ELECTRICAL SYMBOLS
<br />LEGEND
<br />10-m.10 ESM
<br />(SYMBOLS APPLY ONLY WHEN USED ON DRAWINGS)
<br />SYMBOL
<br />DESCRIPTION
<br />/ O
<br />FLUORESCENT / LED OR HID FDCTURE
<br />(WALL MOUNTED/CEILING MOUNTED)
<br />10
<br />FLUORESCENT/ LED FIXTURE
<br />®
<br />FLUORESCENT I LED FIXTURE,
<br />NIGHT LIGHT
<br />®
<br />VOLUMETRIC LED FIXTURE
<br />O
<br />ENCLOSED FREEZER LIGHT
<br />NZ
<br />Aa
<br />TRACK LIGHTING
<br />/ ®
<br />EXIT FIXTURE
<br />(WALL MOUNTED)
<br />EMERGENCY LIGHT
<br />(KA-L MMOLNTED)
<br />SINGLE POLE SWITCH
<br />$3
<br />3-WAY SWITCH
<br />$4
<br />4-WAY SWITCH
<br />$K
<br />KEYED SWITCH
<br />4D
<br />DIMMERSWITCH
<br />*VS
<br />VARIABLE SPED SWITCH
<br />4m
<br />MANUAL MOTOR SWITCH
<br />SINGLE POLE OCCUPANCY
<br />SENSOR SWITCH
<br />DOUBLE POLE OCCUPANCY
<br />SENSOR SWITCH
<br />l
<br />CEILING MOUNTED OCCUPANCY
<br />RECEPTACLE, DUPLEX
<br />RECEPTACLE, DUPLEX,
<br />MOUNTED HORIZONTALLY
<br />RECEPTACLE, GFI
<br />®
<br />RECEPTACLE, DUPLEX FLUSH FLOOR
<br />®
<br />RECEPTACLE, DUPLEX. ISOLATED
<br />GROUND FLUSH FLOOR
<br />RECEPTACLE, DOUBLE DUPLEX
<br />x
<br />V
<br />RECEPTACLE, DUPLEX
<br />ISOLATED GROUND
<br />RECEPTACLE, DOUBLE DUPLEX,
<br />ISOLATED GROUND
<br />RECEPTACLE, SIMPLEX TWIST LOCI,
<br />L5-15R, UNO
<br />RECEPTACLE, SIMPLEX TWIST LOCK,
<br />ISOLATED GROUND, 1-5-1511, UNO
<br />RECEPTACLE, DUPLEX TWIST LOCK,
<br />1-5-15R, UNO
<br />RECEPTACLE, DUPLEX TWIST LOCK,
<br />ISOLATED GROUND, L5-15R, LINO
<br />RECEPTACLE, SPECIAL
<br />d)
<br />RECEPTACLE, SIMPLEX
<br />�111
<br />RECEPTACLE, PLUG -MOLD
<br />O
<br />JUNCTION BOX
<br />(WALL- MOUNTED)
<br />O
<br />I RMOSTAT
<br />(WALL MOUNTED/CEILING MOUNTED)
<br />�!
<br />ALARM JUNCTION BOX,
<br />(WALL MOUMEDICERM MOUNTED)
<br />ALARM JUNCTION BOX,
<br />®
<br />FOR REMOTE TEST/RESET
<br />(WALL MOUNTEDICEILING MOUNTED)
<br />0
<br />EQUIPMENT CONNECTION POINT
<br />(PROVIDED WITH EQUIPMENT)
<br />NOWFUSED DISCONNECT
<br />Ell
<br />FUSED DISCONNECT
<br />CIRCUIT, CONCEALED N WNL.LS OR
<br />CEILING, E INDICATES EXISTING
<br />WIRING
<br />CIRCUIT, CONCEALED N SLAB FLOOR,
<br />E INDICATES EXISTING WIRNG
<br />CIRCUIT, EXPOSED,
<br />-�T
<br />E INDICATES EXISTING WIRING
<br />1--t
<br />CONDUIT SLEEVE
<br />=
<br />FLASH MOUNTED PANELBOARD
<br />SURFACE MOUNTED PANELBOARD
<br />+------
<br />MANUFACTURED WRING SYSTEM
<br />-
<br />TELEPHONE / DATA BOX FOR ISD
<br />LOW VOLTAGE CABLE
<br />BOX FOR OTHER
<br />m
<br />TELEPHONE, FLUSH FLOOR
<br />O
<br />MOTOR
<br />0
<br />TELEPOWE2 POLE
<br />4
<br />PUSH BUTTON
