Laserfiche WebLink
Buildin Anal SIS , Job: 1791B sf ADS <br /> g y , Date: 10/1312017 <br /> Entire House By: Dave <br /> Bayonet Plumbing Heating and Air <br /> ' • - • � <br /> For• Lennar Homes <br /> � - • • • � <br /> Location: Indoor: Heating Cooling <br /> Tampa International AP, FL, US Indoor temperature(°F) 70 75 <br /> Elevation: 10 ft Design TD (°F) 39 16 <br /> Latitude: 28°N Relative humidity(%) 50 50 <br /> Outdoor: Heating Cooling Moisture difference(gr/Ib) 34.7 54.7 <br /> Dry bulb(°F) 31 91 Infiltration: <br /> Daily range(°F) - 14 ( L ) Method Simplified <br /> Wet bulb(°F) - 77 Construction quality Semi-tight <br /> Wind speed(mph) 15.0 7.5 Fireplaces 0 <br /> • <br /> Component Btuh/ft2 Btuh % of load <br /> Walls 5.6 6529 25.4 �as <br /> Glazing 30.2 4772 18.6 wa�� <br /> DOO�S 23.5 466 1.8 nmtration <br /> Ceilings 1.3 2271 8.8 <br /> Floors 3.4 6125 23.9 <br /> Infiltration 2.2 2887 11.2 � <br /> Ducts 2616 10.2 <br /> Piping 0 � Glazing Floors <br /> Humidification 0 0 <br /> Ventilation 0 0 o�ef Ceilings <br /> Adjustments 0 <br /> Total 25667 100.0 <br /> • • • <br /> Component Btuh/ftZ Btuh % of load <br /> Walls ' 2.8 3248 14.4 waus <br /> Glazing 48.5 7661 33.9 Intemal Gains <br /> Doors 18.4 365 1.6 <br /> Ceilings 1.7 3140 13.9 <br /> Floors 0 0 0 <br /> Infiltration 0.5 647 2•9 • oucts <br /> D ucts 2982 13.2 <br /> Ventilation 0 0 <br /> Internal gains 4555 20.2 Glazing <br /> Blower 0 0 Infiltration <br /> Adjustments 0 ceilings <br /> Total 22597 100.0 Other <br /> Latent Cooling Load= 3575 Btuh <br /> Overall U-value= 0.104 Btuh/ftz-°F <br /> Data entries checked. <br /> � -�- wrightsoftm 2017-Oct-1313:10:03 <br /> �� Right-Suitet�Universal 2017 17.0.23 RSU05714 Page 1 <br /> CBA27UHE AH's\1791B sf ADS template 2.5ton.rup Calc=MJS Front Door faces:NW <br />