Laserfiche WebLink
Global Project Values: <br /> I Project Name:I Professional Hair Labs 'Standby Hours: 24 <br /> . Project ID:I Dialer System Alarm Mins: 5 <br /> Prepared By:QP Derating Factor: 1.2 <br /> • Date: 10/29/2019 Voltage Drop Waming'„ <br /> . Threshold%: 10 <br /> Panel ID: 5104B `Model: 8K-2 Fire-Alarm Control Panel Max NAC Current: 2.5 Amps <br /> .Location: I By Staircase Volts: .24 VDC Max Panel Current: 3.01Amps <br /> Current Draw Wire AWG Ohms-Per Length(ft) Actual Volts @ o" <br /> Ckt.# _' Circuit Name Qty /.Drop <br /> Standby'`Alarm &7 e 1000 Ft. ., One-Wa Ohms EOL <br /> 5104B 5104 Main Control 1 0.080 0.112 <br /> SK-5230 SK-5230 Annunciator 1 0.030 0.056 <br /> IDC-1 Smoke Detector 0.060, 0.023 <br /> IDC-2' PULL 0.000 '0.000 _ <br /> NAC-1, Notification Appl Ckt 1 0.000 0.176 #18 Solid 6.39 150 1.92 20.06 1.65% <br /> 0.000 0.000 #12 Solid 1.59 0.00. 20A0 0.00%,. <br /> Total Standby Current(Am s) 0.110 0.361 Total Alarm Current(Amps] <br /> Standb Time In Hours 24 0.083 Alarm Time In Minutes/60 (5 Mins), , <br /> Total Standby AH R ` uired 2.641 -6.030 Total Alarm AH Required , <br /> Total Combined AH Required 2.671 <br /> Multiply By The Derating Factor 1.20 <br /> Minimum Battery Am Hours Required 3.21 <br /> Command Shortcuts <br /> Configure Circuits Print Page <br /> I <br /> 1 <br /> i <br />