Manual S Compliance Report Job: 2575Al sf ADS Carrier <br /> Date: 511/2018 <br /> lower floor By: Dave <br /> BAYONET PLUMBING COOLING HEATING <br /> Project-Information <br /> For: Lennar Homes <br /> Cooling Equipment <br /> Design Conditions <br /> Outdoor design DB: 91.4°F Sensible gain: 11368 Btuh Entering coil DB: 75.8°F <br /> Outdoor design WB: 77.2°F Latent gain: 1216 Btuh Entering coil WB: 62.9°F <br /> Indoor design DB: 75.0°F Total gain: 12584 Btuh <br /> Indoor RH: 50% Estimated airflow: 600 cfm <br /> i <br /> Manufacturer's Performance Data at Actual Design Conditions <br /> Equipment type: SplitASHP <br /> Manufacturer: Carrier Model: 25HBC518A00300+FB4CNP025L <br /> Actual airflow: 600 cfm <br /> Sensible capacity: 15300 Btuh 135% of load <br /> Latent capacity: 2700 Btuh 222% of load <br /> Total capacity: 18000 Btuh 143% of load SHR: 85% <br /> Heating Equipment <br /> Design Conditions <br /> Outdoor design DB: 32.1°F Heat loss: 15750 Btuh Entering coil DB: 69.6°F <br /> Indoor design DB: 70.0°F <br /> Manufacturer's Performance Data at Actual Design Conditions <br /> Equipment type: SplitASHP <br /> Manufacturer: Carrier Model: 25HBC518A00300+FB4CNP025L <br /> Actual airflow: 600 cfm <br /> Output capacity: 13793 Btuh 88% of load Capacity balance: 31 °F <br /> Supplemental heat required: 1957 Btuh Economic balance: -99 °F <br /> Backup equipment type: Elec strip <br /> Manufacturer: Model: <br /> Actual airflow: 600 cfm <br /> Output capacity: 4.5 kW 97% of load Temp. rise: 50 °F <br /> Meets all requirements of ACCA Manual S. <br /> -�- wrightsoft® 2018-May-01 09:12:05 <br /> Right-Suite®Universal 2018 18.0.16 RSU05714 Page 1 <br /> ...ment\2575A sf ADS template 1.5-2ton Carrier.rup Calc=MJ8 Front Door faces: W <br />