� . .. � . <br /> . , � <br /> � <br /> , � <br /> EAS�T PASCO MEDICAL CENTER <br /> EME�RGENCY ROOM AND REGISTRATION <br /> EXP�ANSION AND RENOVATION/SPRINKLER <br /> LOGi NUMBER: H-425-F <br /> DECEMBER 16, 1988 <br /> � <br /> I <br /> I G) Relocate inspectors ' test line inside building. <br /> i H) Provide smooth bore corrosion resistant outlet <br /> for inspector ' s test giving flow equivalent to 1 <br /> � sprinkler�. ' InspectQr ' s .test valve shall not <br /> exceed 7 feet above the �finished floor . - <br /> MFC:MAN/sl <br /> I <br /> ELECTRICAL , <br /> I <br /> E-� Coordinate f1Qw switches and tamp�r switches with the <br /> fir� alarm system and submit revised fire alarm riser . <br /> The main fire sprinkler flow switch shall be connected <br /> as an alarm_ initiating device and shall be annunciated <br /> as a separate zone. All the fire sprinkler valves <br /> I shall have tamper switches . The tamper switches are <br /> zequired to have a distincti�ve supervised signal for <br /> off normal . Cancellation of the off normal signal is <br /> acceptable as the restoration signal when returned to <br /> the normal position. Operation of the tamper switch <br /> alarm shall not affect the operation of the sprinkler <br /> � system flow switches and shall not sound the general <br /> alarm. Zone flow switches shall be connected to the <br /> Fire Alarm System as automatic initiating device and <br /> each switch shall be separately annunciated. <br /> MFC:WS/sl - <br /> � <br /> Page 2 of 2 <br />