• <br /> ATTACHMENT "C" <br /> Commericial Check:. September 12, 1986 <br /> Halterman Property <br /> General Comments Electrical : • <br /> Main service entrance panel must be available to all tenants at all <br /> times and have a panel' schedule attached. There must be a minimum space <br /> 30" wide and 3' deep of clear area in front of service panel-. <br /> Due to types of renters that may be using these buildings, all electrical <br /> should be- metallic conduit. Ref. : N.E.C. Article 331-4. In area where this <br /> • article would not apply, tabing shall be suported every 3' and within 3' of <br /> each outlet, box, fittings etc. Ref. : N.E.C. Article 331-11 . All electrical <br /> in commerical buildings must be in conduit. <br /> All electrical equipment, boxes, fittings, cabinets, and outlets must •; <br /> have all unused openings closed or cover as needed. If flexible cords are <br /> used, they must be of 3 wire approved type, and be wired into fixtures as <br /> approved by N.E.C. codes. <br /> Block Building: <br /> All Romax must be removed. See "General Comments" • <br /> Trim & Drywall Bay: <br /> See 'General Comments" <br /> Ba *2: <br /> ontains fixture with covers missing; also, see "General Comments" <br /> Wagner's Bay: <br /> Flex cord feeding light with open splices; also, see "General Comments" <br /> Empty Bay: <br /> • Exposed wiring conduits hanging loose; also, see. "General Comments" <br /> John Smith's Bay: • <br /> See "General Comments" . <br /> • <br /> Super Tube PVC Furniture: <br /> . See "General Comments" • <br /> Feed Store: <br /> See General Comments" <br /> • <br /> Garage & Paint Shop: <br /> See "General Comments" <br /> Goodwill Store: <br /> Under ground to sign to be in PVC or U.F. Cable;. also, see "General Comments" <br /> Carpet Store: <br /> Panel over sink and mixer must be clear. Note: see "General Comments" <br /> IIIPanel in rear of store. is energized, all unused opening must be closed <br /> and panel have clear area. Main disconnect at service entrance must have <br /> inside cover. . Conduit outside of building must have water tight fittings. <br /> See "General Comments" <br /> • <br />