J
<br />ELECTRICAL LEGEND
<br />F21 O
<br />FLUORESCENT TROFFER, TYPE AS NOTED
<br />q�
<br />tT'
<br />DUPLEX RECEPTACLE
<br />18" AFF OR AS NOTED, NEMA 5-20R
<br />[A Lid
<br />FLUORESCENT TROFFER, TYPE AS NOTED
<br />SPO
<br />SURGE PROTECTION DUPLEX RECEPTACLE, 20A, 125V
<br />PROVIDE WITH EMERGENCY BALLAST
<br />HUBBELL CAT.NO HBL5360SA, NEMA 5-20R
<br />®
<br />FLUORESCENT TROFFER, TYPE AS NOTED
<br />DUPLEX RECEPTACLE
<br />ABOVE COUNTER OR AS NOTED, NEMA 5-20R
<br />FLUORESCENT TROFFER, TYPE AS NOTED
<br />QUAD RECEPTACLE
<br />PROVIDE WITH EMERGENCY BALLAST
<br />18" AFF OR AS NOTED, NEMA 5-20R
<br />Q
<br />RECESSED CAN FIXTURE, TYPE AS NOTED
<br />IG
<br />DUPLEX RECEPTACLE
<br />18" AFF OR AS NOTED, NEMA 5-20R
<br />O
<br />RECESSED CAN FIXTURE, TYPE AS NOTED
<br />SPECIAL PURPOSE RECEPTACLE
<br />PROVIDE WITH EMERGENCY BALLAST
<br />18" AFF OR AS NOTED, SEE SCHEDULE
<br />F--Q-�
<br />FLUORESCENT STRIP FIXTURE
<br />FQ/ JQ
<br />WALL / CEILING MOUNTED JUNCTION BOX
<br />^ ,
<br />�, jy
<br />WALL MOUNTED FIXTURE, TYPE AS NOTED
<br />60/3/1
<br />UNFUSED DISCONNECT SWITCH
<br />RATING/POLES/NEMA RATING
<br />60/3/3R/40
<br />FUSED DISCONNECT SWITCH
<br />PENDANT FIXTURE, TYPE AS NOTED
<br />RATING/POLES/NEMA RATING/FUSE SIZE
<br />PENDANT FIXTURE, TYPE AS NOTED
<br />^-
<br />MOTOR
<br />PROVIDE WITH EMERGENCY BALLAST
<br />.��.j.
<br />TRACK LIGHT FIXTURE, TYPE AS NOTED
<br />�II
<br />GROUND
<br />EMERGENCY LIGHT
<br />0
<br />TELEPHONE OUTLET, PROVIDE 4" BOX
<br />SINGLE GANG PLASTER RING, 1" C STUBBED 6" ABOVE CEILING
<br />TELEPHONE OUTLET, PROVIDE 4" BOX
<br />EXIT/EMERGENCY LIGHT COMBINATION
<br />-T
<br />HALF SHADED- INDICATES SINGLE JACK, FULL SHADED INDICATES
<br />TWO JACKS. NETWORK WIRING SYSTEM:
<br />®
<br />CEILING MOUNTED EXIT SIGN
<br />CAT 5E 110, RJ45 JACK WIRED TO SPEC 568B MODULAR JACK
<br />PROVIDE ONE JACK AND ONE POSITION IVORY FACEPLATE AT
<br />WALL MOUNTED EXIT SIGN
<br />SINGLE JACK LOCATIONS AND TWO AT DOUBLE LOCATIONS.
<br />CONTACT PHIL BENTON, 678-966-3335 FOR INFO.
<br />DOUBLE BOX, AS DESCRIBED ABOVE EXCEPT CONNECT 2 LINES
<br />SINGLE POLE SWITCH, 44" AFF
<br />V
<br />DIRECTLY FROM PUNCH BLOCK (D-MARK) TO DOUBLE BOX IN
<br />MANAGER' OFFICE
<br />TWO SINGLE POLE SWITCHES GANGED TOGETHER
<br />FOR INNER/OUTER CONTROL OF LAMPS, 44" AFF
<br />THREE SINGLE POLE SWITCHES GANGED TOGETHER
<br />SINGLE BOX- MANAGER'S/FAX, DEDICATED ANALOG TELEPHONE
<br />44" AFF
<br />®
<br />LINE WITH RINGMASTER, CAT 5E, RJ11 - NOT TO BE ROUTED
<br />THROUGH TELEPHONE SYSTEM. TERMINATE AT PUNCH BLOCK
<br />THREE WAY SWITCH, 44" AFF
<br />(D-MARK)
<br />TWO THREE WAY SWITCHES GANGED TOGETHER
<br />SINGLE BOX- DSULSR DEDICATED ANALOG TELEPHONE LINE
<br />cl
<br />FOR INNER/OUTER CONTROL OF LAMPS, 44" AFF
<br />0
<br />WITH RINGMASTER, CAT 5E, RA 1 - NOT TO BE ROUTED THRU
<br />TELEPHONE SYSTEM. TERMINATE AT PUNCH BLOCK (D-MARK)
<br />FOUR WAY SWITCH, 44" AFF
<br />q
<br />WALL BOX DIMMER 1000W UNLESS NOTED DIFFERENTLY
<br />SPEAKER STROBE
<br />44" AFF
<br />$yip
<br />WEATHER PROOF SWITCH, 44" AFF
<br />HORN
<br />$M
<br />MOTOR RATED SWITCH, 44" AFF OR AS NOTED
<br />®
<br />PULL STATION
<br />$OS
<br />COMBINATION SWITCH AND OCCUPANCY SENSOR, 44" AFF
<br />Q
<br />FIRE ALARM STROBE, MIN 75 CANDELA
<br />CEILING / WALL MOUNT
<br />$T
<br />DIGITAL TIMER SWITCH, 44" AFF
<br />DUCT MOUNTED SMOKE DETECTOR
<br />®x
<br />CEILING MOUNTED OCCUPANCY SENSOR
<br />OS
<br />SMOKE DETECTOR
<br />�X
<br />WALL MOUNTED OCCUPANCY SENSOR, 44" AFF
<br />OH
<br />HEAT DETECTOR
<br />T�
<br />TIME CLOCK
<br />TS
<br />TAMPER SWITCH
<br />LJ�
<br />SINGLE DOME, CEILING AND WALL MOUNTED SECURITY
<br />FS
<br />FLOW SWITCH
<br />CAMERAS. FURNISHED AND INSTALLED BY OTHERS.
