, i - --- <br /> M?^. Todd Reichard -6- August 30, 1994 <br /> ; � <br /> RESPONSE• <br /> � <br /> � Deleted <br /> COMMENT• <br /> I <br /> Sheet E-26: <br /> I I <br /> E�-12 � Provide a fire alarm visual device outside Infection <br /> ; � Control. <br /> ; <br /> IInformation has not been provided on the revised sheet. <br /> �, Comply with the original comment. <br /> RESPONSE• <br /> Moved horn/strobe in Corridor 172 (north 'end) to outside <br /> � <br /> Infection Control. <br /> IHave complied. See replacement Sheet E-26, Star 2, dated <br /> , ; August 19, 1994. <br /> i i <br /> C�MMENT• ' <br /> E;-14 iSheets E-26, E-28, E-29 and Specifications: Coordinate <br /> � the connection and control of the flashing "Do Not Use <br /> i Elevator" sign with the comments and details on Sheets E- <br /> � 28 and E-29. State Code 4A-47 allows only the machine <br /> � room smoke detector to activate these lights. Provide <br /> electrical details indicating the connection and control <br /> ; ; of these lights. <br /> � <br /> iRevise sheets do not address comment. Comply with the <br /> ioriginal comment. <br /> � <br /> RESPONSE•i <br /> Added note about existing equipment room S.P. clarified <br /> by note, controls of "Do Not Use" sign. , <br /> Have complied. See replacement Sheet E-28, Star 2, dated , <br /> August 19, 1994. ; � <br /> COMMENT• � ' <br /> � � I <br /> E-15 Identify the life safety circuits serving, the lighting in � <br /> the elevator lobbies on the second, third and fourth ' <br /> floors. � <br /> i ; i <br /> � � � <br /> � � <br /> I I I <br />