Laserfiche WebLink
, � <br /> Manual S Compliance Report Job: 3127AB sf ADS <br /> Date: 8/10/2017 <br /> lowerfloor By: DaveAldrich <br /> � Bayonet Plumbing Heating and Cooling <br /> 8950 New York ave,Hudson <br /> � � ' • • <br /> For: Lennar Homes <br /> � • • • • <br /> Design Conditions <br /> Outdoor design DB: 91.3°F Sensible gain: 19711 Btuh Entering coil DB 75.6°F <br /> Outdoor design WB: 77.3°F Latent gain: 2311 Btuh Entering coil WB: 62.8°F <br /> Indoor design DB: 75.0°F Total gain: 22023 Btuh <br /> Indoor RH: 50% Estimated airflow� 800 cfm <br /> Manufacturer's Performance Data at Actual Design Conditions <br /> Equipment type: SpIitASHP � <br /> Manufacturer: Lennox Model: 14HPX-024230-21+CBA27UHE-024-230'`++TDR <br /> Actual airflow: 800 cfm <br /> Sensible capacity: 21420 Btuh 109% of load <br /> Latent capacity: 3780 Btuh `164% of load <br /> Total capacity� 25200 Btuh 114% of load SHR: 85% <br /> a • • <br /> Design Conditions <br /> Outdoor design DB. 30.8°F Heat loss: 24301 Btuh Entering coil DB: 69.6°F <br /> Indoor design DB: 70.0°F <br /> , <br /> � Manufacturer's Performance Data at Actual Design Conditions <br /> Equipment type: SpIitASHP <br /> Manufacturer Lennox Model: 14HPX-024230-21+CBA27UHE-024-230'`++TDR <br /> Actual airflow: 800 cfm <br /> Output capacity� 21800 Btuh 90°/a of load Capacity balance: 35 °F <br /> Supplemental heat required: 2501 Btuh Economic balance: -99 °F <br /> Backup equipment type: Elec strip <br /> Manufacturer: Model: <br /> Actual airflow: 800 cfm <br /> Output capacity: 7.1 kW 99% of load Temp. rise: 26 °F <br /> Meets are all requirements of ACCA Manual S. <br /> 1. W1�1 f1tSOft° 2017-Aug-1013:20:33 <br /> 1, 9 Right-Suite�Universal 2017 17.0.23 RSU05714 Page 1 <br /> � ...BA27UHE AH's13127A8 sf ADS template 2-2tons.rup Calc=MJ8 Front Door faces: S <br />