I. GENERAL PROVISIONS <br />A. OVERVIEW <br />1. ALL WORK DONE UNDER THIS CONTRACT SHALL COMPLY WITH ALL STATE AND LOCAL CODES HAVING JURISDICTION AND WITH <br />THE REQUIREMENTS OF THE UTILITY COMPANIES WHOSE SERVICES MAY BE USED. ALL MODIFICATIONS REQUIRED BY THESE <br />CODES SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL CHARGES. WHERE CODE REQUIREMENTS ARE LESS THAN <br />THOSE SHOWN ON THE PLANS OR IN THE SPECIFICATIONS, THE PLANS AND SPECIFICATIONS SHALL BE FOLLOWED. WHERE <br />APPLICABLE, NFPA REQUIREMENTS SHALL BE MET. <br />2. IN CASE OF ANY CONFLICTS BETWEEN CONTRACT DOCUMENTS, THE STRICTER/MORE STRINGENT SHALL GOVERN. <br />3. THE CONTRACTOR SHALL TAIN ALL PER IT IN P I A P <br />OB M S SECT ONS AND P ROVALS AS RE UIRED BY ALL AUTHORITIES HAVING <br />Q <br />JURISDICTION AND DELIVER ERTIFI ATE F APPR VAL T <br />C C S 0 0 TO HE ENGINEER. ALL FEES AND COSTS OF ANY NATURE WHATSOEVER <br />INCIDENTAL TO THESE PERMITS, INSPECTIONS AND APPROVALS MUST BE ASSUMED AND PAID BY THE CONTRACTOR. <br />4. THE CONTRACTOR SHALL COMPLY WITH ALL APPLICABLE PROVISI NS F . .H.A. <br />0 0 OS <br />5. THE WORKMANSHIP AND MATERIALS COVERED BY THESE SPECIFICATIONS SHALL CONFORM TO ALL ORDINANCES AND <br />REGULATIONS OF THE ITY NTY AND R T E <br />C , COU /0 O H R AUTHORITIES HAVING JURISDICTION. <br />6. CONTRACTOR SHALL VISIT THE SITE AND EXAMINE EXISTING CONDITIONS BEFORE SUBMITTING BID. NO ALLOWANCE WILL BE <br />MADE FOR LACK OF KN WLEDGE F EXISTIN CONDITI N WHEN H NDITI <br />0 0 G 0 S SUC CO ONS CAN BE DETERMINED BY OBSERVATION. <br />7. PRIOR TO SUBMITTIN D T F R R P R IN T <br />G A A O O U CHAS G EQUIPMEN REQUIRING ELECTRICAL SERVICE, THE CONTRACTOR SHALL VERIFY <br />THAT ELECTRICAL CHARACTERISTICS OF EQUIPMENT SUBMITTALS COMPLY WITH ELECTRICAL SERVICE PROVIDED FOR THE <br />SPECIFIED ITEMS OF EQUIPMENT. <br />8. UPON RECEIPT OF THE CONTRACTOR OF REVIEWED SUBMITTALS FORE UIPMENT PROVIDED UNDER THI DI I 1 N THE <br />Q S VSO , <br />CONTRACTOR SHALL COORDINATE THE ELECTRICAL SERVICE RE UIREMENTS I.E. MOTOR HORSEPOWER AND F LL L AD AM <br />Q U 0 PS, <br />ELECTRICAL SERVICE CHARACTERISTICS VOLTAGE AND PHASE AND NUMBER OF SERVICES FOR EACH ITEM F E IPMENT <br />( ), 0 QU <br />REQUIRING ELECTRICAL CONNECTIONS WITH THE ELECTRICAL DRAWINGS AND SPECIFICATIONS. <br />9. ITEMS ON OR PR JE IN TH H THE EILIN HA B I A <br />O CT G ROUG C G S LL E COORD N TED WITH OTHER TRADES. <br />10.EQUIPMENT MODEL NUMBERS ARE PROVIDED FOR GENERAL GUIDANCE, CONTRACTOR SHALL PROVIDE EQUIPMENT THAT MEETS <br />THE PHYSICAL CAPACITIES AS SCHEDULED AND GENERAL ARRANGEMENT AS INDICATED IN THE DRAWING SET. CONTRACTOR <br />SHALL VERIFY EXACT, CURRENT MODEL NUMBERS WITH THE MANUFACTURERS. <br />B. OPERATION AND MAINTENANCE INSTRUCTIONS <br />1. THE CONTRACTOR SHALL PROVIDE TWO OPERATION AND MAINTENANCE MANUALS. THE MANUALS SHALL BE COMPILED IN HARD <br />BACK, THREE RING NOTEBOOKS. 