Laserfiche WebLink
_} , � <br /> � , -�r. � . ' <br /> , � - <br /> M . <br /> EAS PASCO MEDICAL CENTER � <br /> EME GENCY ROOM AND REGISTRATION EXPANSION AND <br /> �ENOVATION/SPRINKLER . <br /> LOG �.NUMBER: H-425-F <br /> DECEMBER. 16, 1988 <br /> ARGHITECTURAL <br /> �' � <br /> No comment. � <br /> ME C�HAN I CAL- - _ ._ . -.- -� . - -- -- - -- - <br /> ( , . <br /> No comment. <br /> FIRE PROTECTION � <br /> FP-1 Upon review of spr 'inkler working dtawings, the <br /> � following items were noted: <br /> . A) Indicate hanger locations . <br /> � B) Provide' locations of all smoke and/or fire walls <br /> which fire protection piping penetrates .� Provide <br /> penetration detail showing the maintaining of the <br /> � _. integrity of the smbke/fire zating. Fire <br /> protection piping shall. �be smoke/fire safed in an <br /> � approved manner when penetrating walls and floors . <br /> C) Provide' 286-degree Fahreriheit sprinkler in <br /> elevator equipment room. <br /> D) Ptovide fire sprinkler wotking drawings for � <br /> Mechanical Rooin 1-131 as called for on Sheet <br /> - - M�-4.- Provide - sprin-,clers= a-bove `-and-�-below exposed= - =- � - - <br /> duct work 4 feet. ot wider . � <br /> E) Provide Yiead guards on sprinkler heads in <br /> electric�, telephone and elevator equipment rooms . <br /> F) Provisions shall be made to properly drain all <br /> parts of the system. Drain riser shall not be <br /> smaller in diameter than the largest floor <br /> control� drain �connection. (Inspectors ' test is ` <br /> not a drain. ) . - � <br /> Page 1 of 2 <br />