<br />aBUZZER
<br />SAIL SWITCH
<br />JUNCTION BOX
<br />SO
<br />SMOKE DETECTOR
<br />HORNISTROBE
<br />®
<br />DOOR HOLD OPEN
<br />ABBREVIATIONS
<br />CF (SING FAN
<br />Co CHECK OUT
<br />CW CASHWRAP
<br />EF EXHAUST FAN
<br />ETR EXISTING TO REMAIN
<br />G GROUND
<br />GFI GROUND FAULT CIRCUIT INTERRUPTER
<br />IG ISOLATED GROUND
<br />REC REFRIGERATION ELECTRICAL CONTRACTOR
<br />RC REFRIGERATION CONTRACTOR
<br />RH RADIANT HEATER
<br />Sc SECURITY CAMERA
<br />TR TAMPER RESISTANT
<br />U H UNIT HEATER
<br />WH WATER HEATER
<br />WP WEATHER PROOF COVERPLATE
<br />WR WEATHER RESISTANT RECEPTACLE
<br />O
<br />RELOCATE LIGHT SWITCH TO
<br />V1ALL AND RECONNECT TO
<br />EXISTING LIGHTING CIRCUIT
<br />1
<br />I
<br />3C F��
<br />SEAFOOD INTERNAL HIGH POWER PLAN
<br />10=1'4r
<br />KEY PLAN
<br />1 11W _ V4r
<br />ELECTRICAL KEYNOTES
<br />16.4V E.C. SHALL COORDINATE WffH GENERAL
<br />CONTRACTOR AND ARCI-IITECTURAL
<br />DEMOLITION PLANS THE EXTENT OF
<br />EECTRICAL DEMOLITION_ REAAOVE
<br />CONDIATS AND WIRES ALL THE WAY BACK TO
<br />ORIGINATING JUNCTION BOXES OR
<br />PN*jXV DS- DEMOLITION SHALL NOT
<br />AFFECT ACTIVECVZCUR& LABEL -
<br />DEMOLISHED CIRCUTP N PANE EX) ARDS
<br />AS'SPAW- COORDINATE EXACT
<br />REOLAtEMENTS WITH EXISTING CONDITIONS
<br />PRIOR TO BID.
<br />16_W04 120 VOLT GENERAL PO W R CIRCUIT(S):
<br />FURNISH AND INSTALL NEW 20 AMP,12D VOLT
<br />CRCxUIT(S), OR AS SPECIFIED ON DRAWINGS
<br />Fib FROM NEAREST 120 VOLT PANEL, WITH
<br />ADEQUATE SPACE AND AMPACTTY. A CIRCUIT
<br />BAKER FOR CIRCUITS INDICTED WITH
<br />(GFI) SHALL BE GFCI TYPE FOR PERSONNEL
<br />PROTECTION_
<br />16.W07 208 VOLT GENERAL POWER CIRCUIT:
<br />FURNISH AND INSTALL NEW 208 VOLT
<br />CIRCUIT, AS SPECIFIED ON DRAWINGS. FEED
<br />FROM NEAREST 208 VOLT PANEL, WITH
<br />ADEQUATE SPACE AND AAMPACITY.
<br />GENERAL POWER NOTES
<br />1 TELEPO NM POLE(S): MOUNT JUNCTION BOX(ES) TO TOP
<br />SIDE OF BOTTOM CHORD OF BAR JOIST_ INSTALL
<br />FURNISH® PRE -WIRED POWER POLE AND TERMINATE
<br />PROVIDED FLEXIBLE CONDUIT AND WIRING TO JUNCTION
<br />BOX. PROVIDE UNISTRUT SUPPORTS AND HARDWARE TO
<br />SECURE TE EPOWER POLE PL.LI B TO BUILDING
<br />STRUCTURE
<br />2- PROVIDE LIQUID:nGHT FLEXIBLE METAL CONDUIT AND
<br />WIRING FROM DISCONNECT SWITCH OR JUNCTION BOX TO
<br />EQUIPMENT KNOCKOUT OR ELECTRICAL CONNECTION
<br />POINT.
<br />3- WIBRE ErQI>pMENT NAMEPLATE PROTECTIVE DEVICE
<br />RATING DEFERS FROM S12E PROVIDED, CHANGE OUT
<br />BRANCH! CIRCUIT WIRING AND OVERCURRENT DEVICE TO
<br />APPROPRIATE RATING PER NEC.