<br />®
<br />PHOTO CELL
<br />RACEWAY CONCEALED IN WALL OR ABOVE CEILING
<br />8" CONE SPEAKER IN CEILING
<br />_�
<br />RACEWAY EXPOSED
<br />EC TO PROVIDE BLACK SPEAKER
<br />(�
<br />8" CONE SPEAKER IN WALL
<br />RACEWAY CONCEALED IN FLOOR SLAB, BELOW SLAB OR GRADE
<br />Y
<br />EC TO PROVIDE BLACK SPEAKER
<br />BELOW SLAB OR GRADE, OR UNDER RAISED ACCESS FLOOR
<br />VOLUME CONTROL
<br />DENOTES CONDUIT TURNING UP IN PLAN VIEW
<br />PLYWOOD EQUIPMENT BACKBOARD
<br />3
<br />DENOTES CONDUIT TURNING DOWN IN PLAN VIEW
<br />4'X8' UNLESS NOTED OTHERWISE
<br />CCTV
<br />CLOSED CIRCUIT TELEVISION CAMERA
<br />STUB UP
<br />COAXIAL CABLE OUTLET
<br />XXXX
<br />SHORT CIRCUIT AVAILABLE CURRENT
<br />(NOTE: ALL SYMBOLS SHOWN MAY NOT APPEAR ON DRAWINGS AND ARE USED AS APPLICABLE TO THIS PROJECT)
<br />ABBREVIATIONS
<br />ELECTRICAL SPECIFICATIONS
<br />A. DEFINITIONS:
<br />1. "PROVIDE": FURNISH AND INSTALL, COMPLETE AND READY FOR OPERATION.
<br />2. "INSTALL": RECEIVE, MOUNT, AND CONNECT, COMPLETE AND READY FOR OPERATION.
<br />3. "FURNISH": SUPPLY, DELIVER TO JOB SITE, PROTECT AND STORE.
<br />B. WORK INCLUDED: PROVIDE ALL LABOR, TOOLS, MATERIAL, EXCAVATION, BACKFILL, CUTTING, PATCHING, TESTING,
<br />ADJUSTING, AND TRADE COORDINATION REQUIRED FOR A COMPLETE AND FULLY OPERATIONAL INSTALLATION, AS
<br />DESCRIBED ON THE DRAWINGS OR IN THE SPECIFICATIONS.
<br />C. CODES, RULES, AND REGULATIONS: COMPLY WITH ALL CODES ENFORCED BY THE LOCAL INSPECTION AUTHORITY,
<br />THE EDITION OF THE NATIONAL ELECTRICAL CODE BEING ENFORCED FOR THIS PROJECT BY THE LOCAL INSPECTION
<br />AUTHORITY, ALL APPLICABLE LAWS AND ORDINANCE, NFPA FIRE CODES, STANDARD BUILDING CODE. GIVE ALL
<br />NECESSARY NOTICES, OBTAIN ALL REQUIRED PERMITS, AND PAY ALL INSPECTION AND OTHER FEES REQUIRED BY
<br />AUTHORITIES HAVING JURISDICTION OVER THE WORK.
<br />D. MATERIALS: ALL MATERIAL SHALL BE NEW, AND SHALL COMPLY WITH THE INDICATED STANDARDS. ALL MATERIAL
<br />SHALL BE UL LABELED OR UL LISTED. ALL MATERIAL SHALL BE OF A SUITABLE TYPE AND RATING FOR THE INTENDED
<br />USE, AND SHALL BE INSTALLED IN CONFORMANCE WITH THE INSTRUCTIONS AND RECOMMENDATIONS OF THE
<br />MANUFACTURER.
<br />E. DRAWINGS
<br />1. THE DRAWINGS ARE SCHEMATIC IN NATURE AND DO NOT SHOW ALL OF THE REQUIRED DETAILS OF THE
<br />WORK. ALL MATERIALS CUSTOMARILY CONSIDERED TO BE A PART OF THE ELECTRICAL WORK AND REQUIRED
<br />FOR A COMPLETE AND OPERATIONAL INSTALLATION SHALL BE PROVIDED WITHOUT ADDITIONAL COST TO THE
<br />OWNER.
