Laserfiche WebLink
h <br />w <br />6^ <br />MECHANICAL GENERAL NOTES: <br />1. COORDINATE LOCATIONS WHERE NEW DUCTWORK CROSSES EXISTING CONDUITS, ETC. PROVIDE OFFSETS AS <br />REQUIRED. <br />2, INSTALL FIRE DAMPERS AS REQUIRED WHENEVER NEW OR EXISTING DUCTWORK PASSES THROUGH FIRE REATED <br />WALLS OR FLOORS. RETURN AIR OPENING IN FIRE RATED WALLS SHALL BE EQUIPPED WITH FIRE DAMPERS. SEE ARCH. <br />DRAWINGS FOR RATED WALLS. <br />3. CONTRACTOR TO VERIFY FIELD CONDITIONS PRIOR TO BEGINNING WORK. NOTIFY ENGINEER WITH ANY <br />DISCREPANCIES BETWEEN DRAWINGS AND EXISTING CONDITIONS <br />4. COORDINATE EXACT LOCATIONS OF EQUIPMENT ON ROOF. PROVIDE DUCTED OUTSIDE AIR INTAKE DUCTS TO MAINTAIN <br />10'-0 CLEARANCE FROM EXHAUST OR FLUE DISCHARGE OPENINGS <br />5. NEW KITCHEN HOODS, EXHAUST FANS AND MAKE UP AIR UNIT BY KITCHEN EQUIPMENT SUPPLIER, VERIFY <br />REQUIREMENTS AND PROVIDE GAS, ELECTRICAL CONNECTIONS AS REQUIRED. EXHAUST DUCT TO BE STAINLESS OR <br />BLACK STEEL, ZERO CLEARANCE TO COMBUSTABLE, INSULATED WRAP. HOOD SHALL BE EQUIPPED WITH AN ANSUL <br />FIRE SUPRESSION SYSTEM. MINIMUM AIR VELOCITY IN EXHAUST DUCTWORK SHALL BE A MINIMUM OF 1500 FPM <br />6. COORDINATE ALL WORK WITH ALL OTHER TRADES, RESOLVE CONFLICT PRIOR TO INSTALLATION OF EQUIPMENT. <br />COORDINATE NEW DIFFUSER LOCATIONS WITH LIGHT FIXTURES, SPRINKLER HEADS AND PIPING, CEILING GRID <br />LOCATION PRIOR TO INSTALLATION. <br />7. ALL NEW HVAC EQUIPMENT INCLUDING FANS, RTU AND MUA SHALL BE PROPERLY SUPPORTED FROM THE STRUCTURE. <br />MOUNT ALL ROOFTOP UNITS ON CURBS. PROVIDE VIBRATION ISOLATORS ON ALL EQUIPMENT. ALL EQUIPMENT SHALL <br />BE APPROVED FOR ITS SPECIFIC INTENDED INSTALLATION AND OPERATION. <br />8. DIFFUSER PER SCHEDULE. EACH SHALL BE PROVIDED WITH BALANCING DEVICE AT DIFFUSER RUNOUT WHERE <br />POSSIBLE AND DEVICE FACE -MOUNTED DAMPER OTHERWISE. <br />9, THERMOSTATS FOR NEW RTU'S SHALL BE PROGRAMMABLE STYLE BY HONEYWELL. SUBMIT SHOP DRAWINGS AND <br />VERIFY MODEL NUMBER PRIOR TO PURCHASE. THERMOSTATS MOUNTED AT 42" AFF <br />10. PROVIDE ROOF TOP AIR HANDLING UNIT AS INDICATED ON DRAWINGS. VERIFY EXACT LOCATION WITH ROOF PLAN AND <br />STRUCTURAL DRAWINGS. PROVIDE GAS PIPING CONNECTION AND COORDINATE ELECTRICAL CONNECTION. MOUNT ALL <br />UNITS ON 14" ROOF CURB. ROOF CURBS ABOVE OR A SINGLE FLOOR ABOVE MUSIC INSTRUCTION OR ASSEMBLY AREAS <br />SHALL BE PROVIDED WITH VIBRATION