACTURER'S REPRESENTATIVE, SHALL PROVIDE A TYPE WRITTEN "SEQUENCE OF OPERATION" TO THE OWNER. PROVIDE A COPY OF <br />THE "SEQUENCE OF OPERATION" AT EACH FACP LOCATION. <br />C. THE CONTRACTOR SHALL PROVIDE A DEVICE LAYOUT SKETCH AT AT EACH FIRE ALARM CONTROL PANEL, TO INDICATE FLOOR PLAN, FIRE ALARM DEVICE LOCATION, ADDRESS AND <br />DEVICE LEGEND FOR EASE OF ALARM LOCATION. THE FIRE ALARM FLOOR PLAN SHALL BE MOUNTED IN A FRAME. <br />FIRE ALARM DEVICE LEGEND <br />SYMBOL <br />QTY <br />DEVICE DESCRIPTION <br />MAKE / MODES <br />DEVICE SPECIFIC NOTES <br />CIO <br />w <br />Z <br />m <br />U <br />FACP <br />1 <br />FIRE ALARM CONTROL PANEL <br />SILENT KNIGHT 6808 <br />Z <br />® <br />1 <br />CELL / ID COMMUNICATOR <br />NAPCO STARLINK <br />DIALER PROVIDED BY OTHERS <br />a <br />z <br />0 <br />Q <br />1 <br />WEATHERPROOF <br />P2RK <br />DEVICE TO BE 'RED' <br />I <br />WP <br />HORN / STROBE (WALL MOUNTED) <br />O <br />z <br />0 <br />Of <br />2 <br />MANUAL PULL STATION <br />SK-PULL-SA <br />INSTALL AT 48" AFF <br />z <br />0 <br />v_ <br />11 <br />PHOTOELECTRIC SMOKE DETECTOR <br />SK-PHOTO-W <br />CEILING MOUNTED DEVICES TO BE 'WHITE' <br />Z <br />`''P <br />Q�F <br />2 <br />135' FIXED HEAT DETECTOR <br />SK-HEAT-W <br />CEILING MOUNTED DEVICES TO BE 'WHITE' <br />Z <br />®WP <br />2 <br />WEATHERPROOF 135' FIXED HEAT <br />302 SERIES <br />INSTALLED IN ELEVATOR PIT <br />F <br />DETECTOR <br />AIM <br />16 <br />ADDRESSABLE MONITOR MODULE <br />SK-MONITOR, SK-MONITOR2 <br />MOUNT WITH -IN 3 FEET OF INTERFACE POINT <br />O® <br />8 <br />ADDRESSABLE RELAY MODULE <br />SK-RELAY <br />MOUNT WITH -IN 3 FEET OF AHU INTERFACE POINT <br />C3 <br />p <br />FLOW SWITCH <br />TAMPER SWITCH <br />-JVVL- <br />END -OF -LINE RESISTOR (EOL) <br />SUPPLIED BY PRODUCT VENDOR INSTALLED AT END OF CIRCUIT LINE <br />8-0 <br />SURGE SUPPRESSOR <br />❑K <br />KNOX BOX <br />❑J <br />JUNCTION BOX <br />FIRE ALARM ABBREVIATIONS LEGEND <br />AH <br />= AIR HANDLER <br />MAX = MAXIMUM <br />C <br />= CEILING MOUNTED <br />MIN = MINIMUM <br />COR <br />= CONTRACTING OFFICER REPRESENTATIVE <br />MNS = MASS NOTIFICATION SYSTEM <br />EXT <br />= EXISTING <br />N/A = NOT APPLICABLE <br />WP <br />= WEATHERPROOF <br />NAC = NOTIFICATION APPUANCE CIRCUIT <br />XP <br />= EXPLOSION PROOF <br />NDU = NETWORK DISPLAY UNIT <br />AFF <br />= ABOVE FINISHED FLOOR <br />NEC = NATIONAL ELECTRIC CODE <br />AHJ <br />= AUTHORITY HAVING JURISDICTION <br />NFPA = NATIONAL FIRE PROTECTION ASSOCIATION <br />ALM <br />= ALARM <br />NIC = NOT IN CONTRACT <br />ANN <br />= ANNUNCIATOR <br />NTS = NOT TO SCALE <br />BMS <br />= BUILDING MANAGEMENT SYSTEM <br />PAP = PRE -ACTION PANEL <br />CD <br />= (eg. 15CD) CANDELA <br />PED = PHOTOELECTRIC SMOKE DETECTOR <br />CSFM <br />= CALIFORNIA STATE FIRE MARSHAL <br />SLC = SIGNALING LINE CIRCUIT <br />DET <br />= DETECTOR <br />SMK = SMOKE <br />EOL <br />= END OF LINE <br />SUPV = SUPERVISORY <br />EPO <br />= EMERGENCY POWER OFF <br />TRBL = TROUBLE <br />FACP <br />= FIRE ALARM CONTROL PANEL <br />IS = TAMPER SWITCH <br />FATC <br />= FIRE ALARM TERMINAL CABINET <br />TYP = TYPICAL <br />FBO <br />= FURNISHED BY OTHERS <br />UFC = UNIFIED FACILITIES CRITERIA <br />FCC <br />= FIRE COMMAND CENTER <br />LINO = UNLESS NOTED OTHERWISE <br />FAA <br />= FIRE ALARM ANNUNCIATOR <br />VCC = VOICE COMMAND CENTER <br />FSD <br />= FIRE SMOKE DAMPER <br />WF = WATER FLOW <br />HT <br />= HEIGHT <br />W = WATT <br />HVAC <br />= HEATING, VENTILATION, & AIR CONDITIONING <br />W/ = WITH <br />IDC <br />= INITIATION DEVICE CIRCUIT <br />W/O = WITHOUT <br />IMS <br />= INFORMATION MANAGEMENT SYSTEM <br />z <br />O <br />In <br />Li <br />O_ <br />w <br />Q <br />0 <br />O <br />z <br />�ocs a���.,, <br />••'' <br />�''•��2' <br />=Z <br />* <br />W <br />:U <br />Q O'Z= <br />F <br />tn <br />v C:4- <br />N O <br />O <br />m <br />0 O O <br />.a1 <br />Li <br />>, V <br />N <br />O <br />ro 4- T <br />!V � <br />`- <br />Q <br />W <br />0 <br />O <br />z <br />a �F zrzwa�}�., <br />N o�z��wWNau' <br />2w�¢ Ou, o a�OU <br />s <br />zowz <br />w} Z z O <br />c-7 °'wwazwo¢ =n�F <br />zz��ozw�>u <br />z 3 z m <br />w -'n�_z �mw w= <br />_8 o <br />�I <br />of <br />rt <br />a <br />U <br />Z <br />Q <br />a <br />m <br />L <br />V' <br />Y ^ n <br />Z <br />LL <br />�I <br />Fy <br />_J <br />LLI <br />p9 <br />ui <br />Z <br />Z a <br />R <br />mh b^ <br />�E� <br />m <br />a <br />NSb� <br />nyOti <br />U <br />w <br />a <br />U <br />Z <br />Z <br />U <br />w <br />n <br />lb <br />g <br />t <br />< <br />m`°Q.°' <br />% <br />T <br />y�i I" <br />2m <br />r'l <br />WN�N^ <br />O <br />q, <br />T <br />m <br />U <br />C <br />w <br />w <br />F <br />3Cim� <br />ii <br />U <br />a <br />[ <br />w <br />3 <br />a <br />w <br />0 <br />V <br />z <br />� n � <br />morn <br />3!* <br />n* <br />om <br />T 7 <br />O� <br />myrn <br />S <br />n <br />�> <br />MrNl� <br />>7 <br />m <br />-�4 O <br />fV <br />r it <br />Ip Ip - <br />2 <br />ni <br />Q <br />,� rlll <br />Q <br />M <br />W m U_ <br />M <br />Q,>rn <br />03 4t m 11, <br />1- m A <br />0 <br />Jza 0 <br />a.. m <br />w <br />Q � <br />OLn <br />O <br />T M J <br />fV O <br />rZ <br />a <br />0 <br />U <br />Z <br />0 <br />Q <br />0 <br />L0 <br />w <br />O <br />EL <br />EL <br />Ld <br />FIRE ALARM DRAWING LEGEND <br />SHEET # <br />DESCRIPTION <br />FAO <br />FIRE ALARM GENERAL NOTES AND SPECIFICATIONS <br />FAt <br />FIRE ALARM PLAN FIRST FLOOR <br />FA2 <br />FIRE ALARM PLAN SECOND FLOOR <br />FA3 <br />FIRE ALARM PLAN THIRD FLOOR <br />FA4 <br />FIRE ALARM DETAILS <br />FA5 <br />FIRE ALARM RISER DIAGRAM AND •CALCULATIONS <br />Lw <br />(10 <br />Ld <br />Z <br />LLI <br />I - <br />O <br />zz <br />a <br />O Q <br />� <br />>M <br />�0 <br />LLI <br />LL,Q <br />F- <br />j -� <br />o u- <br />W U <br />m <br />Z <br />o <br />_j_ <br />a= <br />Ld - <br />Caw <br />o <br />(D <br />N = <br />c�° <br />LLI <br />g <br />fb � <br />Q Q <br />T <br />J <br />LLI <br />LL_ <br />u <br />w <br />U <br />C W <br />a p <br />DESIGNED BY <br />AGO <br />DRAWN BY <br />AGO <br />CHECKED BY <br />RWL <br />PROJECT NO./CAD CODE <br />2023-2601 <br />DATE <br />06/27/2023 i <br />DRAWING NO. <br />FAO <br />ME <br />w <br />