<br />2. THE CONTRACTOR SHALL REFER ALSO TO THE ARCHITECTURAL DRAWINGS AND TO THE DRAWINGS OF ALL
<br />OTHER TRADES TO COORDINATE THE ELECTRICAL INSTALLATION. WHERE ELECTRICAL EQUIPMENT IS SHOWN
<br />ON ARCHITECTURAL DRAWINGS OR DETAILS, THE EQUIPMENT SHALL BE INSTALLED AS SHOWN ON THE
<br />ARCHITECTURAL DRAWINGS.
<br />3. EQUIPMENT OF OTHER TRADES IS SHOWN SCHEMATICALLY ON THE ELECTRICAL DRAWINGS. THE
<br />CONTRACTOR SHALL EXAMINE THE DRAWINGS OF THE TRADE PROVIDING THE EQUIPMENT BEFORE
<br />ROUGHING IN THE CONNECTIONS FOR IT. THE CONTRACTOR SHALL CONNECT THE EQUIPMENT WHERE
<br />ACTUALLY INSTALLED, INCLUDING WIRING THROUGH ANY LINE VOLTAGE CONTROLLERS, WITHOUT ANY
<br />ADDITIONAL COST TO THE OWNER.
<br />4. PRIOR TO ROUGHING IN CIRCUITS FOR EQUIPMENT FURNISHED BY OTHER TRADES, AND PRIOR TO RELEASING
<br />FOR MANUFACTURE PANELBOARDS, STARTERS OR MOTOR CONTROL CENTERS FEEDING SUCH EQUIPMENT,
<br />THE CONTRACTOR SHALL COORDINATE THE ELECTRICAL PROVISIONS BEING PLANNED WITH THE TRADE
<br />PROVIDING THE EQUIPMENT AND SUBMIT ANY CONFLICTS IN WRITING TO THE ARCHITECT.
<br />5. THE ARCHITECT MAY DIRECT THE RELOCATION OF ANY ELECTRICAL OUTLET, FIXTURE, OR OTHER EQUIPMENT
<br />TO A LOCATION WITHIN 10 FEET OF THE LOCATION SHOWN ON THE DRAWINGS AT NO ADDITIONAL COST TO
<br />THE OWNER PROVIDED SUCH RELOCATION IS DIRECTED PRIOR TO THE INSTALLATION OF THE OUTLET,
<br />FIXTURE OR EQUIPMENT BEING RELOCATED.
<br />D. SUBMITTAL DOCUMENTS: PRODUCT DATA AND SHOP DRAWINGS SHALL BE SUBMITTED IN SIX COPIES TO THE
<br />ARCHITECT FOR REVIEW PRIOR TO THE RELEASE OF THE MATERIAL FOR MANUFACTURE. REVIEW OF SUBMITTALS
<br />BY THE ARCHITECT WILL BE ONLY FOR GENERAL CONFORMANCE WITH THE DRAWINGS AND SPECIFICATIONS.
<br />REVIEW WILL BE MADE ONLY OF INFORMATION CLEARLY AND SPECIFICALLY INDICATED IN THE SUBMITTAL, AND
<br />DOES NOT IMPLY THE ACCEPTABILITY OF DETAILS WHICH ARE NOT SO DESCRIBED IN THE SUBMITTAL. REVIEW OF
<br />THE SUBMITTAL DOCUMENTS BY THE ARCHITECT DOES NOT RELIEVE THE CONTRACTOR OF THE RESPONSIBILITY TO
<br />COMPLY WITH ALL REQUIREMENTS OF THE DRAWINGS AND SPECIFICATIONS. SUBMITTAL IS REQUIRED FOR
<br />PANELBOARDS AND LOADCENTERS, LIGHT FIXTURES, WIRING DEVICES, FIRE ALARM DEVICES, AND SURFACE
<br />ALUMINUM RACEWAY.
<br />G. AS -BUILT DRAWINGS: AS -BUILT DRAWINGS SHALL BE MAINTAINED AT THE JOBSITE, AND SHALL BE AVAILABLE FOR
<br />REVIEW DURING CONSTRUCTION. AS -BUILT DRAWINGS SHALL BE KEPT CURRENT DURING THE COURSE OF
<br />CONSTRUCTION OF THE WORK. SUBMIT AS -BUILT DRAWINGS TO THE ARCHITECT AT THE COMPLETION OF THE
<br />PROJECT.
<br />H. TESTING: TEST ALL PARTS OF THE WORK TO VERIFY COMPLIANCE WITH THE DRAWINGS AND SPECIFICATIONS.
<br />VERIFY TIGHTNESS OF ALL MECHANICAL AND ELECTRICAL CONNECTIONS. VERIFY INTEGRITY OF ALL WIRING
<br />SYSTEMS TO ASSURE CONTINUITY, ABSENCE OF UNINTENTIONAL GROUNDS, AND INTEGRITY OF REQUIRED
<br />GROUNDS.
<br />I. CHANGE REQUEST (CHANGE ORDER) APPROVAL: CHANGE REQUESTS WILL NOT BE CONSIDERED UNLESS THE
<br />CONTRACTOR'S DETAILED LABOR AND MATERIAL ESTIMATE DESCRIBING THE CHANGE IS SUBMITTED TO THE
<br />ARCHITECT ALONG WITH THE CHANGE REQUEST, WITH MATERIAL PRICES AND LABOR UNITS ASSIGNED TO EACH
<br />LINE ITEM OF THE ESTIMATE. MATERIAL PRICES SHALL BE THE ACTUAL PRICE PAID BY THE CONTRACTOR FOR
<br />MATERIAL PURCHASED OR THE ACTUAL PRICE QUOTED TO THE CONTRACTOR BY THE MATERIAL VENDOR
<br />PROPOSED BY THE CONTRACTOR.
