<br />GENERAL PLUMBING NOTES
<br />1. IN THE PREPARATION OF THESE PLANS, THE ENGINEER HAS USED CERTAIN
<br />ABBREVIATIONS, CONVENTIONS, AND SYMBOLS, THE MEANING OF WHICH
<br />ARE ILLUSTRATED AND EXPLAINED WITHIN THE LEGEND.
<br />2. PLANS ARE DIAGRAMMATIC ONLY. THEY ARE INTENDED TO INDICATE
<br />CAPACITY, SIZE, LOCATION, DIRECTION AND GENERAL ARRANGEMENT, BUT
<br />NOT EXACT DETAILS OF CONSTRUCTION. THE FACT THAT ONLY CERTAIN
<br />FEATURES OF THE INSTALLATION ARE INDICATED MUST NOT BE TAKEN TO
<br />MEAN THAT OTHER FEATURES WILL NOT BE REQ'D.
<br />3. COORDINATE WITH THE OTHER TRADES TO INSURE THAT EACH TRADE
<br />SHALL HAVE SUFFICIENT SPACE TO INSTALL THEIR EQUIPMENT (DUCTWORK,
<br />PIPING, ELECTRICAL WORK, ETC.).
<br />4. EXISTING PIPING SHOWN WAS DERIVED FROM AS -BUILT DRAWINGS
<br />PROVIDED TO ENGINEER. CONTRACTOR SHALL ANTICIPATE DEVIATIONS IN
<br />ACTUAL CONDITIONS.
<br />5. VERIFY ALL DIMENSIONS FROM ARCHITECTURAL PLANS AND FIELD
<br />DIMENSIONS.
<br />6. ALL RISES AND DROPS IN PIPING ARE NOT NECESSARILY SHOWN.
<br />7. PROVIDE STOP OR ANGLE VALVES ON EACH WATER CONNECTION TO EACH
<br />PLUMBING FIXTURE.
<br />8. PROVIDE ALL STRUCTURAL MEMBERS, SUPPORT BRACKETS, FLASHING,
<br />HARDWARE, ETC. REQUIRED TO INSTALL A COMPLETE SYSTEM.
<br />9. PROVIDE CHROME PLATED ESCUTCHEON PLATES AT ALL EXPOSED WALL
<br />PENETRATIONS AND CEILING PENETRATIONS.
<br />10. PROVIDE CLEANOUTS ON SANITARY LINES AND CONDENSATE DRAIN LINES
<br />AS REQUIRED BY CODE.
<br />11. PROVIDE ACCESS PANELS FOR ALL SHUT-OFF VALVES LOCATED ABOVE
<br />GYP. BOARD CEILINGS. COORDINATE WITH G.C..
<br />PLUMBING LEGEND
<br />— —
<br />COLD WATER PIPE
<br />— — — — — —
<br />HOT WATER PIPE
<br />— — —
<br />HOT WATER RETURN PIPE
<br />SOIL OR WASTE PIPE
<br />— —
<br />GREA5E WA5TE PIPE
<br />— — — — — — — —
<br />VENT PIPE
<br />—
<br />SODA/BEER LINES BELOW SLAB
<br />- Q
<br />TURNED UP
<br />— - - -I--�
<br />TURNED DOWN
<br />— - �—
<br />TEE, OUTLET DOWN
<br />— - —Q-- - —
<br />TEE, OUTLET UP
<br />T&P
<br />TEMPERATURE AND PRESSURE
<br />RELIEF DRAIN PIPING
<br />ED
<br />EMERGENCY DRAIN PAN PIPING
<br />GATE VALVE
<br />PRESSURE RELIEF VALVE
<br />BALL VALVE
<br />FIXTURE
<br />PLUMBING FIXTURE
<br />DESIGNATION (UNDERLINED)
<br />CONNECT NEW TO EXISTING
<br />NOT ALL MAY BE USED.
