Page 4 of 7
<br /> STANDARD RESPONSE
<br /> DRY PENDENT STANDARD
<br /> ORIFICE SPRINKLERS
<br /> The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
<br /> Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
<br /> Visit the Viking website for the latest edition of this technical data page.
<br /> Approva'I Chart � (1�L) Temperature K�
<br /> Standard Response Standard Orifice Dry Pentlent Sprinklers,�-Finish
<br /> Maximum 175 PSI(s1>2 bar,)WWP A1X� Escutcheon(ifapplirable)
<br /> Sprinkler Thread Size Nominal Order Length Listings and Approvals°
<br /> Base SIN Style K-Factorz Increment (Refer also to Design Criteria below.)
<br /> Part No: NPT BSP U.S. metric' Inches mm cULus5 NYC' ® LPCB ' o a
<br /> 07740U VK154 Adjustable 1" - 5.6 - 1/2" 12.7 Al A6 Al - -- - -
<br /> 07854U -- 25 mm -- 80.6 1/2" 12.7 Al A6 - - -- - -
<br /> 09341 VK155 Standard 25 min 80.6 1/2" 12.7 A2 A2 A2
<br /> 0653OU 1" - 5.6 - 1/4" 6.35 B3 B7 B3 - -- - -
<br /> 07853U -- 25 mm -- 80.6 1/4" 6.35 B3, B7 - -- -- - --
<br /> 20239U VK158 Adjustable 1" - 5.6 - 1/4" 6.35 - - C9 -- - -
<br /> 20374U Recessed __ 25 mm -- 80.6 1/4" 6.35 - - C9 -- - -
<br /> 09342 VK159 1 25 mm 80.6 1/4" 6.35 B3 B3 B3
<br /> 07852U VK150 Plain 1" - 5.6 - 1/2" 12.7 A4 A8 A5 - -- - -
<br /> 07855U 25 mm 80.6 112" 12.7 A4 A8 - - -- - -
<br /> 09343 VK151 Barrel 25 mm 80.6 1/2" 12.7 - A5 A5 A5
<br /> Approved Finishes and "A"Dimensions
<br /> 1 - Chrome or White Polyester' sprinkler with a Chrome or White Polyester Sleeve and
<br /> Approved Temperature Ratings Escutcheon with"A"dimensions 1-1/2"to 45-1/2"(38.1 mm to 1,156 mm)
<br /> pp p g 2-Chrome with"A"dimensions 1-1/2"to 45-1/2"(38.1 mm to 1,156 mm)
<br /> A- 155 `F (68 °C), 175 °F (79°C), 200 °F (93 °C), 3-Chrome or White Polyester'with"A"dimensions 3-1/4"to 47-1/2"(82.5 to 1,207 mm)
<br /> and 286°F(141 °C) 4-Chrome,White Polyester',or Brass with"A"dimensions 3"to 47"(76.2 to 1,194 mm)
<br /> 5-Chrome or Brass with"A"dimensions 3"to 47"(76.2 mm to 1,194 mm)
<br /> B-155°F(68°C), 175°F(79°C),and 200°F(93°C) 6-ENT'sprinkler with an ENT'Sleeve and Escutcheon with"A"dimensions 1-1/2"to 45-1/2"
<br /> C-155-F(68°C) (38.1 mm to 1,156 mm)
<br /> 7-ENT'with"A"dimensions 3-1/4"to 47-1/2"(82.5 to 1,207 mm)
<br /> 8-ENT'with"A"dimensions 3"to 47"(76.2 to 1,194 mm)
<br /> 9-Chrome with"A"dimensions 3-1/4"to 47-1/2"(82.5 to 1,207 mm)
<br /> Footnotes
<br /> Part number shown is the base part number.For complete part number,refer to current Viking price list schedule.
<br /> s K-Factor applies for standard lengths("A"Dimensions indicated above).
<br /> 'Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0.
<br /> "This chart shows the listings and approvals available at the time of printing.Other approvals may be in process.Check with the manufacturer for any
<br /> additional approvals.
<br /> 5 Listed by Underwriter's Laboratories for use in the U.S.and Canada.
<br /> 6 Accepted for use,City of New York Department of Buildings, MEA 89-92-E,Vol.37.
<br /> 'CE Certified,Standard EN 12259-1, EC-certificate of conformity 0832-CPR-S0021.
<br /> 'MED Certified,Standard EN 12259-1, EC-certificate 0832-MED-1003.
<br /> 'cULus Listed as corrosion resistant.
<br /> 9. FINIII All,
<br /> Nil 11
<br /> `,� DESIGNtCRITERI�4 �UL.
<br /> . ,r ' m , (Alsorefer to Approval Chaitil'above_t)
<br /> w. r ,� gyp.•. �.. n_ti-,.
<br /> NOTE:When using CPVC fittings with Viking dry sprinklers,use only new Nibco Model 5012-S-BI tees.When selecting other CPVC fittings,
<br /> contact Viking Technical Services.
<br /> cULus Listing Reauirements:
<br /> Standard Dry Pendent Sprinklers are cULus Listed as indicated in Approval Chart 1 for installation in accordance with the latest edition of NFPA 13 for
<br /> standard spray pendent sprinklers.
<br /> • Designed for use in Light,Ordinary,and Extra Hazard occupancies.
<br /> • Protection areas and maximum spacing shall be in accordance with the tables provided in NFPA 13.
<br /> • Minimum spacing allowed is 6 ft.(1.8 m)unless baffles are installed in accordance with NFPA 13.
<br /> • Locate no less than 4"(102 mm)from walls.
<br /> • Maximum distance from walls shall be no more than one-half of the allowable distance between sprinklers.The distance shall be measured per-
<br /> pendicular to the wall.
<br /> • The sprinkler installation and obstruction rules contained in NFPA 13 for standard spray pendent sprinklers must be followed.
<br /> IMPORTANT.Always refer to Bulletin Form No. F_091699-Care and Handling of Sprinklers.Also refer to Form No. F_080614
<br /> for general care, installation,and maintenance information.Viking sprinklers are to be installed in accordance with the latest
<br /> edition of Viking technical data,the appropriate standards of NFPA, LPCB,APSAD, VdS or other similar organizations, and
<br /> also with the provisions of governmental codes, ordinances,and standards,whenever applicable.
<br /> Form No. F 071591 18.06.21 Rev 18.1