<br />J. COORDINATION WITH THE WORK OF OTHERS: COORDINATE WITH EACH TRADE FURNISHING EQUIPMENT REQUIRING
<br />ELECTRICAL SERVICE TO INSURE THAT THE CHARACTERISTICS SHOWN ON THE DRAWINGS FOR THE CIRCUIT
<br />SERVING THE EQUIPMENT ARE COMPATIBLE WITH THE REQUIREMENTS OF THE EQUIPMENT BEING FURNISHED.
<br />CIRCUIT BREAKERS, FUSES, DISCONNECT SWITCHES AND ASSOCIATED BRANCH CIRCUITS SHOWN ON THE
<br />DRAWINGS TO FEED HVAC EQUIPMENT, KITCHEN EQUIPMENT, ELEVATOR MOTORS, AND OTHER EQUIPMENT HAVE
<br />BEEN SELECTED BASED UPON THE CHARACTERISTICS OF EQUIPMENT BY ONE MANUFACTURER AND MAY NOT BE
<br />CORRECT FOR THE EQUIPMENT BEING PROVIDED BY THE CONTRACTOR. THE CONTRACTOR SHALL DETERMINE THE
<br />OPERATING CHARACTERISTICS OF THE EQUIPMENT ACTUALLY BEING PROVIDED AND SHALL PROVIDE AT NO
<br />ADDITIONAL COST TO THE OWNER CIRCUIT BREAKERS, FUSES, DISCONNECT SWITCHES AND BRANCH CIRCUITS AS
<br />REQUIRED BY THAT EQUIPMENT.
<br />K. EXISTING WORK: THE EXISTING ELECTRICAL INSTALLATION SHALL REMAIN AS -IS AND IN OPERATION EXCEPT WHERE
<br />OTHERWISE REQUIRED. GIVE WRITTEN NOTICE OF ANY UNFORESEEN EXISTING CONDITIONS WHICH MAY AFFECT
<br />THE WORK. WORK INVOLVING EXISTING SYSTEMS OR EXISTING SPACES SHALL BE ACCOMPLISHED WITH MINIMUM
<br />INCONVENIENCE TO THE OWNER, AND SHALL BE DONE IN A MANNER AND TIME APPROVED BY THE OWNER. ANY
<br />INTERRUPTIONS SHALL BE DURING TIMES DESIGNATED BY THE OWNER.
<br />L. DEMOLITION: IN THE AREA SHOWN ON THE ARCHITECTURAL DRAWINGS TO BE DEMOLISHED REMOVE ALL EXISTING
<br />A, AMPS
<br />AMPERES
<br />FLA
<br />FULL LOAD AMPERES
<br />NO
<br />NORMALLY OPEN,
<br />CONDUITS, CONDUCTORS, BOXES, FIXTURES, SERVICE ENTRANCE CONDUCTORS, DISTRIBUTION EQUIPMENT, AND
<br />A/C
<br />AIR CONDITIONER
<br />GND
<br />GROUND
<br />NUMBER
<br />ALL OTHER ELECTRICAL EQUIPMENT NOT SHOWN TO REMAIN. UNLESS OTHERWISE INDICATED, MATERIAL BEING
<br />AC
<br />ALTERNATING CURRENT
<br />GALV
<br />GALVANIZED
<br />NTS
<br />NOT TO SCALE
<br />REMOVED INCLUDING WIRE, CONDUIT, AND HANGING MATERIALS BEING REMOVED SHALL BECOME THE PROPERTY
<br />AF
<br />AMPERE FRAME
<br />PNL
<br />PANELBOARD
<br />OF THE CONTRACTOR AND SHALL BE REMOVED FROM THE PREMISES. EQUIPMENT NOTED TO REMAIN THE
<br />AFF
<br />ABOVE FINISHED FLOOR
<br />GRS
<br />GALVANIZED RIGID STEEL
<br />PVC
<br />POLYVINYL CHLORIDE
<br />PROPERTY OF THE OWNER SHALL BE STORED ON SITE AS DIRECTED BY THE ARCHITECT. COORDINATE WITH OTHER
<br />AFG
<br />ABOVE FINISHED GRADE
<br />GFCI
<br />GROUND FAULT
<br />RGS
<br />RIGID GALVANIZED
<br />TRADES AND DISCONNECT MOTORS, HEATERS, OR OTHER EQUIPMENT AS REQUIRED FOR THE DEMOLITION OF
<br />AIC
<br />AMPERE
<br />CIRCUIT INTERRUPTER
<br />STEEL CONDUIT
<br />OTHER TRADES WORK. CUT OFF ALL IN FLOOR CONDUITS, GRIND SMOOTH WITH FLOOR AND PREPARE FOR
<br />GFI
<br />GROUND FAULT INTERRUPTER
<br />RMC
<br />RIGID METALLIC
<br />PATCHING BY OTHERS. REMOVE CONDUCTORS AND DEVICES FROM WALL AND CEILING OUTLETS AND PREPARE
<br />INTERRUPTING CURRENT
<br />HD
<br />HEAT DETECTOR
<br />CONDUIT (GALVANIZED)
<br />OUTLET FOR PATCHING BY OTHERS. CONTRACTOR SHALL DENOTE ALL DEMOLISHED CIRCUITS ON EXISTING PANEL
<br />AL
<br />ALUMINUM
<br />HP
<br />HORSEPOWER
<br />RMS
<br />ROOT -MEAN -SQUARE
<br />DIRECTORIES AND NOTE ALL SPARE BREAKERS.
