Laserfiche WebLink
Manual S Com1�1 liance Re�fort Job: R1115486 <br /> � �- wrightsoft� r r Date: 11-17-15 <br /> Entire House By: JND <br /> Bahr's Propane Gas 8�AC Inc <br /> 4441 Allen Rd,Zephyrhills,FL33541 Phone:813782-5013 <br /> � • ' • � <br /> For: Butterfield Quadplex Unit 6-1 <br /> 4408 Court St, Zephyrhills, FL 33542 <br /> • • • • • <br /> Design Conditions <br /> Outdoor design DB: 91.0°F Sensible gain: 20741 Btuh Entering coil DB: 79.2°F <br /> Outdoor design WB: 76.0°F Latent gain: 3474 Btuh Entering coil WB: 64.3°F <br /> Indoor design DB: 75.0°F Total gain: 24216 Btuh <br /> Indoor RH: 50% Estimated airflow: 927 cfm <br /> Manufacturer's Performance Data atActual Design Conditions <br /> Equipment type: Split AC <br /> Manufacturer: Tempstar or Eqv. Model: N4A330A(G)KC*+FXM4X30''*A' <br /> Actual airtlow: 927 cfm <br /> Sensible capacity: 20850 Btuh 101% of load <br /> Latent capacity: 6950 Btuh 200% of load , <br /> Total capacity: 27800 Btuh 115% of load SHR: 75% <br /> • . • <br /> Design Conditions <br /> Outdoor design DB: 41.0°F Heat loss: 18729 Btuh Entering coil DB: 66.8°F <br /> Indoor design DB: 70.0°F <br /> Manufacturer's PerFormance Data atActual Design Conditions <br /> Equipment type: Elec strip <br /> Manufacturer: Model: <br /> Actual airtlow: 261 cfm <br /> Output capacity: 8.0 kW 146% of load Temp. rise: 96 °F <br /> The above equipment was selected in accordance with ACCA Manual S. <br /> c wri htsoftb 201SNov-1913:57:13 <br /> �, 9 Right-Suite�Universal 2015 15.0.21 RSU07440 Page 1 <br /> ��...le\R1115486-Butte�eld1R1115466 Unit Crl.rup Calc=MJ8 Building Front faces: N <br />