i <br /> ''� ; I <br /> ��� �� r ! :� . <br /> ? , , <br /> I <br /> i <br /> EAST; PASCO MEDICAL CENTER <br /> EMERGENCY ROOM AND REGISTRRTION EXPANSIONS AND RENOVATIONS <br /> LOG NUMBER: H-425-F <br /> MAY �15 , 19 8 9 <br /> � <br /> i <br /> S-6 ; Sections 1/SD-6 and 2/SD-6 show exteriot second story <br /> walls with angle braces at the floor and roof for the <br /> apparent purpose of addinq windows at some future <br /> � time. The top braces could be permanent if covered by <br /> � the ceiling, but the bottom braces will no doubt need <br /> I to be removed so that no obstacle to foot traffic <br /> i exists . It appears that bracing of wall panels needs <br /> ; to _ be structurally designed to provide desired future <br /> � flexibility. <br /> I <br /> MFC:IAK/sl <br /> � <br /> � <br /> I ��� <br /> MECHANICAL J��O �i�� <br /> � q�s� �+r � <br /> No comments . ��� <br /> .e�s <br /> � � < <br /> � <br /> FIRE PROTECTION <br /> FP-1� A. Sprinkleted �reas of buildings require <br /> i comprehensive engineering schematic plans for the <br /> i automatic fire protection system(s) . The <br /> � following items shall be indicated on plans : <br /> � sprinkler head locations , mains and bzanches fire <br /> ; riser arrangement, valving, inspectors ' test(s) , <br /> � flow switches, tamper switches, bulk feed mains, <br /> � drain lines , etc . These drawings are to be <br /> I submitted at the Construction Document, Stage III <br /> submission. <br /> j B. Indicate pipe cutting lengths and/or <br />, � center-to-center dimensions and nominal pipe , <br /> ' diameters at least from the point of connection <br /> � to and including the remote a�ea. <br /> i � <br /> MFC;MAN/sl <br /> i <br /> I <br /> ELECTRICAL <br /> No comments . <br /> I Page 3 of 3 <br /> � <br /> � <br /> � <br /> � <br /> I � <br /> - � <br />