DONNELLY ENGINEERING ELECTRICAL <br /> B. Exposed Boxes: Exposed boxes shall be cast type. <br /> PART 3 - EXECUTION <br /> 3.1 INSTALLATION OF OUTLET BOXES <br /> A. Installation: All flush outlets shall be mounted so that covers and plates shall finish flush with <br /> finished surfaces without the use of shims, mats or other devices not submitted or accepted for the <br /> purpose. Add-a-Depth ring or switch box extension rings (Steel City #SBEX) are not acceptable. <br /> Plates shall not support wiring devices. Gang switches with common plate where two or more are <br /> indicated in the same location. Wall-mounted devices of different systems (switches, thermostats, <br /> etc.) shall be coordinated for symmetry when located near each other on the same wall. Outlets on <br /> each side of walls shall have separate boxes. Through-wall type boxes shall not be permitted. Back- <br /> to-back mounting shall not be permitted. Trim rings shall be extended to within 1/8 inch of finish wall <br /> surface. <br /> B. Stud Walls: Outlet boxes mounted in metal stud walls, shall be supported to studs with 2 screws <br /> inside of outlet box to a horizontal stud brace between vertical studs. Do not mount screws on the <br /> face of the studs. <br /> C. Blank Covers: All outlet boxes that do not receive devices in this contract are to have blank plates <br /> installed matching wiring device plates. <br /> 3.2 MOUNTING HEIGHT <br /> A. Mounting Height: Height of wall outlets to center or bottom of box above finished floor shall be as <br /> follows, unless specifically noted otherwise. Verify all heights with the Architectural plans and shop <br /> drawings for installation. The following dimensions are a guide only. Specific heights required by <br /> governing institutions and laws shall apply. <br /> Switches & Dimmers 4 foot 0 inches to centerline <br /> Receptacles 2 foot 0 inches to centerline <br /> 4 feet or inches or 9"AFC <br /> (receptacles above counter) per symbol <br /> Branch Panelboards 6'-6" inches to top of panel trim <br /> B. Counter Tops: Bottoms of outlets above counter tops or base cabinets shall be <br /> minimum 2 inches above counter top or backsplash, whichever is highest. Outlets may <br /> be raised so that bottom rests on top of concrete block course, but all outlets above <br /> counters in same area shall be at same height. It is the responsibility of this Contractor to <br /> secure cabinet drawings and coordinate outlet locations in relation to all cabinets as <br /> shown on Architectural plans, prior to rough-in, regardless of height shown on <br /> documents. <br /> C. Wall Outlets: Height of wall-mounted fixtures shall be as shown on the drawings or as <br /> required by Architectural plans and conditions. Fixture outlet boxes shall be equipped <br /> with fixture studs when supporting fixtures. <br /> END OF SECTION <br /> Heartland Health Care Center of Zephyrhills-3181 16130-2 DE No 217032 <br /> 38220 Henry Drive,Zephyrhills, FL 33542 Pending Emergency Rule 59A-4.1265 <br />