<br />ANSI
<br />AMERICAN NATIONAL
<br />STANDARDS INSTITUTE
<br />IMC
<br />INTERMEDIATE METAL CONDUIT
<br />RNC
<br />RIGID NON-METALLIC
<br />ISC
<br />INTERRUPTING SHORT CIRCUIT
<br />CONDUIT
<br />M. BASIC MATERIALS AND METHODS:
<br />AWG
<br />AMERICAN WIRE GAUGE
<br />IG
<br />ISOLATED GROUND
<br />SCA
<br />SHORT CIRCUIT
<br />BC
<br />BARE COPPER
<br />INST
<br />INSTANTANEOUS
<br />AVAILABLE
<br />1. ALL WORK SHALL BE SUPPORTED FROM STRUCTURAL ELEMENTS OF THE BUILDING, EXCEPT
<br />BKBD
<br />BACKBOARD
<br />JB
<br />JUNCTION BOX
<br />SWBD
<br />SWITCHBOARD
<br />CEILING MOUNTED EQUIPMENT SUCH AS LIGHT FIXTURES, DETECTORS, REMOTE LAMPS, ETC. CEILING
<br />C
<br />CONDUIT
<br />KAIC
<br />KILO (THOUSAND) AMPERES
<br />SWGR
<br />SWIT
<br />ITCHGEAR
<br />MOUNTED EQUIPMENT SHALL BE SUPPORTED FROM CEILING STRUCTURAL MEMBERS, INDEPENDENT OF
<br />CB
<br />CIRCUIT BREAKER
<br />INTERRUPTING CAPACITY
<br />TBD
<br />TO DETERMINED
<br />CEILING TILES. SIZE AND SPACING OF SUPPORTS SHALL BE DETERMINED BY THE LOAD TO BE SUPPORTED SUCH
<br />CKT
<br />CIRCUIT
<br />KCMIL
<br />KILO (THOUSAND)
<br />TCP
<br />TEMPERATURE CONTROL
<br />THAT THE WORKING LOAD OF SUPPORTS WILL NOT EXCEED A SAFETY FACTOR OF 4:1. PLASTIC ANCHORS
<br />CU
<br />COPPER
<br />ARE NOT ACCEPTABLE. ELECTRICAL WORK SHALL NOT BE SUPPORTED FROM PIPING, DUCTS, OR WORK
<br />DIST
<br />DISTRIBUTION
<br />CIRCULAR MILS
<br />PANEL
<br />OF OTHER TRADES.
<br />KV
<br />KILO (THOUSAND) VOLTS
<br />TD
<br />TIME DELAY
<br />DN
<br />DP
<br />DOWN
<br />DISTRIBUTION PANEL
<br />KVA
<br />KILO (THOUSAND)
<br />TEL
<br />TELEPHONE
<br />2. PROVIDE ENGRAVED PLASTIC NAMEPLATES FOR ALL SWITCHBOARDS, PANELBOARDS, MOTOR CONTROL
<br />DWG
<br />DRAWING
<br />VOLT-AMPERES
<br />TVSS
<br />TRANSIENT VOLTAGE
<br />CENTERS, STARTERS, DISCONNECTS, PRIMARY SELECTOR SWITCHES, AND TRANSFORMERS. INDICATE
<br />EB
<br />ENCASED BURIAL
<br />KW
<br />KILO (THOUSAND) WATTS
<br />SURGE SUPPRESSION
<br />EQUIPMENT NAME, CIRCUIT SOURCE AND NUMBER, CIRCUIT SIZE, AMPERE RATING, VOLTAGE AND PHASE.
<br />EC
<br />EMPTY CONDUIT
<br />KWH
<br />KILO (THOUSAND) WATT-HOURS
<br />TYP
<br />TYPICAL
<br />NAMEPLATES SHALL BE BLACK BACKGROUND LAMACOID PLASTIC WITH 0.25" WHITE LETTERS.
