Chapter 1—General Information <br /> C <br /> CHAPTER I <br /> -. GENERAL INFORMATION <br /> INTRODUCTION The shutdown of all soutanes of fuel and electric power that produce <br /> This manual is intended for use with ProTex Er Restaurant Fire heat to all equipment protected by the system is required upon <br /> Suppression Systems.Those who install,operate,recharge,or system actuation.Make up or supply air fans integral to the <br /> maintain these fire suppression systems should read this entire eahanst hood(s)being protected,shall he shut down upon system <br /> manual.Specific sections will he ofparticular interest depending actuation.Upon system actuation,exhaust fan operation shall be in <br /> upon one's responsibilities, accordance with the locally adopted edition of NPPA 96. <br /> Design,installation,recharge,and maintenance ofthe system must The ProTex 11 and the PwTex 2000 Restaurant Fire Suppression <br /> conform to the limitations detailed in this manual and performed Systems are compatible as long as separate installation guidelines <br /> by an individual who attended a ProTex II training Program and are followed per each system design manual.Exception:The-. <br /> became trained to install,recharge,design,and maintain the actuation limitations for the ProTex U system may be utilized for <br /> ProTex U system_ the FmTex2000system.AhA prior model mechawc;il control head <br /> (PIN MCH)maybe utilized on ProTex 11 systems;provided that the <br /> Firer suppression systems are mechanical devices,They need eons used with this control head are followed. <br /> periodic rare.Maintenance is a vital step in the performance <br /> ofyour fire suppression system.As such,it must be performed *gEMPERATURE LIMITATIONS <br /> in accordance with NFPA 96{Standard for the Installation of The operating temperature range of the PwTex H Restaurant Fire <br /> Equipment for the Removal of Smoke and Grease-Laden Vapors Suppression System is 3r F{0-C)minimum to 120°F{49a C) <br /> from Commensal Cooking Equipment)and NFPA 17A(Standard maximum. <br /> on Wet Chemical Extinguishing Systems)by an authorized <br /> ProTex U distributor_To provide maximum assurance that the fire "WLLISTING <br /> suppression system will operate dlfectively and safidy,maintenance <br /> must be conducted at six-month hftxvais,or earlier ifthe The ProTex U Restaurant Fire Suppression System has been tested <br /> situation dictates.Wielve year maintenance must include cylinder to the UL Standard for Fire Extinguishing Systems For Protection <br /> hydrostatic testing, of Restaurant Cooking Areas,ULMO and Listed by Underwriters <br /> Laboratories,Inc. The UL Listing No.is EX452L <br /> The ProTex 11 Restaurant Fire System is a pre-engineered system <br /> that uses a wet chemical extinguishing agent specifically designed; !(ULC LISTING <br /> to suppress restaurant cooking area fires.The system provides The ProTex U Restaurant Fire suppression system is listed by <br /> automatic actuation and can be manually actuated through a. Underwriters Laboratories of Canada(ULC).The ULC Listing No <br /> _ RPSM Remote Mechanical Pull Station.Upon actuation,the system is EX4521. <br /> _ discharges a pre-determined amount of agent to the duct,plenum; <br /> and cooking appliances.The extinguishing agent acts to suppress 1VIEA APPROVAL <br /> fires in thre ways: <br /> The PraTex U Restaurant Fine Suppression System has been <br /> L The chemical chain reaction causing combustion is inter- approved for use by MEA(Material and Equipment Acceptance <br /> = rupted by both the agent itself and the resulting steam Division)for New York City.The MEA Certification No.is <br /> formation. 249-03-E. <br /> 2. The agent cools the fire bringing it below auto-ignition <br /> temperature. <br /> 3. The agent reacts with hot grease forming a soap-like <br /> 1� layer(saponification)that helps prevent the escape of <br /> combustible vapors,thus preventing re-ignition. <br /> i� <br /> 200-DEC-1,Rev D <br /> TU-a a ID"AWT'W <br />