DON NELLY ENGINEERING ELECTRICAL <br /> of the conduit penetrations consisting of gland type sealing bushing or closed cell silicone foam. Provide <br /> duct seal inside an appropriate seal-off fitting to seal the interior of the conduit system from water seepage <br /> or hazardous gases. <br /> D. Routing: Conduits shall be run parallel to building walls wherever possible, exposed or concealed as <br /> specified, and shall be grouped in workmanlike fashion. Crisscrossing of conduits shall be minimized. <br /> E. Location: All raceways shall be run concealed from view. Surface mounted devices and equipment shall <br /> be specifically noted on the contract drawings or shall be located where panelboards are surface mounted. <br /> It is the intent that all raceways shall be run concealed unless specifically noted. <br /> F. Protection: All raceway runs, whether terminated in boxes or not, shall be capped during the course of <br /> construction until wires are pulled in and covers are in place. No conductors shall be pulled into raceways <br /> until the raceway system is complete. <br /> G. Coordination: All raceways shall be kept clear of mechanical equipment and plumbing fixtures to facilitate <br /> future repair or replacement of said fixtures without disturbing wiring. Except where it is necessary for <br /> control purposes, all raceways shall be kept away from items producing heat. <br /> H. Masonry Installation: All raceway runs in masonry shall be installed at the same time as the masonry so <br /> that no face cutting is required, except to accommodate boxes. <br /> I. Arrangement: All raceways shall be run connecting outlet to circuits generally as shown on the drawings. <br /> Provide circuit connection arrangement shown. Actual final arrangement shall be in accordance with the <br /> record drawings section as specified herein. <br /> J. Grounding: All branch circuit and feeder raceways shall have a insulated copper system ground conductor <br /> within the conduit throughout the entire length of the circuit. All conduit shall be electrically continuous to <br /> establish redundant grounding. <br /> 1. Branch circuit raceways shall have an insulated equipment grounding conductor installed within the <br /> conduit raceway system. <br /> 2. Grounding conductor shall be included in total conduit fill determining conduit sizes, even though not <br /> shown on drawings. <br /> 3. Grounding conductors run with feeders shall be green insulated only. <br /> 4. Grounding conductors run with normal and essential electrical system feeders serving patient care <br /> area shall be bonded to portions of conduit that are metal by listed grounding bushings. <br /> K. Empty Raceways: Raceways which do not have conductors provided under this Division of the <br /> specifications shall be left with an acceptable nylon pullcord in raceway. <br /> L. Manufacturer: Rigid Metallic Conduit, Electrical Metallic Tubing, Flexible Steel Conduit, Liquid-Tight <br /> Flexible Conduit, and PVC Conduit shall be manufactured within the United States, and each shall be as <br /> manufactured by one manufacturer. <br /> M. Roof Installation: Conduit installations on roofs shall be exposed to a bare minimum. Conduit shall not be <br /> installed on roofs. Metal conduit stubs to mechanical equipment or receptacles are allowed however they <br /> must connect directly to the equipment or device without resting or supported on the roof. <br /> N. Firewall Installation: Provide pullboxes, junction boxes, fire barrier at fire rated walls etc., as required by <br /> NEC Article 300 where required. <br /> O. Dissimilar Metals: Avoid the use of dissimilar metals to reduce the possibility of electrolysis. Where <br /> dissimilar metals are in contact, coat all surfaces with corrosion inhibiting compound before assembling. <br /> P. Sealoff Fittings: Provide conduit sealoffs wherever the raceway system enters a hazardous or wet area'or <br /> areas of drastic temperature change such as coolers, freezers, etc. as required. <br /> Heartland Health Care Center of Zephyrhills-3181 16110-6 DE No 217032 <br /> 38220 Henry Drive,Zephyrhills, FL 33542 Pending Emergency Rule 59A-4.1265 <br />