ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699, <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017), <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />PTF- <br />DUPLEX OUTLET ABOVE COUNTER <br />W P <br />WEATHERPROOF DUPLEX OUTLET <br />G.F.I. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />$3 <br />THREE-WAY SWITCH <br />�4 <br />FOUR-WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />® <br />HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />WALL MOUNTED LIGHT FIXTURE <br />© <br />RECESSED LIGHT FIXTURE <br />P.C. <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />e� <br />TRACK LIGHT <br />—� <br />FLUORESCENT LIGHT FIXTURE <br />O <br />EXHAUSTFAN <br />;Q <br />EXHAUST FAN/LIGHT COMBINATION <br />M <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH <br />CHIMES (OPTIONAL) <br />PB <br />PUSH BUTTON SWITCH (OPTIONAL) <br />�D <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />0 <br />TELEVISION (OPTIONAL) <br />© 2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />�M <br />ELECTRIC METER <br />Fri_ <br />ELECTRIC PANEL <br />DISCONNECT SWITCH <br />G J <br />ROUGH -IN FOR OPT. CEILING FAN <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />L T J <br />OPT. CEILING FAN <br />W <br />(1) PHONE LINE, (1) DATA PORT <br />3" VTR <br />3" VTR AIL <br />AIL I <br />I I <br />I I <br />I � <br />I I <br />I OPT. <br />I I LAV LAV <br />IIHANSON <br />BOX I <br />3„ <br />�� I W/G <br />LAV <br />3" SHOWER <br />-U TUB/ <br />W/C SHOWER �\ <br />STUDOR <br />VENTT DBL SINK <br />W/ DISP. <br />LAV I WIC <br />PLUMBING RISER <br />SCALE: NTS NOTE: PLUMBING RISER IS SCHEMATIC <br />TO BE VERIFIED WITH PLUMBER <br />LOAD CALCULATIONS <br />UNIT -A 1532 (1532) <br />SQ. FT. AT 3 WATTS / SQ. F.T. <br />1533 S.F. <br />4599 <br />SMALL APPLIANCE CIRCUITS AT 1500 WATTS <br />3 <br />4500 <br />LAUNDRY CIRCUITS AT 1500 WATTS <br />1 <br />1500 <br />SUBTOTAL: 10599 <br />DISHWASHER AT 1200 WATTS <br />1 <br />1200 <br />DISPOSAL AT 960 WATTS <br />1 <br />960 <br />WATER HEATER AT 5500 WATTS <br />1 <br />5500 <br />DRYER OUTLET AT 5000 WATTS <br />1 <br />5000 <br />AIR HANDLER UNIT AT 1200 WATTS <br />1 <br />1200 <br />RANGE AT 8000 WATTS <br />1 <br />8000 <br />MICROWAVE AT 1200 WATTS <br />1 <br />1200 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />OTHER LOAD WATTS <br />0 <br />SUBTOTAL: 23060 <br />TOTAL: 33659 <br />1st 10 KW at 100% <br />10000 <br />BALANCE OF WATTS AT 40% <br />9464 <br />AIR CONDITIONER WATTS AT 100% <br />1 <br />7104 <br />HEAT PUMP WATTS AT 100% <br />0 <br />HEAT PUMP & SUP. HEAT WATTS AT 65% <br />5200 <br />TOTAL: 31768 <br />LOAD WATTS --- 240 VOLTS <br />AMPS: 133 <br />PROVIDE 150 AMP SERVICE <br />Optional Overhead Service 200A <br />Same As Underground Indoor Panel <br />150 Or 200 Amp Service Center <br />NEMA1 <br />200 AMP <br />ETER MAN <br />1 0-200 A P /—Serial Cable <br />3R <br />Power Co. Feed ---, #4 Solid COPPER Ground <br />C.Q. <br />DB & GFI TO <br />BE ALIGNED <br />VERTICALLY <br />COACH LIGHTS <br />OR PREWIRE AS <br />PER SPECS <br />DISCONNECT <br />DEDICATED RECEPTACLE <br />FOR MICROWAVE RANGE <br />HOOD PER SPECS <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY <br />WITH THE SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT FIXTURES <br />SHOWN ARE FOR LOCATION PURPOSES. <br />II <br />Intersystem Bonding-7 Termination Per 1ST ELECTRICAL - UNIT -A 1532 2ND ELECTRICAL - UNIT -A 1532 <br />NEC 17, 250.94 5/8" Galvanized Driven Ground <br />Rods at least 6' apart SCALE: Yn"=1'-0" SCALE: y4'=1'-0" <br />Typical 150-200 Amp Electrical Riser Diagram <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE PROVISIONS OF <br />THE NFPA 70 - 17, LOCAL CODES AND THE LOCAL POWER CO. <br />O <br />O <br />CMLL�r <br />kCU <br />o <br />y <br />� C' _t <br />40 <br />0 <br />-- 0) . <br />C) <br />a 6 <br />0 <br />m <br />r <br /><'. LU <br />CV <br />[V <br />0 <br />c.r <br />rn <br />0 <br />To the best of the Engineers knowledge, information and belief, <br />the structural <br />plans and specifications contained within these <br />drawings comply with the 2020 Florida Building Code - <br />Residential <br />7th Edition. Engineer's signature and seal is only for <br />the structural <br />engineering portions <br />of the drawing pages bearing <br />Engineer's signature and seal, <br />0) <br />g <br />WIm 11- <br />E <br />0 <br />m ° <br />0 <br />0 <br />Y °°a, �� <br />���� <br />fA <br />Q <br />m vu7 <br />LL <br />-� W <br />J LLB LL <br />0 <br />Z <br />13 <br />W <br />— o a Y <br />L N V <br />o <br />f� <br />L � O <br />0 (0O <br />W <br />U�mrn m <br />Z <br />CL LL <br />a7 N Z Q <br />ZN <br />OU < 0 <br />W <br />13❑ <br />Cq M <br />z N M <br />o g <br />z <br />g QN <br />z o <br />U) <br />J <br />N <br />z <br />(4 0 <br />LU <br />O <br />t/1 <br />o <br />c <br />ws <br />W <br />J <br />t <br />_ � 0 <br />C.J a <br />C U <br />Mild <br />¢ N 0 <br />co <br />co <br />w <br />co <br />co0 <br />z <br />z <br />< <br />u <br />QE <br />zo <br />�O <br />>� <br />QN <br />O <br />E U <br />j <br />Z® <br />on <br />ca <br />I <br />�4 <br />W� <br />_° <br />pL <br />Z <br />fp E <br />O <br />N L <br />a p <br />¢ 00 <br />¢ <br />Z <br />r <br />N <br />o <br />�'� <br />.0 <br />z R' <br />CJ� C') <br />J <br />¢w <br />¢w <br />Zz <br />a)00< <br />aO <br />W3wLL <br />�w <br />CD <br />�z <br />¢F <br />=r <br />0 <br />�O <br />IIIIIIIIIIII' <br />�Y <br />W, <br />zl�d <br />aF <br />3 <br />C O <br />0 <br />;n <br />> (� <br />Z <br />� <br />rn <br />E <br />m <br />.-r <br />CN <br />Cfl <br />'' <br />L <br />CO <br />O <br />M <br />Lc� <br />M <br />N <br />N <br />T <br />00 <br />U) m <br />N <br />O <br />L0 <br />a--' <br />N <br />L0 <br />O <br />T <br />N <br />Co <br />C7 <br />0, <br />r <br />Em <br />1 <br />r <br />i6 LC) <br />o <br />Z <br />Z <br />a <br />ca <br />a Ca <br />E <br />U <br />Q 0 <br />� <br />JOB <br />NO: 22-05610-05605 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />1 �1.1 <br />