Laserfiche WebLink
• � SECTIOfV IV — SYSTEM DE51GN <br /> UL EX.3470 ULC CEx747 Page 4-43 <br /> 4-1-06 REV.S <br /> � TARlK A(dD CARTRIDGE REQUIREMEiVTS ACTUATION AfdD EXPELLAhiT GAS LINE REQUIREMEI�fTS <br /> Once the hazard analysis is completed and the total noule flow This section contains the guidelines for installing the actuation and <br /> numbers are established,the quantity and size of agent tanks and expellant gas lines between the regulated release mechanism reg- <br /> cartridges needed to supply the nozzles with the proper volumes ulator, each regulated actuator regulator, and each agent tank. <br /> of agent at the proper flow rates can be determined.For cartridges These limitations should be considered when selecting the com- <br /> used in the regulated reiease mechanism, flow capacities, tank ponent mounting locations. <br /> quantities and sizes, and regulated release cartridge options are <br /> given in the table below. Actuation Gas Line—6 to 8*Tanks Maximum <br /> TOt31 Quantity and r Regulated Release '8 Tank mauimum reflecis the utilization of 3 tank regulated actuators. <br /> Flow Size of Cartridge Options 1.Use only 1/4 in. Schedule 40 black iron, hot-dipped galva- <br /> Numbers' Tank s Nitrogen Carbon Dioxide nized,chrome-plated,or stainless steel pipe and fittings. <br /> 1 — 5 (1) 1.5 Gallon LT-20-R 101-10 2.The actuation gas line piping is installed from the regulated <br /> 6-11 (1)3.O Gallon LT-30-R 701-20 release mechanism to each regulated actuator connected <br /> within the system.The total length of the actuation gas line <br /> 11 —16 (fi)i.5 Gallon' Double 101-30 from the regulated release assembly to the regulated actuator <br /> (1)3.0 Gallon assembly(ies) must not exceed 20 ft. (6 m) when using an <br /> 16—22 (2)3.0 Gallon Double 101-30'* LT20-R, an L'f-30-R nitrogen cartridge, or a 101-10 or a <br /> ► 101-20 carbon dioxide cartridge.See Figure 80. <br /> When one or more regulated actuators are used, the following <br /> tank and cartridge combinations apply for each regulated actuator: <br /> Regulated Actuator Regulated Actuator <br /> Tank(s) Cartridge <br /> (1) 1.5 Gallon LT-20-R or 101-10 <br /> (1)3.0 Gallon LT30=R or 101-20 <br /> (1) 1.5 Gallon and LT-A-101-30 or 101-30'"or <br /> (1)3.0 Gallon double tank <br /> (2)3.0 Gallon LT-A-101-30 or 101-30'"or <br /> double tank <br /> ' For exceptions to maximum flow numbers,see Distribution Piping Requirements for 1.5 gallon <br /> ��� and 3.0 gallon systems in Ihis Sectian. <br /> "The 101-30 cartridge can not be used when(2)hvo 3.0 gallon tanks are manifolded togethec) <br /> For higher total flow numbers(23 to 110), multiple cartridges and <br /> regulated actuators are required as shown in the System Selection <br /> Guide in Section IX—Appendix. <br /> REGULATED ACNATOR ASSEMB�Y <br /> EXPELLANT GAS LINES <br /> NOT INCLUDED IN ACNATIO[d <br /> GAS LINE LENGTH TOTALS <br /> REGULATED <br /> ACTUATOR <br /> , ASSEMBLY <br /> ACTUATION GAS LINE WITH Aid LT-26-R, <br /> LT-30-R,101-t00R 101-20 CARTRIQGE ' <br /> MAXIMUM LENGTH OF 20 FT(6 m), <br /> MAXIMUM NO.OF FITTINGS 9 <br /> REGULATEO <br /> ACTUATOR <br /> ASSEMBIY <br /> "ANSUL AUTOMAN" <br /> REGULATED RELEASE <br /> ASSEMBLY <br /> � FIGURE 80 <br /> 000ns <br />