ISOLATION ROOF CURBS. <br />11. PROVIDE NEW GAS SERVICE FROM NEW METER UP TO RTU'S AND EQUIPMENT GAS PIPING TO BE SCHEDULE 40 BLACK <br />STEEL. PROVIDE METER AND PIPING CONNECTION TO ALL AHU'S DUCT FURNACES, HOT WATER HEATER, MAKE UP AIR <br />UNITS AND KITCHEN COOKING EQUIPMENT. GAS PIPING FOR KITCHEN COOKING EQUIPMENT TO BE EQUIPPED WITH A <br />SOLENOID SHUT-OFF VALVES CONNECTED TO HOOD FIRE SUPPRESSION SYSTEM DUCTWORK FOR GRILL HOOD (TYPE 1) <br />SHALL BE WELDED 16 GAGE BLACK IRON, OR STAINLESS STEEL. <br />12. MAKE UP AIR UNITS AND ROOFTOP UNIT FANS AND OUTDOOR AIR DAMPERS SHALL BE INTERLOCKED WITH EXHAUST <br />FANS. <br />13. TYPE I EXHAUST FAN TO TERMINATE AT A MINIMUM 40 ABOVE ROOF, PROVIDE FAN WITH 24" METAL ROOF CURB OR <br />WITH HEIGHT SUFFICIENT FOR 18" CLEARANCE FROM ROOF FLASHING TO FAN BASE. <br />14. ALL MECHANICAL WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE LOCALLY ADOPTED MECHANICAL CODE WITH <br />ALL CURRENTLY APPLICABLE ERRATA AND AMENDMENTS. <br />15. CONTRACTOR SHALL COORDINATE MECHANICAL WORK WITH ALL OTHER TRADES PRIOR TO FABRICATION AND <br />INSTALLATION. DO NOT SCALE FROM DRAWINGS FOR ANY EXACT DIMENSION. SEE ARCHITECTURAL DRAWINGS AND <br />REFLECTED CEILING PLANS FOR EXACT LOCATIONS OF DOORS, WINDOWS, AIR DISTRIBUTION DEVICES. <br />16. COORDINATE THE SIZE OF ALL WALL OPENINGS, ROOF OPENINGS AND EQUIPMENT PADS WITH ACTUAL EQUIPMENT <br />PURCHASED. ALL MECHANICAL ITEMS EXTENDING THRU WALL & ROOF SHALL BE FLASHED AND COUNTER FLASHED. <br />ALL ROOF CURBS FOR MECHANICAL EQUIPMENT SHALL BE BY MECHANICAL CONTRACTOR. <br />17. ROUTE FULL SIZE CONDENSATE DRAINS WITH P-TRAP AND VENT ON OUTLET SIDE. PIPE 12" AWAY FROM UNIT. SPILL ON <br />CONCRETE SPLASH BLOCK WHERE ROUTED TO ROOF. <br />18. DUCT SMOKE DETECTORS IN SUPPLIES AND RETURNS PER LOCALLY ADOPTED CODE SHALL BE FURNISHED & WIRED <br />BY DIV 16, INSTALLED BY DIV. 15. <br />19. ALL DUCTWORK SIZES ARE INSIDE CLEAR FREE AREA. INCREASE SIZE WHERE REQUIRED TO INCLUDE INTERNAL <br />INSUALTION <br />20. MOTOR STARTERS AND DISCONNECTS SHALL BE FURNISHED UNDER DIVISION 15 AND INSTALLED BY THE ELECTRICAL <br />CONTRACTOR. COORDINATE ELECTRICAL CHARACTERISTICS OF HVAC EQUIPMENT AND CONTROL SYSTEM <br />SPIN -IN FITTING WITH <br />VOLUME DAMPER <br />METAL DUCT <br />FOR SIZE SEE <br />PLANS- % <br />AIR SCOOF <br />SUPPLY <br />NLY) j <br />�1 <br />LOCKING QUADRANT <br />DEVICE NECK SIZE TO MATCH RUN OUT <br />STEEL WIRE TO STRUCTURE <br />SUPPORT STRAP <br />INSULATED <br />FLEX DUCT <br />HANGER (TYP.) <br />INSULATED SUPPLY ADAPTER/PLENUM <br />T-BAR FRAME TYP.)