<br />ABBREVIATIONS
<br />AFF
<br />ABOVE FINISHED FLOOR
<br />BTU
<br />BRITISH THERMAL UNIT
<br />CONN
<br />CONNECTION
<br />CW
<br />COLD WATER
<br />ED
<br />EQUIPMENT DRAIN
<br />EXT'G
<br />EXISTING
<br />FCW
<br />FILTERED COLD WATER
<br />FL
<br />FLOOR
<br />FU
<br />FIXTURE UNIT
<br />GC
<br />GENERAL CONTRACTOR
<br />GPM
<br />GALLONS PER MINUTE
<br />HW
<br />HOT WATER
<br />IN
<br />INCHES
<br />MIN
<br />MINIMUM
<br />PC
<br />PLUMBING CONTRACTOR
<br />SAN OR S
<br />SANITARY
<br />V
<br />VENT
<br />VTR
<br />VENT TO ROOF
<br />WTR
<br />WATER
<br />W/
<br />WITH
<br />W/o
<br />WITHOUT
<br />W
<br />WASTE
<br />DN
<br />DOWN
<br />HW
<br />HOT WATER
<br />HWR
<br />HOT WATER RETURN
<br />CO
<br />CLEANOUT
<br />WCO
<br />WALL CLEANOUT
<br />THW
<br />TEMPERED HOT WATER
<br />TP
<br />TRAP PRIMER
<br />PRV/BFP
<br />PRESSURE REDUCING VALVE/
<br />BACKFLOW PREVENTER
<br />NOT ALL MAY BE USED.
<br />GENERALSYMBOLS
<br />PLAN OR DETAIL NO.
<br />SHEET NUMBER
<br />O
<br />KEYED NOTE NUMBER
<br />QREVISION
<br />NUMBER
<br />BUILDING NORTH ARROW
<br />PLUMBING FIXTURE SCHEDULE
<br />CONNECTION SCHEDULE
<br />DESIGNATION
<br />MANUFACTURER
<br />MODEL NO,
<br />FIXTURE DESCRIPTION
<br />WASTE
<br />VENT
<br />Ill
<br />HW
<br />P-1
<br />PEERLESS
<br />766
<br />COMFORT HEIGHT (17" HIGH) VITREOUS CHINA WATER CLOSET
<br />W/ ELONGATED BOWL, FLUSH TANK, 1.6 GPF, ADA COMPLIANT.
<br />3"
<br />2"
<br />1/2"
<br />--
<br />SEAT - SOLID PLASTIC, CLOSED FRONT, WITH COVER.
<br />SUPPLY - 3/8" ANGLE -TYPE WITH STOP.
<br />P-2
<br />PEERLESS
<br />39
<br />VITREOUS CHINA OVAL COUNTERTOP LAVATORY (ADA COMPLIANT)
<br />FAUCET - DELTA 22C131 (ADA COMPLIANT)
<br />TRAP - 1 1 /4" CAST BRASS WITH C.O. PLUG
<br />2"
<br />2"
<br />1 /2"
<br />1 /2"
<br />SUPPLY - 3/8" ANGLE -TYPE WITH STOPS
<br />P-3
<br />SPURLIN INDUSTRIES
<br />NF 60 3W L/R
<br />SHOWER STALL, 60"x35"x8O" MOLDED FIBERGLASS SHOWER.
<br />PROVIDE FULLY EQUIPED, COMPLETE WITH FAUCET (WITH PRESSURE
<br />2"
<br />2"
<br />1 /2"
<br />1 /2"
<br />BALANCING MIXING VALVE), HAND-HELD SHOWER HEAD (W/24" SLIDE
<br />BAR, VACUUM BREAKER & 60" HOSE), HORIZONTAL (L-SHAPED) &
<br />VERTICAL STAINLESS STEEL GRAB BARS, FRAMELESS HDPE FOLD -UP
<br />CUSHIONED SEAT, STAINLESS STEEL CURTAIN ROD, SOAP DISH,
<br />BRASS DRAIN, AND SLIP RESISTANT TEXTURED BOTTOM.
<br />P-4
<br />FIAT
<br />MSB-2424
<br />24"x24"x10" MOLDED STONE MOP RECEPTOR.