<br />4- ELECTRONIC FIRE PRoTEcTnvsEGuRrry ALARM BOXES
<br />AND CONDUITS SHOWM ON POWER PLANS SHALL BE
<br />PROVIDED UNDER THIS CONTRACT. N ADDITION, UNLESS
<br />NOTED OTHERWISE, THE FOLLOWING GENERAL NOTES
<br />APPLY:
<br />A- ALL ALARM JUNCTION BOXES SHALL BE
<br />4'C4'X2-1/8' MINIMUM.
<br />B- ALARM RACEWAYS SHALL BE 314' MINIMUM WITH
<br />PILL VdRE AND NSt"TNG BUSHINGS AT END OF
<br />VERTICAL RA(EV1AY RUN.
<br />C- VERTICAL RACEWAYS FROM ALARM BOXES SHALL BE
<br />EITHER CONCEALED INSIDE WAALL OR SURFACE
<br />MOUNTED (TO MATCH JUNCTION BOX MOUNTING). ALL
<br />VERTICAL RUNS SHALL BE TURNED 900EGREES AT
<br />TOP SIDE OF BOTTOM CHORD OF BAR JOIST AND
<br />EXTENDED HORIZONTALLY TO A LOCATION ACCESSIBLE
<br />BY VERTICAL FLOOR TYPE LIFT.
<br />5- UPON COMPLETION OF ELECTRICAL INSTALLATION AND
<br />PRIOR TO ENERGIZING CRCUIT-
<br />A- INSPECT WIRE AND CABLE FOR PHYSICAL DAMAGE.
<br />B- PERFORM CONTNUITY TEST.
<br />C- VERIFY PROPER PHASING CONNECTION TO ALL THREE
<br />PHASE MOTOR LOADS.
<br />20A WIRE SIZING SCHEDULE
<br />ALL WIRE SIZES SHOWN ON PANEL SCHEDULES AND
<br />PLANS ARE INTENDED TO BE MINMALIIM ACCEPTABLE
<br />WIRE SIZE -
<br />THE FOLLOWING SCHEDULE IS TO BE USED TO SIZE
<br />WIRE FOR 20 AMP CIRCUITS (120 AND 277 VOLT).
<br />LENGTHS; (N FEET) ARE INTENDED TO BE MAXIMUM.
<br />FINAL CONNECTIONS: WHERE 20A BRANCH CIRCUITS
<br />HAVE 08 AND LARGER WIRE CALLED OUT, #10AWG WIRE
<br />MAY BE USED FOR THE FINAL CONNECTION (16 MAX.)_
<br />12D VOLT
<br />#12
<br />#10
<br />#8
<br />#6
<br />1S AMPS
<br />200 FT.
<br />325 FT.
<br />4W FT.
<br />7T0 HT.
<br />6-10 AMPS
<br />100 FT.
<br />160 FT.
<br />245 FT.
<br />385 FT.
<br />1145 AMPS
<br />70 FT.
<br />110 FT.
<br />165 FT.
<br />255 FT.
<br />277 VOLT
<br />#12
<br />#10
<br />#8
<br />#6
<br />1S AMPS
<br />4W FT.
<br />760 FT.
<br />1170 FT.
<br />1865 FT.
<br />6-10 AMPS
<br />240 FT.
<br />380 FT.
<br />585 FT.
<br />930 FT.
<br />11-15 AMPS
<br />160 FT.
<br />250 FT.
<br />390 FT.
<br />620 FT.
<br />GENERAL NOTES
<br />06.31.12 EN08
<br />1- FURNISH AND INSTALL ALL MATERIALS, EQUIPMENT, AND
<br />LABOR, FOR A COMPLETE INSTALLATION IN ALL RESPECTS,
<br />READY FOR INTENDED USE AND IN STRICT ACCORDANCE WITH
<br />NEC, NESC, STATE, AND LOCAL CODES, AND MANUFACTURERS
<br />RECOMMENDATIONS. PAY ALL NECESSARY FEES AND PERMITS.
<br />A. NO CIRCUITRY SHALL BE ALLOWED TO BE ROUTED ACROSS
<br />THE ROOF OR THE EXTERIOR SIDE OF THE EXTERIOR
<br />WVALL.S.