- PROVIDE METAL <br />FRAME AT GYP INSTALLTIONS <br />CEILING <br />DIFFUSER / RETURN DETAIL <br />REQUIREMENTS (VOLTAGE/PHASE, SIGNAL TYPE, AUXILIARY CONTACTS ETCO ) PRIOR TO PURCHASING. <br />21. CONTRACTOR SHALL NOTE THAT THE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO NOT INDICATE ALL OFFSETS, <br />TRANSITIONS, OR OTHER APPURTENANCES REQUIRED FOR A COMPLETE HVAC SYSTEM. PROVIDE ALL EQUIPMENT <br />NECESSARY FOR A COMPLETE SYSTEM. <br />22. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CONTROL ITEMS NECESSARY FOR THE HEATING AND COOLING <br />FUNCTIONS OF THE AHU AND MAU. THE AHU THERMOSTAT LAYOUT IS THE HONEYWELLT6590 FAN COIL CONTROLLED. <br />THE MAU SHALL BE PROVIDED WITH ADJUSTABLE DISCHARGE AIR CONTROL WITH DISCHARGE AIR SENSOR AND <br />MODULATING CONTROL VALVE. <br />23. ALL PIPING AND DUCTWORK SHALL RUN CONTINUOUSLY THROUGH FLOORS, ROOFS AND PARTITIONS. ENGINEER WILL <br />REVIEW DUCT/PIPING SHOP DRAWINGS AT THE REQUEST OF THE CONTRACTOR. NO EXHAUST HOOD SHALL BE LEFT <br />OPEN INTO BUILDING SPACE. <br />24. THIS CONTRACTOR SHALL PROVIDE & INSTALL ALL MISCELLANEOUS STEEL AS REQUIRED FOR INSTALLATION OF ALL <br />MECHANICAL ITEMS. <br />25. ALL DIFFUSERS LOCATED IN CEILINGS WITH A NON -RETURN AIR PLENUM SHALL BE INSULATED AIR TIGHT WITH FOIL <br />FACES 1 INCH FIBERGLASS INSULATION. <br />26. CONTRACTOR SHALL PURCHASE AIR FILTERS FROM THE OWNER -APPROVED AIR FILTER VENDOR WHERE OWNER HAS <br />A SUPPLIER. ALL FILTERS SHALL BE REPLACED IMMEDIATELY PRIOR TO SUBSTANTIAL COMPLETION. <br />27. CONTRACTOR SHALL SUBMIT THE TAB AGENCY, 2 WEEKS PRIOR TO SCHEDULE TESTING AND BALANCING OF THE <br />SYSTEM, AN UP-TO-DATE SET OF HVAC DRAWINGS, AND RELATED PRODUCT DATASUBMITTALS SUCH AS HVAC UNITS, <br />FANS, DIFFUSERS, and CONTROL DIAGRAMS. <br />28. THESE DRAWINGS ARE SCHEMATIC IN NATURE AND ARE NOT INTENDED TO SHOW ALL POSSIBLE CONDITIONS. IT IS <br />INTENDED THAT A COMPLETE MECHANICAL SYSTEM IS PROVIDED WITH ALL NECESSARY EQUIPMENT AND CONTROLS. <br />29. REFER TO ARCHITECTURAL PLANS FOR ADDITIONAL SYSTEM REQUIREMENTS. <br />30. TESTING AND BALANCE: CONTRACTOR SHALL CONTRACT AN INDEPENDENT TESTING AND BALANCING COMPANY TO <br />TEST THE EQUIPMENT AND ADJUST