Page 4 of 7
<br /> MICROMATIC® STANDARD
<br /> N I Ki RESPONSE PENDENT
<br /> SPRINKLER VK102 (K5.6)
<br /> The Viking Corporation,210 N Industrial Park Drive,Hastings MI 49068
<br /> Telephone:269-946-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email:techsvcs@vikingcorp.com
<br /> Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
<br /> Approval Chart 1 (UL) Temperature KEY
<br /> Micromatic°Standard Response Pendent Sprinkler VK102 •�Ftn;sh
<br /> Maximum 1r75 PSI(1.2 bao)WWP A1XFEscutcheon(ifapplipbte)
<br /> Sprinkler Thread Size Nominal Overall Length Listings and Approvals'
<br /> Base Part SIN K-Factor (Refer also to UL Design Criteria.)
<br /> Number' NPT I BSP U.S. metric' Inches mm cULus" VdS LPCB E e 9
<br /> Standard Orifice
<br /> 12987 VK102 1/2" 15 mm 5.6 80.6 2-1/4" 57 Al.B4,B1Y,C5,D3,E6,G6Z A2 A2,B4,132Y F2,G2Y F2X' -
<br /> 12989 VK102 - 15 mm 5.6 80.6 2-1/4" 57 Al.B4,B1Y,C5,D3,E6,G6Z A2 A2,B4,B2Y F2,G2Y F2X9 -
<br /> 19776 VK102 1/2" - 5.6 80.6 2-1/4" 57 - - - - - E7
<br /> 20229 VK102 - 15 mm 5.6 80.6 2-1/4" 57 - - - - - E7
<br /> • Office)
<br /> 10139 VK102 1/2" 15 mm 5.6 80.6 2-1/4" 57 Al,B4,B1Y,C5,D3,E6,G6Z - - - - -
<br /> 10173 VK102 - 15 mm 5.6 80.6 2-1/4" 57 Al,B4,B1Y,C5,D3,E6,G6Z A2 A2,B4,B2Y - F21N. -
<br /> 18020 J VK102 1 1/2" 15 mm 5.6 80.6 2-1/4" 57 Al,B4,B1Y,C5,D3,E6,G6Z A2 A2,B4,B2Y F2,G2X F2W' -
<br /> Approved Temperature Ratings
<br /> A- 135°F(57°C), 155°F(68 °C), 175°F(79 Approved Finishes
<br /> °C), 200 °F (93 °C), 286 °F (141 °C), and 360
<br /> °F(182°C) 1 - Brass, Chrome, White Polyesters.6, and Black
<br /> B-135°F(57°C), 155°F(68°C), 175°F(79 Polyester5,6 Approved Escutcheons
<br /> °C),and 200°F(93°C) 2-Brass,Chrome,White Polyester6,and Black Polyesters X - Recessed with the Viking Micromatic® Model
<br /> C-286°F(141 °C) 3-Brass and Chrome E-1,E-2,or E-3 Recessed Escutcheon
<br /> D-500°F(260°C)7 4-Wax-Coated Brass and Wax Over Polyesters Y - Standard surface-mounted escutcheon or re-
<br /> cessed with the Viking Micromatic Model E-1, E-2,
<br /> E-155°F(68°C), 175°F(79°C),200°F(93 5-High Temperature 200°F(93°C)Wax Coating(corro- or E-3 Recessed Escutcheon
<br /> °C), 286°F(141 °C), 360°F(182°C),and 500 sion resistant);maximum ambient temperature allowed at Z - Standard surface-mounted escutcheon or re-
<br /> -F(260-C)7 ceiling=150°F(65°C) cessed with the Viking Micromatic®Model E-1
<br /> F- 155°F(68°C), 175°F(79 °C),200°F(93 6-ENT5
<br /> °C),266°F(141 °C), and 360°F(182°C) 7-Chrome
<br /> G-155°F(68°C), 175°F(79°C), and 200°F
<br /> (93°C)
<br /> Footnotes
<br /> Base part number is shown.For complete part number,refer to Viking's current price schedule.
<br /> 'Metric K-factor shown is for use when pressure is measured in bar.When pressure is measured in kloa,divide the metric K-faclor shown by 10.0.
<br /> 'This table shows the listings and approvals available at the time of printing.Check with the manufacturer for any additional approvals.
<br /> <Listed by Underwriters Laboratories Inc.for use in the U.S.and Canada.
<br /> 5 cULus Listed as corrosion resistant.
<br /> 5 Other colors are available on request with the same Listings and Approvals as the standard colors.
<br /> 7 Sprinklers of Ultra-High temperature rating are intended for use inside ovens,dryers,or similar enclosures with normal operating temperatures above 300•F(149•C).Where the ambient temperature around
<br /> the Ultra-High temperature rated sprinkler is significantly reduced below 300°F(149°C),the response time of the Ultra-High temperature rated sprinkler may be severely retarded.
<br /> °CE Certified,Standard EN 12259-1,EC-cenmcate of constancy of performance 0832-CPRS0021.
<br /> a MED Certified,Standard EN 12259-1:EC-certificate 0832-MED-1003.
<br /> 0'�'ffi DESIGN" CRITERIA- UL
<br /> (Also refer�"to�Appr'�o alCfia
<br /> '.&§ �an.JCa��,.y,�,"Aq,-;yl .,;` ,Msv:__w.;�,.; a.x: re..,t+a.ra .
<br /> cULus Listina Requirements:
<br /> The Viking Micromatic®Standard Response Pendent Sprinkler VK102 is cULus Listed as indicated in Approval Chart 1 for installation in accordance
<br /> with the latest edition of NFPA 13 for standard spray sprinklers.
<br /> • Designed for use in Light,Ordinary,and Extra Hazard occupancies.
<br /> • The sprinkler installation rules contained in NFPA 13 for standard spray pendent sprinklers must be followed.
<br /> IMPORTANT:Always refer to Bulletin Form No.F 091699-Care and Handling of Sprinklers.Also refer to Form No. F 080614
<br /> for general care,installation,and maintenance information.Viking sprinklers are to be installed in accordance with the latest
<br /> edition of Viking technical data,the appropriate standards of NFPA, LPCB,APSAD,VdS or other similar organizations, and
<br /> also with the provisions of governmental codes,ordinances,and standards,whenever applicable.
<br /> Form No. F_031414 19.02.21 Rev 19.1