Laserfiche WebLink
B. Hose threads, operating nuts, and accessories for hydrants, siamese • <br /> connections shall meet local Fire Department Standard. <br /> C. The installing contractor shall be licensed or permitted by the state <br /> and local authority having jurisdiction to perform fire protection <br /> installations. <br /> 1.4 SUBMITTALS AND SHOP DR.AWINGS <br /> A. Prepare detailed and coordinated working drawings, accurately <br /> representing the design of record. <br /> B. Prepare complete, detailed, signed and sealed working drawings <br /> for Fire Protection System. Submit drawings and Hydraulic <br /> Calculations to authorities having jurisdiction for approval. Aftier <br /> receiving this approval, submit shop drawings to Designer for <br /> review and approval prior to starting installation. Prior approval by <br /> authorities having jurisdiction is required before sprinkler <br /> installation is begun. <br /> C. Equipment submittal drawings and data are required on all iterns <br /> named by manufacturer, including the following: <br /> 1. Sprinkler Heads -Type and Manufacturer. � � • <br /> 2. Piping and fittings. <br /> 1.5 APPLICABLE CODES <br /> A. NFPA 13 , <br /> PART 2 -PRODUCTS <br /> 2.1 ACCEPTABLE MANUFACTURERS <br /> A. Products listed indicate standard. <br /> 2.2 PIPE AND FITTINGS � <br /> A. Interior Pipe and Fittings: , <br /> 1. Piping shall be Schedule 40 black steel pipe conforming�o <br /> ASTM A135 or ASTM A53 and Schedule 10 black stee'1 <br /> pipe conforming to ASTM A135. • <br /> ICT 99184 <br /> 15300 -2 <br />