Laserfiche WebLink
TFP172 <br /> Page 3 of 4 <br /> Step 3.Tighten the sprinkler into the 2-7/8"DIA. <br /> sprinkler fitting using only the W Type (73,0 mm) <br /> 6 Sprinkler Wrench(Figure 2).With ref- <br /> erence to Figure 1,apply the W-Type 6 2-1/4"DIA. <br /> Sprinkler Wrench to the wrench flats. FACE OF (57,2 mm) <br /> Torque sprinklers 7 to 14 ft.-Ibs.(9,5 to SPRINKLER <br /> 19,0 Nm). FITTING 5/8"(15,9 mm) <br /> Recessed Pendent Sprinklers FLUSH <br /> The Series TY-FRB Recessed Pendent 3/8t5/16" <br /> Sprinklers must be installed in accor- (9,5t7,9 mm) 1` (I <br /> dance with the following instructions. <br /> 0/1 <br /> Step A.After installing the Style 15 or MOUNTING 1/8" <br /> Style 20 Mounting Plate over the sprin- SURFACE (3,2 mm) <br /> kler threads, and with pipe-thread — <br /> sealant applied to the pipe threads, CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) <br /> hand-tighten the sprinkler into the TY-FRB PLATE 3/4"(19,1 mm) <br /> sprinkler fitting. <br /> Step B.Tighten the sprinkler into the FIGURE 4 <br /> sprinkler fitting using only the in Type SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) <br /> 7 Recessed Sprinkler Wrench (Figure WITH TWO PIECE 518 INCH TOTAL ADJUSTMENT STYLE 15 <br /> RECESSED ESCUTCHEON <br /> 3).With reference to Figure 1,apply the <br /> W Type 7 Recessed Sprinkler Wrench <br /> to the sprinkler wrench flats. Torque 2-7/8"DIA. <br /> sprinklers 7 to 14 ft.-Ibs. (9,5 to 19,0 (73,0 mm) <br /> Nm). FACE OF <br /> Step C.After ceiling installation and fin- SPRINKLER (57,2 mm) <br /> DIA. <br /> FITTING 57 <br /> fishing,slide on the Style 15 or Style 20 <br /> Closure over the Series TY-FRB Sprin- 5/16t1/4"kler and push the Closure over the (7,9t6,4 mm) 1/2"(12,7 mm) <br /> Mounting Plate until its flange comes in FLUSH <br /> contact with the ceiling. � , <br /> _I <br /> Care and <br /> UNTING 1/8" <br /> Maintenance SOURFACE (3,2 mm) <br /> The TYCO Series TY-FRB,5.6 K-factor, <br /> Upright(TY313)and Pendent(TY323) CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) <br /> Sprinklers must be maintained and ser- TY-FRB PLATE 7/8"(22,2 mm) <br /> viced in accordance with this section. FIGURE 5 <br /> Before closing a fire protection system SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) <br /> main control valve for maintenance WITH TWO PIECE 112 INCH TOTAL ADJUSTMENT STYLE 20 <br /> work on the fire protection system RECESSED ESCUTCHEON <br /> that it controls, obtain permission to <br /> shut down the affected fire protection Modified sprinklers must be replaced. standards of any other authorities hav- <br /> systems from the proper authorities Sprinklers that have been exposed to ing jurisdiction. Contact the installing <br /> and notify all personnel who may be corrosive products of combustion, but contractor or sprinkler manufacturer <br /> affected by this action. have not operated,should be replaced regarding any questions. <br /> Absence of the outer piece of an if they cannot be completely cleaned Automatic sprinkler systems are rec- <br /> escutcheon, which is used to cover by wiping the sprinkler with a cloth or ommended to be inspected, tested, <br /> a clearance hole, can delay sprinkler by brushing it with a soft bristle brush. and maintained by a qualified Inspec- <br /> operation in a fire situation. Care must be exercised to avoid dam- tion Service in accordance with local <br /> The owner must assure that the sprin- age to the sprinklers before,during,and requirements and/or national codes. <br /> klers are not used for hanging any after installation. Sprinklers damaged <br /> objects and that the sprinklers are only by dropping, striking, wrench twist/ <br /> cleaned by means of gently dusting slippage,or the like,must be replaced. <br /> with a feather duster; otherwise, non- Also, replace any sprinkler that has a <br /> operation in the event of a fire or inad- cracked bulb or that has lost liquid from <br /> vertent operation may result. its bulb.(Ref.Installation Section.) <br /> Sprinklers which are found to be leak- The owner is responsible for the <br /> ing or exhibiting visible signs of corro- inspection,testing,and maintenance of <br /> sion must be replaced. their fire protection system and devices <br /> in compliance with this document, as <br /> Automatic sprinklers must never be well as with the applicable standards <br /> painted, plated, coated, or other- of the National Fire Protection Associa- <br /> wise altered after leaving the factory. tion (e.g., NFPA 25), in addition to the <br />