THE HVAC SYSTEM TO OBTAIN THE DESIGN AIR FLOWS AS SHOWN ON PLANS. THE <br />TAB AGENCY SHALL BE NEBB CERTIFIED AND SHALL SUBMIT TAB REPORT AS REQUIRED BY THE NEBB. <br />31. ALL SUPPLY RETURN- AND OUTSIDE AIR DUCTWORK SHALL BE INSULATED. DUCT LINER SHALL BE 1 1/2" ELASTOMERIC <br />RUBBER (ARMAFLEX OR EQ.); EXTERNAL INSULATION SHALL BE 2" THICK, 1 LB.CU.FT. DENSITY, FIBERGLASS TYPE, <br />FOIL -FACED DUCT WRAP, COMMERCIAL GRADE. ALL EXPOSED DUCTWORK SHALL BE LINED. R-VALUE SHALL BE <br />ADJUSTED PER LOCAL ENERGY CODE REQUIREMENTS. EXPOSED DUCT SHALL BE PROVIDED WITH APINT GRIP FINISH. <br />32. PROVIDE PVC WATER HEATER "CONCENTRIC TYPE THRU THE ROOF ARRANGEMENT" VENTING ASSEMBLY FOR FRESH <br />AIR INTAKE AND EXHAUST AS RECOMMENDED BY MANUFACTURER. <br />33. DUCTWORK SHALL BE GALVANIZED STEEL FABRICATED PER SMACNA STANDARDS. VOLUME DAMPERS SHALL BE <br />INSTALLED AT ALL DUCT BRANCHES AND DIFFUSER TAKE OFFS TO BE ABLE TO BALANCE THE AIR SYSTEM. DUCT SHALL <br />BE HUNG WITH 1" WIDE DUCT STRAPS. <br />34. EACH AC UNIT SHALL BE CONTROLLED WITH A WALL MOUNTED 7-DAY PROGRAMMABLE THERMOSTAT WITH AUTO <br />CHANGE OVER TO PROVIDE OCCUPIED/UNOCCUPIED MODES OF OPERATION. PROVIDE CLEAR PLASTIC COVER WITH <br />LOCKING KEY ALL THERMOSTATS. <br />35. ALL UNIT HEATER TO HAVE, INTERNAL DISCONNECT, MAGNETIC OVERLOAD PROTECTION; INTEGRAL TSTAT AND 24 V <br />CONTROLTRANSFORMER. <br />36. ALL PIPING SHALL BE INSULATED COMPLETELY AIR TIGHT WITH NO EXPOSED INSULATION MATERIAL. PROVIDE <br />INSULATION OUTSIDE OF PIPING HANGERS OR SUPPORTS WITH RIGID INSULATION AND PIPING SADDLES AT SUPPORTS <br />SUFFIECIENT TO PREVENT DEFORMATION OF INSULATION. <br />37. PROVIDE SIESMIC FITTINGS AND SUPPORTS AS REQUIRED BY THE LOCAL BUILDING CODE AND SIESMIC <br />CHARACTERISTICS FOR THE CONSTRUCTION LOCATION. <br />38. ALL COOLING UNITS SHALL BE PROVIDED WITH DRAIN PANS AND FLOAT SIWTCHES TO PREVENT UNIT OPERATION <br />WHERE CONDENSATE DRAINAGE CAN BE UNEXPECTEDLY INHIBITED, NO EQUIPMENT SHALL SIT DIRECTLY IN A DRAIN <br />PAN. <br />SUPPLY SUPPLY <br />--4► <br />RETURN/EXHAUST RETURN/EXHAUST <br />45° <br />VD <br />SUPPLY- RETURN/EXHAUST <br />DUCT BRANCH DETAIL <br />AIR DEVICE SCHEDULE <br />DESIGN <br />MARK <br />LAYOUT BASIS <br />TYPE <br />FACE SIZE <br />MOUNTING <br />FINISH <br />MATERIAL <br />NOTES <br />S-1 <br />TITUS TMS <br />CEILING DIFFUSER <br />24X24/12X12 <br />2x2 T-BAR <br />WHITE <br />STEEL <br />1,4 <br />S-2 <br />TITUS PAR <br />PATTERNLESS PERF GRILLE <br />24X24/ <br />2x2 T-BAR <br />WHITE <br />STEEL <br />1,4 <br />R-1 <br />TITUS 50 F <br />1/2" EGGCRATE RETURN <br />24X24 <br />2X2 T-BAR <br />WHITE <br />ALUMINUM <br />2 <br />NOTES <br />1 <br />. NECK SIZE TO MATCH DUCT RUN OUT SIZE AS SHOWN ON MECHANICAL PLANS. <br />2 <br />.PROVIDE MANUFACTURER'S ACCESSORY INSULATED PLENUM WITH RUN OUT SIZED CONNECTION. <br />3 <br />.BALANCING DEVICE AT AIR DEVICE FACE <br />4 <br />.BALANCING DEVICE AT RUN OUT TAKEOFF <br />5 <br />.DIVERT BLADES TO 45 DEGREE LATERALLY AND 35 DEGREES BELOW HORIZONTAL <br />6 <br />.3-WAY DIFFUSER <br />I <br />F <br />I <br />I END <br />ABREVIATIONS <br />AC <br />ABOVE CEILING <br />HR <br />HOUR <br />ACC <br />ACCESS <br />HW <br />HOT WATER <br />ACU <br />AIR CONDITIONING UNIT <br />HZ <br />HERTZ <br />AFF <br />ABOVE FIN ISHED FLOOR <br />IE <br />INVERT ELEVATION <br />AHU <br />AIR HANDLING UNIT <br />LAT <br />LEAVING AIR TEMPERATURE <br />AP <br />ACCESS PANEL <br />LBS <br />POUNDS <br />ARCH <br />ARCHITECT <br />LOB <br />LEAVING DRY BULB <br />BDD <br />BACKDRAFT DAMPER <br />LWB <br />LEAVING WET BULB <br />BTUH <br />BTU PER HOUR <br />LWT <br />LEAVING WATER TEMP. <br />CC <br />COOLING COIL <br />MAX <br />MAXIMUM <br />CCP <br />CENTRAL CONTROL PANEL <br />MBH <br />THOUSAND BTU PER HOUR <br />CD <br />CEILIIYIG DIFFUSER <br />EVAP <br />EVAPORATOR <br />CFM <br />CUBIC FEET PER MINUTE <br />MIN <br />MINIMUM <br />CG <br />CEILING GRID <br />MOD <br />MOTORIZED DAMPER <br />CONC. <br />CONCRETE <br />MTD <br />MOUNTED <br />CR <br />CEILING REGISTER <br />N.C. <br />MORMALLY CLOSED <br />CV <br />CONTROL VALVE <br />NIC <br />NOT IN CONTRACT <br />D <br />DROP <br />N.O, <br />NORMALLY OPENED <br />DB <br />DRY BULB <br />NO. <br />NUMBER <br />DIA. <br />DIAMETER <br />NPSH <br />NET POSITIVE SUCTION HEAD <br />DN <br />DOWN <br />NTS <br />NOT TO SCALE <br />DWG <br />DRAWING <br />OA <br />OUTSIDE AIR <br />EA <br />EXHAUST AIR <br />OD <br />OUTSIDE DIAMETER <br />EAT <br />ENTERING AIR TEMP <br />OS&Y <br />OUTSIDE SCREW AND YOKE <br />EDB <br />ENTERING DRY BULB <br />PD <br />PRESSURE DROP <br />EF <br />EXHAUST FAN <br />PSI <br />POUNDS PER SQUARE INCH <br />ELEV <br />ELEVATION <br />RA <br />RETURN AIR <br />ELEC <br />ELECTRIC <br />RM <br />ROOM <br />EWB <br />ENTERING WET BULB <br />RPM <br />REVOLUTION PER MINUTE <br />EWT <br />ENTERING WATER TEMP <br />SD <br />SMOKE DAMPER <br />ESP <br />EXTERNAL STATIC PRESSUR <br />SF <br />SUPPLY FAN <br />SP <br />STATIC PRESSURE <br />SF <br />SUPPLY FAN <br />EXH <br />EXHAUST <br />SP <br />STATIC PRESSURE <br />EXT <br />EXTERNAL <br />SPEC <br />SPECIFICATIONS <br />F <br />DEGREES FAHRENHET <br />SR <br />SUPPLY REGISTER <br />FC <br />FLEXIBLE CONNECTION <br />SS <br />STAINLESS STEEL <br />FCU <br />FAN COIL UNIT <br />TDH <br />TOTAL DYNAMIC HEAD <br />FD <br />FIRE DAMPER <br />TEMP <br />TEMPERATURE <br />AFG <br />ABOVE FINISHED GRADE <br />TG <br />TRANSFER GRILLE <br />FLD <br />FLOOR DRAIN <br />TV <br />TURNING VANES <br />FPI <br />FINS PER INCH <br />TYP. <br />TYPICAL <br />FPM <br />FEET PER MINUTE <br />UH <br />UNIT HEATER <br />FT <br />FEET <br />UC <br />3/4" UNDERCUT <br />GV <br />GATE VALVE <br />V <br />VOLTS <br />G <br />GAUGE <br />VAV <br />VARIABLE AIR VQLUME <br />GAL <br />GALLON <br />VEL <br />VELOCITY <br />GPH <br />GALLONS PER HOUR <br />VERT. <br />VERTICAL <br />GPM <br />GALLONS PER MINUTE <br />W <br />WIDTH <br />HP <br />HORSE POWER <br />W/ <br />WITHOUT <br />HT <br />HEIGHT <br />W/O <br />WITHOUT <br />H2O <br />WATER <br />IWB <br />WET BULB <br />HORIZ, HORIZONTAL IW.C. <br />WATER COLUMN <br />----------- <br />LEGEND <br />DUCT (SINGLE LINE) <br />THERMOSTAT <br />EXISTING DUCT/PIPE <br />ss <br />REMOTE SENSOR <br />LINED DUCT (SINGLE LINE) <br />O <br />HUMIDISTAT <br />HOOD ANSUL SYSTEM PULL STATION <br />LINED DUCT <br />jj....,, <br />OVERFLOW NOZZLE <br />EXPOSED SPIRAL W/ PAINT GRIP <br />PIPE DROP <br />ROOF DRAIN <br />SUPPLYNENTILATION DROP _ <br />__ _ - <br />BALL VALVE <br />RETURN DROP <br />STRAINER <br />EXHAUST DROP <br />PRV <br />SUPPLY DIFFUSER <br />CHECK VALVE <br />M <br />METER <br />RETURN GRILLE <br />NAT GAS REGULATOR <br />EXHAUST GRILLE <br />CAP <br />3 WAY VALVE <br />VOLUME DAMPER <br />2 WAY VALVE <br />FIRE DAMPER <br />BUTTERFLY VALVE <br />MOTORIZED DAMPER <br />CIRCUIT SETTER <br />SMOKE DETECTOR <br />FLOW CONTROL VALVE <br />DUCT ELBOW WITH VANES <br />-SINGLE LINE (EXCLUDE VANES IN <br />GAGE <br />GREASE EXHAUST) <br />THERMOMETER <br />DUCT ELBOW WITH VANES <br />PT PLUG <br />(EXCLUDE VANES IN GREASE EXHAUST) <br />PUMP <br />RADIUS ELBOW <br />DOUBLE CHECK VALVE <br />RPZ CHECK <br />FLEX DUCT RUN OUT <br />FLEXIBLE CONNECTION <br />FLEX PIPE/CONNECTION <br />AUTO AIR VENT <br />INLINE CABINET FAN <br />FROSTAT <br />CEILING CABINET FAN <br />UNION <br />HORIZ. UNIT HEATER <br />CEILING UNIT HEATER <br />INTAKE/VENT HOOD <br />EXHAUST/FLUE VENT HOOD <br />ROOF FAN <br />GAS PIPING <br />CW PIPING <br />HW PIPING <br />HOT WATER RECIRCULATION PIPING <br />VENT PIPING <br />SANITARY PIPING (LONG DASH) <br />GREASE WASTE (SHORT DASH) <br />EXISTING PACKAGED GAS/ELECTRIC ROOFTOP UNIT SCHEDULE <br />MIN <br />FAN <br />COOLING <br />COOLING <br />HEATING <br />HEATING <br />NOM <br />UNIT <br />QTY <br />FAN <br />OA <br />FAN <br />MOTOR <br />TOTAL <br />SENSIBLE <br />MBH <br />MBH <br />HEATING <br />VOLTS/ <br />MARK <br />SERVES <br />MODEL <br />TONS <br />CONFIGURATION <br />COMPR. <br />CFM <br />CFM <br />ESP <br />HP <br />MBH <br />MBH <br />OUTPUT <br />INPUT <br />STAGES <br />PHASE <br />RTU-1 <br />BOH <br />TRANE YHC120 <br />10 <br />DOWNFLOW <br />1 <br />4000 <br />0.5 <br />113.97 <br />94.06 <br />120 <br />150 <br />1 <br />208/3 <br />RTU-2 <br />BOH <br />TRANE YHC120 <br />10 <br />DOWNFLOW <br />1 <br />4000 <br />0,5 <br />113.97 <br />94.06 <br />120 <br />150 <br />1 <br />208/3 <br />RTU-3 <br />DINING <br />TRANE YHC120 <br />10 <br />DOWNFLOW <br />1 <br />4000 <br />0.5 <br />113.97 <br />94.06 <br />120 <br />150 <br />1 <br />208/3 <br />RTU-4 <br />DINING <br />TRANE YHC060 <br />5 <br />DOWNFLOW <br />1 <br />2000 <br />250 <br />0.5 <br />--- <br />63.49 <br />47.33 <br />48 <br />60 <br />1 <br />208/3 <br />NOTE 1: INDOOR COIL EAT = 80/67 FOR COOLING, 70 FOR HEATING. <br />NOTE 2: OUTDOOR COIL EAT = 95 FOR COOLING, 17 FOR HEATING. <br />NOTE 3: ESP DOES NOT INCLUDE FILTERS. FAN PERFORMANCE FOR DIRECT DRIVE UNITS IS AT HIGH SPEED. <br />NOTE 4: PROVIDE HINGED ACCESS DOORS, UNIT MOUNTED DISCONNECT AND UNPOWERED RECEPTACLE, CONDENSER COIL GUARDS, STAINLESS STEEL HEAT EXCHANGER. <br />NOTE 5: FACTORY MOUNTED SMOKE DETECTOR IN SUPPLY AND RETURN COMPARTMENTS AND INTERNAL FLOAT SWITCH WIRED FOR UNIT SHUTDOWN. <br />NOTE 6: PROVIDE 2-POSITION MOTORIZED DAMPER AT OUTDOOR AIR HOOD. <br />NOTE 7: ECONOMIZER WITH COMP ENTHALPY CONTROL MODULE. POWER EXHAUST FOR UNITS ABOVE 2000 CFM, BAROMETRIC RELIEF FOR 2000 CFM AND LOWER. <br />NOTE 8: PROVIDE MANUFACTURER ACCESSORY ROOF CURB. CURB ADAPTORS SHALL REQUIRE