<br />B. ALL EQUIPMENT SHALL BE UL LISTED WHERE APPLICABLE
<br />C. ARRANGE ALL WORK TO MINIMIZE DISRUPTIONS TO STORE
<br />OPERATIONS. COORDINATE ALL DISRUPTIONS WITH
<br />WWLMART CONSTRUCTION MANAGER AND STORE MANAGER.
<br />D. CONTRACTOR SHALL VERIFY ALL WALL FINISH THICKNESSES
<br />BEFORE INSTALLING BOXES. FURNISH AND INSTALL
<br />EXTENDED BOXES OR BOX EXTENDERS WHERE REQUIRED.
<br />E- CONTRACTOR SHALL VERIFY THAT ALL AFFECTED
<br />PANEBOARDS HAVE CIRCUIT BREAKER KNOCKOUTS
<br />PROPERLY COVERED AND THAT ALL TRIM IS IN GOOD
<br />CONDITION, ALLOWING NO ACCESS TO LIVE PARTS.
<br />2- PROVIDE SEALS AT RACEWAY PENETRATIONS AS FOLLOWS:
<br />A- FIRE RATED WALLS- SEAL PER SPECIFICATIONS FOR FIRE
<br />STOPPING.
<br />B NEUTRALIZATION AREA: SEAL PER MECHANICAL DETAIL
<br />C FREEZERCOOLER BOXES: SEAL WITH EXPANDING FOAM
<br />SEALANT.
<br />D- EXTERIOR: REFER TO ARCHITECTURAL DOCUMENTS FOR
<br />SEALING REQUIREMENTS AT ALL EXTERIOR MOUNTED
<br />DEVICES, FIXTURES, ENCLOSURES, AND RACEWAY
<br />PENETRATIONS.
<br />3- PROVIDE A SEPARATE EQUIPMENT GROUNDING CONDUCTOR
<br />(SIZE PER NEC) N PVC TYPE CONDUIT, POWER CIRCUITS,
<br />ISOLATED GROUND CIRCUITS, OR AS SHOWN ON PLANS.
<br />CONDUIT SHALL BE SIZED PER NEC BASED ON THWN 600
<br />VOLT COPPER SINGLE CONDUCTORS, PLUS THE EQUIPMENT
<br />GROUNDING CONDUCTOR
<br />4- WIRING DEVICES: DEVICE MOUNTING HEIGHTS ARE FROM
<br />FINISHED FLOOR TO CENTER OF OUTLET BOX UNLESS NOTED
<br />OTHERWISE ON PLANS. COORDINATE THE STANDARD
<br />MOUNTING HEIGHTS WITH MASONRY:
<br />A. SWITCHES +46'
<br />B. RECEPTACLES +20'
<br />C. VOK;F"TA +20'
<br />5- WIRING SHALL INCLUDE FINAL CONNECTION TO ALL EQUIPMENT
<br />IN CONFORMANCE WITH EQUIPMENT SUPPLIER WIRING
<br />DIAGRAMS.
<br />6- CONTRACTOR IS RESPONSIBLE FOR PROVIDING COMPLETE
<br />PANELBOARD IDENTIFICATION SCHEDULES FOR PANE BOARDS
<br />AFFECTED BY REMODEL-
<br />7- NEW OVERCURRENT PROTECTIVE DEVICES INSTALLED IN
<br />EXISTING PANELBOARDS OR DISTRIBUTION BOARDS SHALL
<br />MATCH THE TYPE AND AIC RATING OF EXISTING OVERCURRENT
<br />PROTECTIVE DEVICES
<br />8- BRANCH CIRCUIT CONDUCTORS SHALL BE MINIMUM #12 AWG THHN
<br />UNLESS NOTED OTHERWISE N SCHEDULES. WHERE 20A
<br />BRANCH CIRCUITS HAVE #8 AND LARGER WIRE SPECIFIED, #10
<br />AWG WIRE SHALL BE USED FOR THE FINAL CONNECTION
<br />(15-FT MAXIMUM)_
<br />9. WHERE BRANCH CIRCUITS ARE GROUPED, SIZE CONDUIT AND
<br />DERATE CURRENT CARRYING CONDUCTORS PER NEC.
<br />10. SUPPORTS FROM STRUCTURE: NO ATTACHMENT OF ANY TYPE
<br />SHALL BE MADE TO BRIDGING OR JOIST WEB MEMBERS.
<br />UTILIZE ONLY THE TOP AND BOTTOM CHORDS FOR
<br />SUPPORTING THE ELECTRICAL SYSTEM INSTALLATIONS.