<br />LFMC
<br />LIQUID -TIGHT FLEXIBLE
<br />UG
<br />UNDERGROUND
<br />EEW
<br />ENERGIZED ELECTRICAL WORK
<br />METAL CONDUIT
<br />EGC
<br />EQUIPMENT GROUNDING
<br />MCB
<br />MAIN CIRCUIT BREAKER
<br />UL
<br />UNDERWRITER'S LABORATORIES
<br />CONDUCTOR
<br />MCM
<br />THOUSAND CIRCULAR MILS
<br />LION
<br />UNLESS OTHERWISE
<br />ELR
<br />END -OF -LINE RESISTOR
<br />MCCB
<br />MOLDED CASE
<br />UNDERGROUND PULLBOX
<br />EWC
<br />ELECTRIC WATER COOLER
<br />MLO
<br />MAIN LUGS ONLY
<br />V
<br />VOLTS
<br /><E>
<br />EXISTING
<br />N
<br />NEUTRAL
<br />VA
<br />VOLT-AMPERES
<br /><ER>
<br />EXISTING TO REMAIN
<br />NEC
<br />NATIONAL ELECTRICAL
<br />VFD
<br />VARIABLE
<br /><EX>
<br />EXISTING
<br />CODE
<br />FREQUENCY DRIVE
<br />FA
<br />FIRE ALARM
<br />NESC
<br />NATIONAL ELECTRICAL
<br />WH
<br />WATER HEATER
<br />FAA
<br />FIRE ALARM ANNUNCIATOR
<br />SAFETY CODE
<br />WP
<br />WEATHERPROOF
<br />FACP
<br />FIRE ALARM CONTROL PANEL
<br />NIC
<br />NOT IN CONTRACT
<br />WT
<br />WATERTIGHT
<br />NL
<br />NIGHT LIGHT
<br />XFMR
<br />TRANSFORMER
<br />3. ALL PENETRATIONS OF FIRE RATED WALLS, SLABS, PARTITIONS, AND CEILINGS SHALL BE FIREPROOFED
<br />WITH A U.L. LISTED SYSTEM THAT WILL MAINTAIN THE ORIGINAL FIRE RATING OF THE PENETRATED
<br />STRUCTURE. ALL FIREPROOFING MATERIALS APPLIED AT ANY ONE PENETRATION SHALL BE THE PRODUCT OF
<br />ONE MANUFACTURER AND SHALL BE APPLIED AS DESCRIBED BY THE UL FIREPROOFING SYSTEM BEING
<br />CONSTRUCTED. FIREPROOFING OF SLEEVES, CABLE TRAYS, TROUGHS, AND NIPPLES TO BE USED FOR LOW
<br />VOLTAGE CABLES SHALL BE INDEFINITELY NON -HARDENING AND REMOVABLE WITH COMMON HAND TOOLS.
<br />4. BACKBOARDS SHALL BE 8 FT. HIGH BY LENGTH SHOWN ON THE DRAWINGS AND SHALL BE UL LABELED
<br />FIRE TREATED PLYWOOD.
<br />5. PROVIDE ALL POWER WIRING AND CONNECTIONS FOR ALL ELECTRICALLY OPERATED EQUIPMENT. POWER
<br />WIRING INCLUDES WIRING THROUGH ANY LINE VOLTAGE CONTROL DEVICES, SUCH AS THERMOSTATS AND
<br />MANUAL STARTERS. INSTALL ALL STARTERS AND CONTACTORS EXCEPT THOSE FURNISHED AS AN INTEGRAL
<br />PART OF THE EQUIPMENT.
<br />6. CONNECTIONS TO MOTORS, TRANSFORMERS, AND OTHER VIBRATING EQUIPMENT NOT INSTALLED IN A
<br />PLENUM SPACE SHALL BE MADE WITH A SHORT LENGTH OF LIQUIDTIGHT FLEXIBLE CONDUIT, MINIMUM 18",
<br />INSTALLED IN A MANNER TO PERMIT MOVEMENT OF EQUIPMENT.
<br />7. PERFORM ALL EXCAVATING, BACKFILLING, CUTTING AND REPAIRING REQUIRED FOR INSTALLATION OF
<br />ELECTRICAL WORK.
<br />8. CONTRACTOR SHALL X-RAY FLOOR SLABS, WALLS, OR CEILING CONCRETE PRIOR TO ALL CORE DRILLINGS.
<br />N. CONDUIT: FEEDERS AND BRANCH CIRCUIT HOME RUNS SHALL BE CONSTRUCTED OF EMT WITH ALL STEEL
<br />RAINTIGHT OR SET -SCREW FITTINGS. CONNECTORS SHALL BE INSULATED THROAT TYPE. PROVIDE METALLIC
<br />BUSHINGS WITH PLASTIC INSERTS FOR 3" OR LARGER. CONDUITS FEEDING OR CONNECTING TO EQUIPMENT
<br />PROVIDED BY OTHER TRADES SHALL NOT BE INSTALLED UNTIL SUCH EQUIPMENT IS INSTALLED OR UNTIL SPECIFIC
<br />ROUGH -IN INSTRUCTIONS ARE PROVIDED BY THE TRADE PROVIDING THE EQUIPMENT. UNLESS OTHERWISE
<br />INDICATED, CONDUITS SHALL BE CONCEALED. RACEWAYS INSTALLED IN OR UNDER SLABS, ON GRADE, OR AS
<br />EXTERIOR DUCT BANKS SHALL BE PVC SCHEDULE 40 OR 80. RUN EXPOSED CONDUITS PARALLEL OR
<br />PERPENDICULAR TO STRUCTURAL ELEMENTS. TWO OR MORE RACEWAYS RUN TOGETHER SHALL BE INSTALLED ON
<br />GANG TRAPEZE TYPE HANGERS. SUCH RACEWAYS ASSEMBLIES SHALL BE RUN PARALLEL OR PERPENDICULAR TO
<br />STRUCTURAL ELEMENTS. CONDUITS EMBEDDED IN SLABS SHALL HAVE A MINIMUM OF 1" COVER OF CONCRETE ON
<br />ALL SIDES. OUTSIDE DIAMETER OF CONDUIT SHALL NOT EXCEED 1/3 OF THE SLAB THICKNESS. PROVIDE 0.25" NYLON
<br />PULL TAPE IN ALL EMPTY CONDUITS. BRANCH CIRCUITS MAY UTILIZE TYPE MC ARMORED CABLE ASSEMBLY WITH
<br />COPPER CONDUCTORS AND FULL SIZE EQUIPMENT GROUNDING CONDUCTORS FOR INDIVIDUAL DROPS TO DEVICES.