SPECIFIC ENGINEER APPROVAL. <br />NOTE 9: PROVIDE SPRING ISOLATION TYPE ROOF CURB. <br />NOTE 10: COORDINATE VOLTAGES WITH ELECTRICAL DRAWINGS PRIOR TO ORDERING. SUBMITTALS SHALL BE REQUIRED TO HAVE ELECTRICAL ENG. APPROVAL <br />NOTE 13: PROVIDE REFRIGERANT HOT GAS REHEAT DEHUMIDIFICATION. <br />NOTE 15: PROVIDE 7-DAY PROGRAMMABLE THERMOSTAT WITH REMOTE SENSOR. <br />END <br />EXHAUST/VENTILATION FAN SCHEDULE <br />MOTOR <br />VOLTS/ <br />FAN <br />TAG <br />MODEL <br />TYPE <br />SERVES <br />CFM <br />ESP <br />HP <br />RPM <br />SONES <br />DRIVE <br />PHASE <br />INTERLOCK <br />NOTES <br />F-1 <br />HOOD <br />HOOD <br />1,350 <br />0.925 <br />0.75 <br />1,164 <br />11.8 <br />DIRECT <br />120/1 <br />TIMECLOCK SET FOR OCCUPIED SCHEDULE <br />F-2 <br />HOOD <br />HOOD <br />2000 <br />0.931 <br />0.75 <br />1377 <br />16.1 <br />DIRECT <br />120/1 <br />TIMECLOCK SET FOR OCCUPIED SCHEDULE <br />F-3 <br />HOOD <br />HOOD <br />2000 <br />0.93 <br />0.75 <br />1377 <br />16.1 <br />DIRECT <br />120/1 <br />TIMECLOCK SET FOR OCCUPIED SCHEDULE <br />F-4 <br />HOOD <br />HOOD <br />3000 <br />1.122 <br />1.5 <br />1120 <br />13.6 <br />DIRECT <br />120/1 <br />TIMECLOCK SET FOR OCCUPIED SCHEDULE <br />F-5 <br />ACED <br />DOWNBLAST <br />RESTROOMS <br />300 <br />0.250 <br />1/3 <br />1,325 <br />8.9 <br />DIRECT <br />1 120/1 <br />TIMECLOCK SET FOR OCCUPIED SCHEDULE <br />1,2,3,4 <br />1. COORDINATE VOLTAGES WITH ELECTRICAL DRAWINGS. <br />2. PROVIDE INDOOR FANS WITH BACKDRAFT DAMPER, SPRING/NEOPRENE ISOLATION HANGERS AND ACCESSORY ROOF CAP AT SIZE INDICATED ON DRAWINGS. <br />END <br />Z <br />I"I <br />O <br />W <br />co <br />N <br />a <br />�00 <br />Lo <br />U <br />W <br />� <br />z <br />w Q <br />I- <br />LIJ <br />UzU�= <br />N� <br />N <br />U <br />N <br />Q <br />V� <br />LU <br />z <br />m <br />. <br />M� <br />• E <br />0. 7 • . o <br />Q <br />4 STAT OF • ��Lu <br />i�0 •. Al .• �� z <br />�O �pP w <br />SS�OIVA •E � �, <br />#oil Its <br />m <br />q <br />c5 <br />z <br />q <br />Q <br />w <br />Y <br />U) <br />Z <br />Q <br />00 <br />w <br />w <br />J <br />18014 <br />0 <br />CONTRACT DATE: 08-13.2017 <br />BUILDING TYPE: ONE-OFF <br />PLAN VERSION: <br />SITE NUMBER: <br />STORE NUMBER: <br />SUNRISE EATERY <br />5915 GALL BLVD. <br />ZEPHYRHILLS, FL <br />MECHANICAL <br />SCHEDULES <br />AND DETAILS <br />Mo. 1 <br />PLOT DATE: <br />