<br />1i. DEVICES SHOWN ON COOLEWFREEZER PANELS SHALL BE
<br />SURFACE MOUNTED UNLESS NOTED OTHERWISE REFER TO
<br />ARCHITECTURAL DOCUMENTS FOR CONDUIT INSTALLATION AND
<br />SEALING REQUIREMENTS.
<br />12. ONLY FEEDER CIRCUITS NOTED ON THE ONE LINE DIAGRAM
<br />AND BRANCH CIRCUITS NOTED BY LEGEND SHALL BE
<br />INSTALLED UNDER SLAB. ALL OTHER FEEDER AND BRANCH
<br />CIRCUITS SHALL BE INSTALLED OVERHEAD. PROVIDE EXTERIOR
<br />COATED GRC BENDS ON ALL CONDUIT RUINS THAT HAVE 45
<br />DEGREE BENDS OR GREATER REF SPECIFICATIONS.
<br />13. SEISMIC ZONE REQUIREMENTS-. PROVIDE EXPANSION COUPLINGS
<br />AND BRACING FOR ELECTRICAL EQUIPMENT AS REQUIRED BY
<br />LOCAL CODES.
<br />14. EXISTING ELECTRICAL AND ALARM:
<br />A- WHERE DEMOLITION OR NEW INTERRUPTS
<br />EXISTING ELECTRICAL CIRCUITS FEEDING EXISTING
<br />EQUIPMENT, DEVICES, OR LIGHTING TO REMAIN, BUT NOT
<br />SHOWN ON DRAWINGS, PROVIDE LABOR AND MATERIALS TO
<br />REWORK CIRCUITRY, AS REQUIRED, TO MAINTAIN EXISTING
<br />OPERATION.
<br />B• IF DEMOLTION OR NEW CONSTRUCTION WILL DISRUPT
<br />EXISTING UNDERGROUND SERVICES (ELECTRICAL,
<br />TELEPHONE, PARKING LOT LIGHTING CIRCUITRY, ETC-)
<br />PROVIDE ALL MATERIALS AND LABOR AS REQUIRED TO
<br />REROUTE, SLEEVE, OR OTHERWISE REWORK THESE SERVICES
<br />TO MAINTAIN THEIR EXISTING OPERATION.
<br />C LSE CAUTION AROUND At AND SECURITY CABLES
<br />- EXERC
<br />DURING DEMOLITION AND CONSTRUCTION. PROTECT ALARM
<br />AND SECURITY CABLES FROM ACCIDENTAL DAMAGE SO
<br />THAT SYSTEMS REMAIN OPERATIONAL AT ALL TINES.
<br />D- DISPOSE OF ALL REMOVED MATERIALS, UNLESS OT'HERWWSE
<br />NOTED.
<br />15. EXISTING ELECTRICAL DEbbLf170N:
<br />A- GENERAL: REMOVE OR RELOCATE EXISTING ELECTRICAL
<br />EQUIPMENT CONDUIT, AND CONDUCTORS AS INDICATED ON
<br />THE DRAWINGS, OR ONLY AS REQUIRED BY DEMOLITION.
<br />SCO NE T SWITCHES BOXES
<br />0
<br />w m m%O Cw0Dy
<br />W p moMaz
<br />wTwww w 1a
<br />ix
<br />~Q���mam°am
<br />lL cFLI 0) aLLF?Wit Wi
<br />z 22 �am�00 rOZp
<br />O g 0 ogj`�fsa-
<br />$� 05 m�� I'i p
<br />D a luo aumn—wom
<br />IL
<br />pmo"'°�g` Sma°cmw S
<br />w x i nook-0 ww-wx
<br />Ego
<br />gZ■
<br />0
<br />� S
<br />Z
<br />z
<br />�_
<br />U
<br />�$
<br />z
<br />w
<br />O O
<br />w
<br />O C=
<br />OO
<br />J
<br />w
<br />O
<br />J
<br />M
<br />$
<br />Z
<br />1.i..
<br />0
<br />Z
<br />O
<br />N
<br />N
<br />w
<br />m
<br />D
<br />z
<br />O
<br />ISSUE BLOCK I
<br />CHECKED BY:
<br />SAG
<br />DRAWN BY:
<br />JOP
<br />FEE N
<br />E1
<br />PROTO CYCLE
<br />07/03/18
<br />DOCUMENT DATE:
<br />07/25/18
<br />REMOVE ALL PANELBOARDS, DI N C ,
<br />RELAYS, TIME SWITCHES, LIGHTS, DEVICES, ETC., WHICH
<br />WILL NOT BE REUSED.
