Laserfiche WebLink
DONNELLY ENGINEERING ELECTRICAL <br /> withstand high fault current levels without contact damage or separation. Parallel main <br /> contacts are not acceptable. Contacts shall be open and inspectable type. <br /> C. Exercise Timer: Include an exerciser with the transfer switches for exercising the generator <br /> in loaded or unloaded condition, up to every 168 hours for a period adjustable from a minimum <br /> of 20 minute intervals to 24 hours. <br /> D. Engine Start Delay: Time delay to override momentary normal source power outages to <br /> delay engine start signal and transfer switch operation. Adjustable 0.5 to 3 seconds,factory <br /> set at 1.5 seconds. <br /> E. Load Test Switch: Load test switch to simulate normal power failure. (Maintained type). <br /> F. Contact Failure indicators: Contact to close on failure of normal source to interface with <br /> data acquisition panel. Contact to open on failure of normal source to initiate customer <br /> functions. <br /> G. Pilot lights: Green push to test pilot light on the cabinet door to indicate the main switch in <br /> normal position. Red push to test pilot light on the cabinet door to indicate the main switch in <br /> emergency position. All lights shall be LED type. No incandescent types are allowed. <br /> H. Auxiliary Contacts: Provide an auxiliary contact closed in normal position. Provide an <br /> auxiliary contact closed in emergency position. <br /> I. Load Shed Relay: Provide a relay energized by 24 volt DC signal from generator control <br /> switchgear to disconnect the load from the emergency source when an overload condition <br /> occurs. <br /> J. Additional Contacts: Two sets of relay contacts shall be provided to open and close upon <br /> loss of the normal power supply. <br /> K. Doors: Door swings shall be as required based on layout. Refer to drawings for door swing <br /> positions. <br /> 2.3 OPERATION <br /> A. Low Voltage: Provide engine starting contacts in transfer switches to start the generator if <br /> any ungrounded phase of the normal source drops below 70 percent of rated voltage,after a <br /> non-adjustable time delay period of 1 to 3 seconds, to allow for momentary dips. <br /> B. Transfer: The transfer switch shall transfer to emergency as soon as the generator source <br /> voltage and frequency have reached 90 percent of rated values. <br /> • C. Stabilization: After restoration of normal power on all phases to 90 to 95 percent of rated <br /> voltage, adjustable time delay period of 2 to 25 minutes shall delay transfer to normal power <br /> until it has had time to stabilize. If the emergency power source shall fail during the time delay <br /> period, the time delay shall be by-passed, and the switch shall return immediately to the <br /> normal source. <br /> D. Generator No-Load Operation: Whenever the switch has retransferred to normal, the <br /> engine-generator shall be allowed to operate at no load for a fixed period of time(5 minutes) <br /> to allow it to cool before shut-down. <br /> E. Test Switch: The transfer switch shall include a test switch to simulate normal power failure <br /> with actual load transfer. <br /> Heartland Health Care Center of Zephyrhills-3181 16490-3 DE No 217032 <br /> 38220 Henry Drive,Zephyrhills, FL 33542 Pending Emergency Rule 59A-4.1265 <br />