Laserfiche WebLink
DONNELLY ENGINEERING ELECTRICAL <br /> C. Floor Penetrations In Block: PVC may also be used for penetrations of floor into concrete block or hollow <br /> walls up to first outlet box provided outlet box is at a maximum height of 48 inches above finished floor. <br /> D. Joints: PVC joints shall be solvent welded. Threads shall not be permitted on PVC conduit and fittings, <br /> except for rigid steel to PVC couplings. Installation of PVC conduit shall be in accordance with <br /> manufacturer's recommendations. <br /> E. Ground Conductor Installation: All individual bare copper ground conductors (i.e. service, transformer, or <br /> lightning protection grounds) shall be installed in PVC conduit. <br /> F. Support: PVC conduit shall not be used to support fixture or equipment. <br /> G. Bends: Field bends shall be made with an approved hotbox. Heating with flame and hand held dryers are <br /> prohibited <br /> PART 3 -EXECUTION <br /> 3.1 IDENTIFICATION OF BOXES <br /> A. Tags: During installation of pull strings all pull strings shall be marked with vinyl tags indicating where the <br /> opposite end may be found. <br /> B. Boxes: Provide fixed label on boxes indicating circuit, panel and use of box eg. "power 120V, lighting <br /> 120V". Refer to identification specification section <br /> 3.2 BLANK PLATES <br /> A. Plates: Unless otherwise noted all outlet boxes shall receive blank plates matching the finish of plates on <br /> electrical devices in the same room. <br /> 3.3 RACEWAY INSTALLATION <br /> A. Support: All raceways shall be run in a neat and workmanlike manner and shall be properly supported and <br /> in accordance with the latest edition of the NEC. Supporting conduit and boxes with wire is not acceptable. <br /> Exposed raceways where allowed, shall be supported with clamp fasteners with toggle bolt on hollow walls, <br /> and with lead expansion shields on masonry. All conduits shall be securely fastened in place with at least <br /> one support per eight foot section. Support within one foot of changes in direction. All required hangers, <br /> supports and fastenings shall be provided at each elbow and at no more than one foot from the end of each <br /> straight run terminating at a box or cabinet. The use of perforated iron for supporting conduits shall not be <br /> permitted. The required strength of the supporting equipment and size and type of anchors shall be based <br /> on the combined weight of conduit, hanger and cables. Horizontal and vertical conduit runs may be <br /> supported by one-hole malleable straps, clamp-backs, or other accepted devices with suitable bolts, <br /> expansion shields (where needed) or beam-clamps for mounting to building structure or special brackets. <br /> B. Hanger Installation: Where 2 or more conduits 1 inch or larger run parallel trapeze hangers may be used <br /> consisting of concrete inserts, threaded solid rods, washers, nuts and galvanized "L" angle iron, or Unistrut <br /> cross members. These conduits shall be individually fastened to the cross member of every other trapeze <br /> hanger with galvanized cast one hole straps, clamp backs, bolted with proper size cadmium machine bolts, <br /> washers and nuts. If adjustable trapeze hangers are used to support groups of parallel conduits, U-bolt <br /> type clamps shall be used at the end of a conduit run and at each elbow. J-bolts, or approved clamps, shall <br /> be installed on each third intermediate trapeze hanger to fasten each conduit. <br /> C. Sealant: Provide a closed cell silicone foam sealant rated to provide a rating equal to the wall, ceiling, or <br /> floor assembly rating. Provide seals for the exterior of conduit penetrations consisting of a cast-in-place <br /> sleeve with a compressible rubber gasket between the conduit and the sleeve. Provide seals for the interior <br /> Heartland Health Care Center of Zephyrhills-3181 16110-5 DE No 217032 <br /> 38220 Henry Drive,Zephyrhills, FL 33542 Pending Emergency Rule 59A-4.1265 <br />