I ! <br /> � <br /> i <br /> i <br /> � � <br /> ; <br /> � <br /> Don Edge -3- April 6, 1995 <br /> � <br /> i <br /> � � <br /> � <br /> MECHANICAL ' <br /> � <br /> COMMENT: <br /> AC-19 Provide a firejsmoke damper at the duclt penetration of <br /> the two-haur wall tha�G separates Mechani�cal Room G91 from , <br /> � Pump Room G92. A fireJsmoke damper �n lieu a� a fire <br /> i damper will be required to maintain the smoke barrier of <br /> ; the graund floor fram the first floor smoke compartment. <br /> I <br /> RESPt?NSE• . <br /> We will comply, a fira smoke damper will be installed. <br /> See revised drawing Shee� M-1, dated April 6, 1995, Star <br /> , #9- <br /> COMMENT• <br /> AC-�0 Provide the filter efficienay for PAHU-1. This <br /> i information could not be found on any of the previous <br /> j drawings submitted. Please note that PAHU-1 sha1.2 be ! ; <br /> I provided with 90 percent filtration. ; <br /> 'I <br /> RESPONSE• ' <br /> � <br /> , � <br /> � We will comply. A 90% efficiency filter will be ; ', <br /> ' provided. See revised drawings Sheet M-1 and M-8� dated ; ; <br /> April 6, 1995, Star �9. i � <br /> � <br /> COMMENT• � <br /> AC-21 Pravide ventilation in Gloset 136A and Closet 136B. The � <br /> closets may be designed for a posi ive or negative i <br /> relative pressure due to there size as lang as Passage � <br /> 131 remains designed at an equal relat�ive pressure. <br /> RESPONSE• <br /> � <br /> � � We will compl�. Return air grilles will be added in <br /> , Closets 136A and 136B. See revised drawing Sheet M-3 <br /> ' dated April 6, 1995, Star #9• i <br /> i ; � <br /> � � ; � ; <br /> I car�ENm• i <br /> i <br /> ; P-6 Clarify that the lavatary in Toilet 134D is identified � ; <br /> � ' properly. Fixture L-4 is specified as a drop in type � " <br /> lavatory. The lavatory in Toilet 134D appears to be a ; <br /> � ! wall hung type. � ' <br /> � � <br /> � ' � <br /> I ' � <br /> i ' <br /> � � ' '� <br /> � � � <br />