Page 5 of 7
<br /> ® MICROMATICO STANDARD
<br /> 0 RESPONSE PENDENT
<br /> SPRINKLER VK102 (K5.6)
<br /> The Viking Corporation,210 N Industrial Park Drive, Hastings MI 49058
<br /> Telephone: 269-946-9601 Technical Services:877-384-5464 Fax: 269-818-1680 Email:techsvcs@vikingcorp.com
<br /> Visit the Viking website for the latest edition of this technical data page www.vikinggroupine.com
<br /> Approval Chart 2 (IFM)
<br /> Micromatic®Standard Response Pendent Sprinkler UK102 Temperaturey
<br /> [ffl�
<br /> "WWP '� Esculcheon(Ilapplicable)
<br /> Sprinkler Base Thread Size Nominal K-Factor Overall Length FM Approvals'
<br /> Part Number' SIN NPT BSP U.S. I metric' Inches mm (Refer also to Design Criteria below.)
<br /> Standard Orifice
<br /> 12987 VK102 1/2" 15 mm 5.6 80.6 1 2-1/4" 57 Al,B2,C3, D1, E4,G1Y,G4Z
<br /> 12989 VK102 — 15 mm 5.6 80.6 2-1/4" 57 A1,B2,C3, D1, E4,G1Y,G4Z
<br /> NOTICE- .• Office)
<br /> 10139 VK102 1/2" 15 mm 5.6 80.6 2-1/4" 57 Al, B2,C3, D1, E4,G1Y,G4Z
<br /> 10173 VK102 — 15 mm 5.6 80.6 2-1/4" 57 Al,B2,C3, D1, E4,G1Y,G4Z
<br /> 18020 VK102 1/2" 1 15 mm 5.6 80.6 2-1/4" 57 Al, B2,C3, D1,G1Y
<br /> Approved Temperature Ratings
<br /> A - 135 OF (57 °C), 155 OF (68 °C), 175 OF (79
<br /> °C), 200 OF (93 °C), 212 OF (100 °C),
<br /> 286 OF(141 °C),and 360 OF(182°C) Approved Finishes
<br /> B-135 OF(57°C), 155 OF(68°C), 175 OF(79°C),200 OF 1 - Brass, Chrome, White Polyester4, and Approved Escutcheons
<br /> (93°C),and 212 OF(100°C) Black Polyester' Y- Standard surface-mounted escutcheon
<br /> C-286 OF(141 °C) 2-Wax-Coated Brass(corrosion resistant) or recessed with the Viking Micromatic@
<br /> Model E-1, E-2, or E-3 Recessed
<br /> D-500 OF(260°C)5 3 - High Temperature 200 OF (93 °C) Wax Escutcheon
<br /> E-155 OF(68°C), 175 OF(79°C),200 OF(93°C),286 OF Coating (corrosion resistant); maximum am- Z - Standard surface-mounted escutcheon
<br /> (141 °C),360 OF(182°C),and 500 OF(260°C)5 bient temperature allowed at the ceiling = or re- cessed with the Viking Micromatic®
<br /> 150°F(65°C) g
<br /> F- 135 OF (57 °C), 155 OF (68 °C), 175 OF (79 °C), and 4-ENT6 Model E-1
<br /> 200 OF(93°C)
<br /> G-155 OF(68°C), 175 OF(79°C),and 200 OF(93°C)
<br /> Footnotes
<br /> 'Base part number is shown.For complete part number,refer to Viking's current price schedule.
<br /> s Metric K-factor shown is for use when pressure is measured in bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0.
<br /> 'This table shows the listings and approvals available at the time of printing.Check with the manufacturer for any additional approvals.
<br /> 4 Other colors are available on request with the same Approvals as the standard colors.
<br /> 5 Sprinklers of Ultra-High temperature rating are intended for use inside ovens,dryers,or similar enclosures with normal operating temperatures above 300°F(149°C).
<br /> Where the ambient temperature around the Ultra-High temperature rated sprinkler is significantly reduced below 300°F(149°C),the response time of the Ultra-High
<br /> temperature rated sprinkler may be severely retarded.
<br /> 6 FM approved as corrosion resistant.
<br /> °qa3
<br /> . ' < 2_DE�IGN*CRITERIA
<br /> f S r . PJso refer to A roval'Char#2 r=
<br /> i s .. . k z ;fir)'"( . PP
<br /> FM Approval Requirements:
<br /> The Viking Micromatic®Standard Response Pendent Sprinkler VK102 is is FM Approved as standard response Non-Storage pendent sprinkler as
<br /> indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data
<br /> Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply
<br /> requirements,hydraulic design,ceiling slope and obstructions,minimum and maximum allowable spacing,and deflector distance below the ceiling.
<br /> NOTE:The FM installation guidelines may differ from cULus and/or NFPA criteria.
<br /> IMPORTANT:Always refer to Bulletin Form No.F 091699-Care and Handling of Sprinklers.Also refer to Form No. F 080614
<br /> for general care,installation,and maintenance information.Viking sprinklers are to be installed in accordance with the latest
<br /> edition of Viking technical data,the appropriate standards of NFPA, FM Global, LPCB,APSAD,VdS or other similar organiza-
<br /> tions,and also with the provisions of governmental codes, ordinances,and standards,whenever applicable.
<br /> Form No. F_031414 19.02.21 Rev 19.1