SECTION 4—SYSTEM DESIGN R-102 Restaurant Fire Suppression Manual <br /> UL EX3470 ULC EX3470 <br /> PAGE 4-58 REV. 11 2014-SEP-01 <br /> OVERLAPPING NOZZLE COVERAGE(Continued) Overlapping Appliance Nozzle and Hazard Zone Locations <br /> TABLE 1 1. All overlapping appliance nozzles must be the 245 nozzle <br /> Overlapping Nozzle Coverage(Zone Protection) for "end of zone" protection and the 260 nozzle for zone <br /> protection, and must be located under a common hood at <br /> Appliance Type Maximum Cooking Hazard the same height above the hazard zone, in a straight line <br /> Fryer 34 in. (863 mm) Deep x 5.8 ft2(0.5 m2) from right to left and aimed at the centerline of the hazard <br /> Griddle 30 in. (762 mm) Deep x Unlimited Length zone. The overlapping nozzle is used for both continuous <br /> Range 30 in. (762 mm) Deep x Unlimited Length overlapping and multiple group overlapping protection. <br /> Wok, Maximum 30 in. (762 mm) Diameter x 8 in. 2. The hazard zone must be positioned (located) so that all <br /> (203 mm) Deep appliance hazard surfaces are within the zone. For appli- <br /> Wok, Minimum 11 in. (279 mm) Diameter x 3 in. ance hazard surfaces smaller than the standard hazard <br /> (76 mm) Deep zone size, the hazard surface can be located anywhere <br /> Braising Pan/Tilt 34 in. (863 mm) Deep x Unlimited Length within the standard hazard zone. For appliance hazard <br /> Skillet* surfaces with listed protection exceeding the standard <br /> Lava Rock 26 in. (660 mm) Deep x Unlimited Length hazard zone size of 28 in. (711 mm) in depth (see Table <br /> Char-Broiler(see Note 1) 4-1), the hazard surface(s) must be aligned with the back <br /> Charcoal Broiler 30 in. (762 mm) Deep x Unlimited Length edge of the hazard zone, with the front edge overhanging <br /> (4 in. (101 mm) Maximum Fuel Depth) the front of the zone. <br /> Mesquite Wood 30 in. (762 mm) Deep x Unlimited Length 3. The overlapping appliance nozzles must be located 40 in.to <br /> Broiler (6 in. (152 mm) Maximum Fuel Depth) 45 in. (1016 mm to 1143 mm) above the top surface of the <br /> Gas Radiant 36 in. (914 mm) Deep x Unlimited Length protected appliances. See Figure 4-115. <br /> Char-Broiler Exception No. 1: Nozzle dimensions for wok protection are <br /> Electric Char-Broiler 34 in. (863 mm) Deep x Unlimited Length measured to bottom of wok. Exception No. 2: When using <br /> *See Figure 4-113 for nozzle location overlapping appliance nozzles in areas where there is a <br /> Note 1:Always try to place Lava Rock Char-Broiler(s)near the center of the back shelf, the nozzle cannot be positioned in the shaded <br /> zone.When the Lava Rock Char-Broiler is the first or last appliance in the zone, area as shown in Figure 4-114. <br /> the outside edge of the broiler must not be more than 6 in.(152 mm)outside the <br /> end nozzle. Also, back shelf must not extend more than 11 in. (279 <br /> mm) over the hazard zone and cannot be less than 18 in. <br /> f� (458 mm) above the hazard zone. See Figure 4-114. <br /> 0-12 IN. / OVERLAPPING NOZZLE(S) <br /> COVER MUST NOT I 1 (0-304 mm) 45 / CANNOT BE POSITIONED <br /> INTERFERE WITH i 1 44 IN THIS SHADED AREA <br /> EDGE OF f <br /> DISCHARGE 42 <br /> PATTERN I f 41 <br /> ! 40-45IN. 40 <br /> 1 i (1016-1143 mm) 1210 8 6 4 2 <br /> I , 1 <br /> 1; CENTER LINE OF <br /> ZONE ~HAZARD ZONE <br /> r / BACK <br /> / 'Z SHELF <br /> I <br /> 11 IN.(279 mm) <br /> MAXIMUM <br /> ZONE CENTER LINE 18 IN. <br /> FIGURE 4-113 MINIMUM <br /> 006927 <br /> 28 IN.(711 mm) ►I <br /> FIGURE 4-114 <br /> 006914 <br />