<br />3"
<br />2"
<br />1/2"
<br />1/2"
<br />FAUCET - T&S B-0665-BSTR
<br />PIPE MATERIAL LIST
<br />1. SANITARY, WASTE, AND VENT PIPING: FITTINGS SHALL BE LONG RADIUS FITTINGS,
<br />EXCEPT FITTINGS IN VENT PIPING MAY BE SHORT RADIUS FITTINGS. CONTRACTOR
<br />OPTIONS.,
<br />A. BELOW GRADE: SCHEDULE 40 PVC - DWV WITH DRAINAGE PATTERN FITTINGS.
<br />B. ABOVE GRADE: SCHEDULE 40 PVC - DWV WITH DRAINAGE PATTERN FITTINGS,
<br />2. DOMESTIC WATER PIPING CONTRACTORS OPTIONS:
<br />A. ABOVE GRADE: SCHEDULE 80 CPVC.
<br />PLUMBING TESTING AND DISINFECTING:
<br />1. TESTING:
<br />A. SOIL, WASTE, VENT SYSTEM:
<br />1. TEMPORARILY PLUG ALL OUTLETS.
<br />2. FILL LINES WITH WATER TO THE ROOF LEVEL.
<br />3. ALLOW TO REMAIN FULL FOR 24 HOURS.
<br />B. WATER SYSTEM:
<br />1. TEST AT 150 PERCENT OF DESIGN PRESSURE BUT NOT LESS THAN 100 PSIG.
<br />2. ALLOW PRESSURE TO REMAIN ON LINE FOR 24 HOURS.
<br />C. REPAIR ALL DETECTABLE LEAKS IN PIPING SYSTEMS.
<br />2. DISINFECTION OF DOMESTIC WATER SYSTEM:
<br />A. DISINFECT DOMESTIC WATER SYSTEM AFTER APPROVAL OF TEST RESULTS AND PIPING
<br />INSTALLATION BY BUILDING OFFICIAL.
<br />B. PRIOR TO SUBSTANTIAL COMPLETION STERILIZE PIPING SYSTEM IN ACCORDANCE WITH LOCAL
<br />PLUMBING CODE REQUIREMENTS.
<br />C. DELIVER CERTIFICATION TO BUILDING OFFICIAL.
<br />_ cVEIGH & MANGUM
<br />ENGINEERING•INC
<br />340 interstate North Parkway, Suite 360
<br />Atlanta - Georgia 30339
<br />Ph: (678)213-1616 Fax: (679)213-1617
<br />email: mail@McVeighMangum_com
<br />of Record: Farshid Yarizadeh License No.: 40287
<br />FOUSE
<br />ARCHITECTURE
<br />& INTERIORS, P.C.
<br />3201 S. Cherokee Lane Suite 340
<br />Woodstock, Georgia 30188
<br />Voice 678-391-5365
<br />Fax 678-391-5362
<br />email: rlf@fousearchitecture.com
<br />© Copyright 2011 Fouse Architecture & Interiors, P.C.
<br />Seal:
<br />�N1D YA�j
<br />` ay
<br />0
<br />AT f 3! 2,,
<br />RIO
<br />21OINVAL ENGti
<br />Consultants: CIVIL ENGINEER:
<br />�1I�111 71. _1��►Le�J�
<br />McVeigh & Mangum Engineering Inc
<br />340 N Interstate Parkway, Suite 360
<br />Atlanta, GA 30339
<br />Contact: Chad McDonald, P.E.
<br />678.213.1616
<br />MEP ENGINEER:
<br />McVeigh & Mangum Engineering Inc
<br />340 N Interstate Parkway, Suite 360
<br />Atlanta, GA 30339
<br />Contact: Tony G. Fernandez, P.E.
<br />678.213.1616
<br />Sheet Information.
<br />Job Number 11002
<br />Original Issue Date 08-31-2012
<br />Issue Dates:
<br />No.I ISSUE I DATE
<br />I PERMIT/CONSTRUCTION 1 08-31-2012
<br />Sheet Title:
<br />PLUMBING
<br />LEGEND,
<br />NOTES AND
<br />SCHEDULE
<br />Sheet:
<br />Piiiiiiiiiiiiiiiioo_l
<br />FOR CONSTRUCTION