I � . ��� � � <br /> } ' <br /> i� ' � , • ��_ ,� <br /> i <br /> Fire Chief William T. Fenton <br /> � City of Zephyrhills Fire Department <br /> ; September 28, 1989 . <br /> iPage 2 <br /> � 4. Comment - Remote duct detector indicators should be <br /> provided, and located where readily visible from below the <br /> � ceiling. <br /> I <br /> Response - Remote duct detector indicators have been <br /> specified (Section 16720 Fire Alarm System, 4.1.5) to be <br /> ; provided and mounted in a corridor near tne detector <br /> � location. They are also shown on drawing E1. <br /> ; <br /> � 5. Comment - Exit lights are required on both sides of all <br /> ' three double-egress control doors. <br /> i <br /> i <br /> Response - Yes, thank you. The Life Safety Plan correctly <br /> shows all exit lights. We have to add two more to drawing <br />, � E1. <br /> , 6. uestion - Are all fire alarm initiating devices within new <br /> j Fire Zone 11, including existing areas formerly on Fire <br /> Zone 5, all to be tied into new Fire Zone 11? <br /> I Answer - Yes. Notes to this effect are on drawing E4. <br />' <br /> i I hope this covers all of your questions thus far. <br /> � <br /> I <br /> ; Yours very truly, <br /> I � <br /> i . �.p-�� ac�„�� <br /> oe Rainwa er, A.I.A. <br /> I JR/wk <br /> cc: Mr. Ken Griffin <br /> � <br />