Laserfiche WebLink
D <br /> Q <br /> 2 <br /> t <br /> Single Family Dwelling <br /> Plan Review Comments <br /> 1. ERE; shall be.a minimum of 8" above the road elevation and an engineered site plan. <br /> 2. Lots shall be-graded to comply with R401.3 of the F.B.C. <br /> 3: Compaction test required if 24" or more of fill dirt is brought in at any one place. <br /> 4: Tie in survey required before pouring concrete. <br /> 5. Driveways require a R.O.W. use permit. All 4 sides of driveway thra the sidewalk skull have <br /> expansion material. <br /> 6. All setbacks shall be met. <br /> 7. All property markers shall be uncovered_and marked at time of first inspection. <br /> 8.. All A.D.A."requirer 'eats shall be met: <br /> 9. 'No electric,plumbing, mechanical, or framing shall be covered without an inspection and . <br /> approval first. <br /> 10..A11 Garages shall comply with section R302.6 of the F.B.C. (Fire Separation).: <br /> 1-1. Appliances shall not be installed in a,location where subject to mechanical damage unless <br /> protected by approved barriers. M303.4 of the F.B.0 <br /> 12. Waterheaters shall comply with section P607.3 of the F.B.C. <br /> 13. Foundation supports for A/C units shall be raised at least 3" above finished grade. M1308.1 <br /> 14. Return air in all bedrooms. F.B.C. M1620.4 <br /> 15. Smoke detectors are to be installed in accordance with R3111 of the F.B.C. <br /> 16. All glazing requirements are to be in- accordance with R308.4 of the F.B.C. <br /> 17. All means of egress are to be in accordance with R311 of the R.B.C. <br /> 18. "Green gypsum board" shall not be used as a backer in showers or tubs. R702.4.2 F.B.C. <br /> 10. Combination-type AFCI breakers are required at all locations requiring an AFCI type breaker. <br /> 20. Carbon monoxide alarms will be required in new construction that uses fossil-burning heating <br /> or appliances or an attached garage. 'They shall be-installed in accordance with the F.B.C. <br /> 21. All plumbing,mechanical;and electrical shall be separate from unit to unit-. This includes all <br /> underground plumbing and electric. <br /> 22. All 2016 N.E.C. Codes will be enforced: <br />