<br />B. SALES FLOOR: REMOVE UNUSED POWER DROP CONDUIT,
<br />CONDUCTORS AND RELATED DEVICES SERVING SALES AREA
<br />GONDOLAS BEING RELOCATED OR REMOVED. EXISTING
<br />CONDUIT AND CONDUCTORS MAY BE REUSED FOR NEW
<br />POWER DROPS WHERE SIZE, RATING, AND CONDITION MEET
<br />REQUIREMENTS INDICATED ON PLANS AND ALL U.L RATINGS. REL40VE ALL
<br />D CONDUIT AND
<br />CONDUCTORS BACK TO POINT OF ORIGIN WHENEVER ����````0'
<br />FEASIBLE AND RELABEL DEMOLISHED CIRCUITS AS'SP,
<br />PROVIDE HANDLE DEVICE TO LOCK'SPARE' CIRCUIT * 19
<br />BREAKER IN THE `OFF` POSITION. = * =
<br />C- CONDUIT AND WIRING TO BE ABANDONED IN CEILING " 78 L ST
<br />SPACES AND OTHER NON-PUBLIC AREAS (I.E., THROU6g,0wk ; uG 0 3 2�t8
<br />STOCKROOM AREA): CUT WIRING LOOSE AND REMOVE�i �iQ "' O pP �� ���
<br />FROM RACEWAY(S), LEAVING RACEWAY(S) IN PLACE -
<br />CONDUIT
<br />CONDUIT TO 13E ABANDONED IN WALLS OR FLOORS SHALL /lllll
<br />BE REMOVED BACK TO FINISHED SURFACE AND CAPPED
<br />INSIDE. REPAIR SURFACE(S) TO MATCH ADJACENT. RIIINI�1 ' ��' P.E.
<br />D- ALL C9RCUT BREAKERS SERVING BRANCH CIRCUITS TO BE FL I179819
<br />ABANDONED OR REMOVED SHALL REMAIN IN RESPECTIVE
<br />PANELBOARD FOR FUTURE USE, UNLESS NOTED OTHERWISE
<br />ON DRAWINGS. PROVIDE HANDLE DEVICE TO LOCK'SPARE`
<br />CIRCUIT BREAKER IN THE'OFF' POSITION.
<br />E- DEMOLISHED FLUORESCENT LIGHT FIXTURES: REFER TO
<br />SELECTIVE SITE SON SPECIFICATION FOR
<br />DISPOSAL OF LIGHT FIXTURE.
<br />F. BUILDING COMPONENTS ABANDONED BY THE SCOPE OF
<br />WORK SHALL BE SECURED TO PREVENT FALLING,
<br />LOOSENING, OR CREATING DAMAGE OF ANY KIND IN THE
<br />FUTURE.
<br />EXISTING CONDITIONS WERE TAKEN FROM
<br />ORIGINAL DRAWINGS AND MAY NOT REFLECT
<br />EXACT AS-BUILr CONDITIONS. CONTRACTOR
<br />SHALL FIELD VERIFY ALL EXISTING CONDIITONS
<br />PRIOR TO SUBMITTING FINAL BIDS. CONTRACTOR
<br />SHALL CAREFULLY COORDINATE NEW WORK AND
<br />DEMOLITION ION WITH ALL OTHER DIMMES AMID
<br />EXISTING CONDITIONS.
<br />NOTE:
<br />RECEPTACLES, SWITCHES, DATA BOXES
<br />AND THEIR CORRESPONDING COVER
<br />PLATES SHALL BE WHITE NYLON.
<br />EACH SLBCONTRATOR IS RESPONSIBLE FOR HAVING A
<br />THOROUGH KNOWLEDGE OF ALL DRAWINGS AND
<br />SPECIFICATIONS IN THEIR RELATED FIELD. THE FAILURE
<br />TO ACQUAINT THEMSELF WITH THIS KNOWLEDGE DOES
<br />NOT RELIEVE THE RESPONSIBILITY OF PERFORMING
<br />THE WORK PROPERLY. NO ADDITIONAL
<br />COMPENSATION SHALL BE ALLOWED BECAUSE OF
<br />CONDITIONS THAT OCCUR DUE TO FAILURE TO
<br />FAMILIARIZE WORKERS WITH THIS KNOWLEDGE
<br />ELECTRICAL
<br />PLANS
<br />SHEET -
<br />El