Standby Prime <br /> Air rating rating <br /> Combustion air,m3/min(scfm) 15.86(560) 15.38(543) <br /> Maximum air cleaner restriction with clean filter,kPa(in H2O) 3.7(15) <br /> Exhaust <br /> Exhaust flow at set rated load,m3/min(cfm) 40.74(1439) 37.8(13.35) <br /> Exhaust temperature,°C(°F) 512.22(954) 484.44(904) <br /> Maximum back pressure,kPa(in H2O) 10(40.19) 10(40.19) <br /> Actual exhaust back pressure with CPG sound level 2 enclosure 10(40.19) 9.9(39.78) <br /> muffler,kPa in H2O <br /> Actual exhaust back pressure with CPG weather enclosure 8.4(33.76) 7.8(31.47) <br /> muffler,kPa in H2O <br /> Standard set-mounted radiator cooling <br /> Ambient design,°C(°F) 49(120.2) <br /> Fan load,kW.(HP) 14.02(18.8) <br /> Coolant capacity(with radiator),L(US Gal) 22(5.9) <br /> Cooling system air flow,m3/min(scfm) 305.82(10800) <br /> Total heat rejection,MJ/min(Btu/min) 10.06(9538) 9.44(8952) <br /> Maximum cooling air flow static restriction,kPa(in H2O) 0.12 0.5 <br /> Weight2 <br /> Unit wet weight kgs(lbs) ;1583(3491) <br /> Notes: <br /> 1 For non-standard remote installations contact your local Cummins Power Generation representative. <br /> 2 Weights represent a set with standard features. See outline drawing for weights of other configurations. <br /> Derating factors <br /> Engine power available up to 2148 m(7047 ft.)at ambient temperatures up to 40°C(104°F)and <br /> Standby 1086 m(3563 ft.)at 50 °C(122 °F).Above these conditions,derate at 8%per 305 m(1000 ft.)and <br /> 34%per 10°C 18°F <br /> Engine power available up to 1944 m at ambient empera ures up to an <br /> Prime 811 m(2661 ft.)at 50 °C(122'F).Above these conditions,derate at 9%per 305 m(1000 ft.)and <br /> 40%per 10 °C 18°F <br /> Ratings definitions <br /> Limited-time running power Base load(continuous)power <br /> Emergency standby power(ESP): (LTP): Prime power(PRP): (COP): <br /> Applicable for supplying power to Applicable for supplying power to Applicable for supplying power Applicable for supplying power <br /> varying electrical load for the a constant electrical load for to varying electrical load for continuously to a constant <br /> duration of power interruption of a limited hours. Limited Time unlimited hours.Prime Power electrical load for unlimited <br /> reliable utility source.Emergency Running Power(LTP)is in (PRP)is in accordance with hours.Continuous Power <br /> Standby Power(ESP)is in accordance with ISO 8528. ISO 8528.Ten percent overload (COP)is in accordance with <br /> accordance with ISO 8528.Fuel capability is available in ISO 8528,ISO 3046, <br /> Stop power in accordance with accordance with ISO 3046, AS 2789,DIN 6271 and <br /> ISO 3046,AS 2789,DIN 6271 and AS 2789,DIN 6271 and BS 5514. <br /> BS 5514. BS 5514. <br /> North America <br /> 1400 73rd Avenue N.E. <br /> Minneapolis,MN 55432 <br /> USA <br /> Phone 763 574 5000 <br /> Fax 763 574 5298 <br /> Our energy working for you s <br /> ©2019 Cummins Inc.All rights reserved. <br /> Cummins is a registered trademarks of Cummins Inc.PowerCommand,Amp Sentry,InPower <br /> and-Our energy working for you."are trademarks of Cummins.Other company,product,or service names <br /> may be trademarks or service marks of others.Specifications are subject to change without notice. power.cummjns.com <br /> NAD-6374-EN(01119)A0611`589 <br />