Laserfiche WebLink
i <br /> M;r. Todd Reichard -5- August 30, 1994 <br /> , <br /> � �i <br /> � . <br /> iEach summary sheet of each individual unbound set of <br /> i Ihydraulic calculations shall be signed, dated and sealed <br /> by the engineer of record. Provide replacement <br /> , calculations. <br /> � <br /> RESPONSE• <br /> . <br /> i <br /> '� ' The calculations have been issued and have been approved <br /> I �'ibased on the July 15, 1994 letter from James Gregory of <br /> ; AHCA. <br /> i <br /> EYLECTItICAL <br /> � <br /> CUMMENT• � <br /> ; <br /> Sheet E-24• <br /> E�1 !Coordinate the exit light locations with the <br /> ! ;architectural drawings and comments. Example: Lights at <br /> � IWon door. <br /> � <br /> � � <br /> i Exit lights are not shown at the Won-door location <br /> separating the atrium lobby from the elevator lobby. <br /> Comply with the original comment. <br /> RESPONSE• � <br /> � 'Have complied. See replacement Sheet E-24, Star 2, dated � <br /> '�, August 19, 1994. <br /> COMMENT• I - <br /> � i �, <br /> E-'2 ��Provide panel and branch circuit information for the <br /> !light circuit in the telephone equipment room. <br /> , i <br /> ', 'Branch circuit information has not been provided for this <br /> ilighting. Comply with the original comment. <br /> REISPONSE• <br /> � <br /> Have complied. See replacement Sheet E-24, Star 2, dated <br /> � iugust 19, 1994. <br /> i ' <br /> COMMENT• '� <br /> E-iDelete the interconnection of the photocells controlling ' <br /> , �the life safety and normal lighting. <br /> I <br /> �� � � � <br /> � <br /> i � <br />