<br />TYPE MC CABLE SHALL BE SUPPORTED AT 48" INTERVALS AND SHALL NOT LAY ON THE CEILING GRID OR INTERFERE
<br />WITH THE REMOVAL OF CEILING.
<br />0. CONDUCTORS: ALL BUILDING WIRE SHALL BE 600 VOLT RATED THHN OR THWN COPPER, STRANDED FOR SIZES
<br />#8AWG AND LARGER, SOLID FOR SIZES 10 AND SMALLER UNLESS APPLIED FOR CONTROL. ALL BUILDING WIRE AND
<br />SPECIAL CABLES FOR SYSTEMS SHALL BE INSTALLED IN A RACEWAY. ALL WIRE AND CABLE SHALL BE DELIVERED TO
<br />THE JOBSITE IN ORIGINAL UNBROKEN PACKAGES, CARTONS OR REELS, WITH THE MANUFACTURERS NAME, UL
<br />LABEL, AND CHARACTERISTICS OF THE PRODUCT PLAINLY VISIBLE. ALL WIRE AND CABLE SHALL BE MANUFACTURED
<br />IN THE UNITED STATES OF AMERICA. WIRES SHALL BE COLOR CODED AS FOLLOWS (A,B,C,N,G): 120/208-BLACK, RED,
<br />BLUE, WHITE, GREEN; 480/277 - BROWN, ORANGE, YELLOW, GRAY, GREEN. SPLICES SHALL BE COMPRESSION TYPE.
<br />CONTROL CONDUCTORS SHALL BE TERMINATED WITH INSULATED CONNECTORS, T&B STAKON. 120 VOLT CIRCUITS
<br />WITH HOMERUN LENGTH OVER 125 FEET AND 277 VOLT CIRCUITS WITH A HOMERUN LENGTH OVER 250 FEET SHALL
<br />HAVE #10 MINIMUM HOMERUN CONDUCTORS. ALL THREE PHASE BRANCH CIRCUITS WITH A COMMON NEUTRAL
<br />SHALL HAVE #10 MINIMUM NEUTRAL.
<br />P. BOXES: OUTLET BOXES SHALL BE SHEET STEEL, MINIMUM 4" SQUARE, MINIMUM 1.5" DEEP, WITH PLASTER RING IN
<br />PLASTER OR BRICK CONSTRUCTION. OUTLETS BOXES IN POURED CONCRETE SHALL BE CONCRETE RINGS.
<br />MASONRY BOXES SHALL BE USED IN MASONRY OR TILE CONSTRUCTION. OUTLET BOXES FOR SURFACE ALUMINUM
<br />RACEWAY SHALL BE 4-11/16 WITH PLASTER RINGS ORIENTED HORIZONTALLY. BOXES SHALL BE SECURELY
<br />ANCHORED IN PLACE, AND SHALL BE SUPPORTED INDEPENDENT OF THE RACEWAY SYSTEM. PULL BOXES SHALL BE
<br />GALVANIZED SHEET STEEL, MINIMUM 12 GAUGE, WITH SCREW COVERS, AND WELDED CONSTRUCTION. WELDS
<br />SHALL BE COLD GALVANIZED. USING PERMANENT WATER PROOF WIDE BLACK MARKER, CLEARLY LABEL COVER OF
<br />ALL BRANCH CIRCUIT JUNCTION AND PULL BOXES WITH PANEL AND CIRCUIT NUMBER OF CIRCUITS CONTAINED IN
<br />OR PASSING THROUGH THE BOX. BRANCH CIRCUIT AND FEEDER JUNCTION AND PULL BOXES USED WITH
<br />EMERGENCY FEEDERS AND CIRCUITS SHALL BE PAINTED RED. PROVIDE P-TOUCH OR DYMO LABELS ON COVER OF
<br />EACH FEEDER PULL OR JUNCTION BOX INDICATING FEEDER DESIGNATION, SOURCE, LOAD, AND VOLTAGE.
<br />Q. WIRING DEVICES: SWITCHES FOR LIGHTING CIRCUITS SHALL BE 120/277 VOLT, 20 AMP, A.C. ONLY, QUIET TYPE, WITH
<br />GROUND BONDING SCREW, SPECIFICATION GRADE. MOMENTARY CONTACT SWITCHES SHALL BE SINGLE POLE
<br />DOUBLE THROW, CENTER OFF GE #5935 OR EQUAL. DUPLEX RECEPTACLES SHALL BE 15 AMP HUBBELL 5262 OR
<br />EQUAL. DEDICATED DUPLEX RECEPTACLES SHALL BE ORANGE 20AMP HUBBELL IG5362 OR EQUAL. SPECIAL
<br />RECEPTACLES SHALL BE OF SIMILAR CONSTRUCTION. FACE PLATES SHALL BE SMOOTH NYLON OR THERMOSET
<br />PLASTIC. ADJACENT OUTLETS SHALL BE INSTALLED IN MULTI -GANG BOXES WITH A SINGLE MULTI -GANG FACE PLATE.
