467 Swan Ave • Hohenwald,TN 38462 • (800) 284-7437 • www.olivertechnologies.com • Fax (931) 796-8811 <br /> INSTALLATION USING CONCRETE RUNNER/FOOTER <br /> 15. A concrete runner,footer or slab may be used in place of the steel ground pan. <br /> a) The concrete shall be minimum 2500 psi mix <br /> b) A concrete runner may be either longitudinal or transverse,and must be a minimum of 8"deep with a minimum width of_16 inches <br /> longitudinally or 18 inches transverse to allow proper distance between.the concrete bolt and the edge of the concrete(see below). <br /> c) Footers must have minimum surface area of 441 sq.in.(i.e.21"square),and must be a minimum of 8"deep. <br /> d) If a full slab is used,the depth must be a 4"minimum. Special inspection of the system bracket installation is not.required.Footers <br /> must allow for at least 4"from the concrete bolt to the edge of the concrete. <br /> NOTE:The bottom of all footings,pads,slabs and runners must be per local jurisdiction. <br /> LONGITUDINAL:(Model 1101 LC"V") <br /> 16: When using Part#1101-W-CPCA(wetset)simply install the bracket in runner/footer OR When installing in cured concrete use Part# <br /> 101-D-CPCA(dryset):The 1101 (dryset)CA bracket is attached to the concrete using(2)5/8"x3"concrete wedge bolts(Simpson part# <br /> S162300H 5/8"X 3"or Powers,equivalent).Place the CA bracket in desired location.Mark bolt hole locations,then using a 5/8"diameter <br /> masonry bit,drill a.hole to a minimum depth of 3".Make sure all dust and concrete is blown out of the holes.Place-wedge bolts into drilled <br /> holes,then place 1101-(dry set)CA bracket onto wedge bolts and start wedge bolt nuts.Take a hammer and lightly drive the wedge bolts <br /> down by hitting the nut(making sure not to hit the top of threads on bolt).The sleeve of concrete wedge bolt needs to be at or below the <br /> top of concrete.Complete by tightening nuts. <br /> LATERAL:(Model 1101 TC"V") <br /> 17. For wet set(part#1101-W-TACA)installation simply install the anchor bolt into runner/footer.For dry set installation(part#1101-D TACA) <br /> mark bolt hole locations,then using.a 5/8"diam.masonry bit.drill a hole to a minimum depth of Y! Make sure all dust and concrete is <br /> blown out of the hole.Place wedge bolts(Simpson part#S162300H 5/8".X 3"or Powers equivalent)into(D)concrete dry transverse <br /> connector and into drilled hole.If needed,take a.hammer and lightly drive the wedge bolts down by hitting the nut(making sure not to <br /> hit the top of threads on bolt),then remove the nut.The sleeve of concrete wedge bolt needs to be at or below the top of concrete. <br /> 18. When using part#1101 CVW(wetset)or 1101 CVD(dryset),'install per steps 17&18. <br /> Notes: <br /> 1.LENGTH OF HOUSE ISTHE ACTUAL BOX SIZE <br /> 2.Ll-=LOCATION OF TRANSVERSE BRACING ONLY <br /> 3 ® =LOCATION OF LONGITUDINAL BRACING ONLY <br /> 4.KJ­=TRANSVERSE AND LONGITUDINAL LOCATIONS <br /> ALL WIDTHS AND LENGTHS UP TO 52' <br /> ALL WIDTHS AND LENGTHS OVER 52'TO 80" <br /> HOMES WITH 5/12 ROOF PITCH REQUIRE:PER FLORIDA REGULATIONS <br /> 6 systems for home lengths up to 52'and 8 systems for homes over 52'and up 80'. <br /> PATENT#6634150&OTHER PATENT PENDING Page 2 <br /> Revision 08/23/18 <br />