Laserfiche WebLink
, , � <br /> Manual S Compliance Report Job: 2889A1 sf ADS <br /> Date: 10/30/2017 <br /> upper floor By: Dave <br /> BAYONET PLUMBING COOLING HEATING <br /> ' • - • � <br /> For: Lennar Homes <br /> • • • • • <br /> Design Conditions <br /> Outdoor design DB: 92.4°F Sensible gain: 12143 Btuh Entering coil DB: 75.8°F <br /> Outdoor design WB: 77.4°F Latent gain: 2049 Btuh Entering coil WB. 62.9°F <br /> Indoor design DB• 75.0°F Total gain: 14192 Btuh <br /> Indoor RH 50% Estimated airflow: 600 cfm <br /> Manufacturer's Performance Data at Actual Design Conditions <br /> Equipment type: Split ASHP <br /> Manufacturer: Lennox Model: 14HPX-018-230-21+CBA27UHE-018-230'`++TDR <br /> Actual airflow: 600 cfm <br /> Sensible capacity: 15300 Btuh 126% of load <br /> Latent capacity: 2700 Btuh 132% of load <br /> Total capacity: 18000 Btuh 127% of load SHR: 85% <br /> . • • <br /> Design Conditions <br /> Outdoor design DB: 30.8°F Heat loss. 10946 Btuh Entering coil DB: 69.6°F <br /> Indoor design DB: 70.0°F <br /> Manufacturer's Performance Data at Actual Design Conditions <br /> Equipment type: SpIitASHP <br /> Manufacturer: Lennox Model: 14HPX-018-230-21+CBA27UHE-018-230"++TDR <br /> Actual airflow� 600 cfm <br /> Output capacity: 17500 Btuh 160% of load Capacity balance: 20 °F <br /> Supplemental heat required: 0 Btuh Economic balance: -99 °F <br /> Backup equipment type: Elec strip <br /> Manufacturer: Model: ' <br /> Actual airflow: 600 cfm <br /> Output capacity� 3.1 kW 98% of load Temp. rise: 15 °F <br /> Meets are all requirements of ACCA Manual S � <br /> ..•_ wri htsoftm 2017-Oct-30 09:34:45 <br /> �, 9 Right-Suite�Universal 2017 17.0.23 RSU05714 Page 2 <br /> �'� .BA27UHE AH's�2889A sf template ADS 1.5-2ton.rup Calc=MJ8 Front Door faces: E <br />