<br />RECEPTACLES CONNECTED TO AN EMERGENCY CIRCUIT SHALL BE RED. COORDINATE COLOR OF DEVICES AND
<br />FACEPLATE WITH ARCHITECT.
<br />R. GROUNDING: ALL FEEDERS AND BRANCH CIRCUITS SHALL BE PROVIDED WITH INSULATED GREEN EQUIPMENT
<br />GROUNDING CONDUCTOR. CONDUIT GROUNDS ONLY ARE NOT PERMITTED.
<br />S. LIGHTING: SPARE FLUORESCENT LAMPS SHALL MATCH BUILDING STANDARD UNLESS OTHERWISE NOTED.
<br />INCANDESCENT LAMPS SHALL BE 130VOLT. NEW BALLASTS SHALL BE SOILD STATE ELECTRONIC. EXIT FIXTURES
<br />SHALL MATCH BUILDING STANDARD. FIXTURE LOCATIONS SHALL BE AS SHOWN ON THE REFLECTED CEILING PLAN.
<br />PROVIDE LAY -IN FIXTURES WITH TWO REMOVABLE CLIPS ATTACHING FIXTURE TO CEILING GRID. FLANGED FIXTURES
<br />SHOWN TO BE INSTALLED IN CONTINUOUS ROWS SHALL NOT HAVE INTERMEDIATE FLANGES. ALL PENDANT
<br />FIXTURES SHALL BE MOUNTED TO STRUCTURE. SEISMIC SUPPORT WIRES AND/OR COMPRESSION STRUTS FOR
<br />LAY -IN FIXTURES SHALL BE SUBJECT TO LOCAL AHJ LATEST REQUIREMENTS.
<br />T. FIRE ALARM DEVICES: NEW FIRE ALARM DEVICES SHALL BE COMPATIBLE WITH EXISTING BUILDING ADDRESSABLE
<br />FIRE ALARM SYSTEM. INSTALL NEW DEVICES AND CONNECT TO NEAREST SIGNALING OR NOTIFICATION DEVICE
<br />CIRCUIT WITHIN THE AREA. CONTRACTOR SHALL VERIFY CIRCUIT HAS CAPACITY FOR ADDED LOAD. SYSTEM SHALL
<br />BE CERTIFIED BY FIRE ALARM VENDOR AFTER COMPLETION OF WORK.
<br />U. PANELBOARDS: DEAD FRONT PANEL CONSTRUCTION WITH SEPARATELY MOUNTED INTERIOR TRIM. MAIN AND
<br />BRANCH DEVICES SHALL BE BOLT -ON. MULTI -POLE BREAKERS SHALL BE COMMON TRIP. WIDTH SHALL NOT EXCEED
<br />22" FOR PANELBOARD AND ENCLOSURE SHALL MATCH BUILDING STANDARD. PROVIDE GROUND BUS IN PANELBOARD
<br />AND PROVIDE DEVICE MOUNTING HARDWARE WHERE A SPACE IS SCHEDULED. PANEL AND OCPD SHORT CIRCUIT
<br />RATINGS SHALL BE AT LEAST 10% GREATER THAN AVAILABLE SHORT CIRCUIT CURRENT AT PANELBOARD.
<br />V. DRY -TYPE TRANSFORMERS: TRANSFORMERS SHALL BE DRY -TYPE, ENCLOSED, SELF -COOLED, VENTILATED TYPE,
<br />DEAD -FRONT DRIP PROOF. PRIMARY AND SECONDARY TAPS SHALL BE ACCESSIBLE FROM THE FRONT.
<br />TRANSFORMERS SHALL MEET OR EXCEED BUILDING STANDARD TRANSFORMERS SPECIFICATIONS. PROVIDE AN
<br />EQUIPMENT GROUNDING CONDUCTOR IN THE PRIMARY FEED TO THE TRANSFORMER, SUPPLEMENTAL GROUND TO
<br />NEAREST ACCESSIBLE PRIMARY STRUCTURAL MEMBER OR EQUIPMENT ROOM GROUND BUS BAR. SIZE PER NEC
<br />AND RUN IN CONDUIT WITH BOND BUSHING AT EACH END. NEUTRAL AND GROUNDING CONDUCTOR SHALL BE
<br />BONDED TO ENCLOSURE.
<br />SF�9F1
<br />E Noo
<br />W74056
<br />S OF
<br />SF�0RIDP•��`;;`�
<br />o
<br />Q
<br />G ICi0 Digitally signed
<br />4
<br />z
<br />by Guido Inoa
<br />J
<br />nOa Alvarez
<br />Date:2018.05.10
<br />A I Va reZ
<br />m
<br />17:29:38-04'00'
<br />Q
<br />U
<br />z
<br />Q
<br />Q
<br />Ui
<br />U)
<br />Z
<br />Q
<br />cm
<br />w
<br />w
<br />J
<br />0 '
<br />•
<br />CONTRACT DATE: 08.13.2017
<br />BUILDING TYPE: ONE-OFF
<br />PLAN VERSION:
<br />SITE NUMBER:
<br />STORE NUMBER:
<br />SUNRISE EATERY
<br />5915 GALL BLVD,
<br />ZEPHYRHILLS, FL
<br />ELECTRICAL
<br />GENERAL
<br />NOTES
<br />& LEGNED
<br />EO.0
<br />PLOT DATE: May 10, 2018 - 5:25pm
<br />
|