0&M MANUALS SHALL HAVE PERMANENT LABELS ON FRONT AND SIDE. THE FOLLOWING <br />INFORMATION SHALL APPEAR IN EACH MANUAL: <br />2. PROVIDE MANUFACTURER'S PRINTED OPERATING PROCEDURES TO INCLUDE START-UP, BREAK-IN, ROUTINE AND NORMAL <br />OPERATING INSTRUCTIONS; REGULATION, CONTROL, STOPPING, SHUTDOWN AND EMERGENCY INSTRUCTIONS; AND SUMMER <br />AND WINTER OPERATING INSTRUCTIONS. PROVIDE MAINTENANCE PROCEDURES FOR ROUTINE PREVENTATIVE MAINTENANCE <br />AND TROUBLESHOOTING; DISASSEMBLY, REPAIR AND REASSEMBLY; ALIGNING AND ADJUSTING INSTRUCTIONS. SERVICING <br />INSTRUCTIONS AND LUBRICATION CHARTS AND SCHEDULES. <br />C. INSTRUCTIONS OF OWNER PERSONNEL <br />1. BEFORE FINAL INSPECTION, AT A TIME DESIGNATED BY THE DESIGNER, PROVIDE A COMPETENT REPRESENTATIVE TO INSTRUCT <br />OWNER'S DESIGNATED PERSONNEL IN OPERATION, ADJUSTMENT AND MAINTENANCE OF PRODUCTS, EQUIPMENT AND SYSTEMS <br />UNDER THIS DIVISION OF THE SPECIFICATIONS. FOR EQUIPMENT REQUIRING SEASONAL OPERATIONS, PERFORM INSTRUCTIONS <br />FOR OTHER SEASONS WITHIN SIX MONTHS UNLESS REQUESTED OTHERWISE. <br />D. COORDINATION <br />1. THE PRODUCTS OF PARTICULAR MANUFACTURERS HAVE BEEN USED AS THE BASIS OF DESIGN IN PREPARATION OF THESE <br />DOCUMENTS. ANY MODIFICATIONS TO THE MECHANICAL SYSTEMS AND THEIR COMPONENTS, THE ELECTRICAL SYSTEMS, THE <br />BUILDING STRUCTURE AND ARCHITECTURE, OR ANY OTHER PORTION OF THE BUILDING THAT RESULT FROM THE USE OF ANY <br />OTHER THAN THAT BASIS OF DESIGN EQUIPMENT SHALL BE COORDINATED WITH ALL OTHER TRADES. SUCH COORDINATION <br />SHALL OCCUR BEFORE PURCHASE OR DELIVERY OF PRODUCTS FROM THE MANUFACTURER DRAWINGS OR INSTALLED <br />ACCORDINGLY. ANY RELATED MODIFICATIONS SHALL BE PERFORMED WITHOUT ANY ADDITIONAL COST TO THE CONTRACT. <br />2. RESIDENTIAL GRADE HVAC COMPONENTS SHALL NOT BE PERMITTED WITHOUT SPECIFIC OWNER INSTRUCTION AND ENGINEER <br />APPROVAL. <br />E. EXECUTION <br />1. THE PLANS DO NOT GIVE EXACT ELEVATIONS OR LOCATIONS OF LINES, NOR DO THEY SHOW ALL THE OFFSETS, CONTROL LINES, OR <br />OTHER INSTALLATION DETAILS. THE CONTRACTOR SHALL CAREFULLY LAY OUT HIS WORK AT THE SITE TO CONFORM TO THE <br />STRUCTURAL CONDITIONS, TO PROVIDE PROPER GRADING OF LINES, TO AVOID ALL OBSTRUCTIONS, TO CONFORM TO DETAILS OF <br />INSTALLATION SUPPLIED BY THE MANUFACTURERS OF THE EQUIPMENT TO BE INSTALLED, AND TO THEREBY PROVIDE AN <br />INTEGRATED, COORDINATED AND SATISFACTORY OPERATING INSTALLATION. DO NOT SCALE DRAWINGS. <br />2. IF THE CONTRACTOR PROPOSES TO INSTALL EQUIPMENT, INCLUDING PIPING AND DUCTWORK, REQUIRING SPACE CONDITIONS <br />OTHER THAN THOSE SHOWN, OR TO REARRANGE THE EQUIPMENT, HE SHALL ASSUME FULL RESPONSIBILITY FOR THE <br />REARRANGEMENT OF THE SPACE AND CONNECT ARRANGEMENT AT NO ADDITIONAL COST TO THE OWNER, AND SHALL HAVE THE <br />ENGINEER REVIEW THE CHANGE BEFORE PROCEEDING WITH THE WORK. THE REQUEST FOR SUCH CHANGES SHALL BE <br />ACCOMPLISHED BY SHOP DRAWINGS OF THE SPACE IN QUESTION. <br />3. TEMPORARY FILTERS SHALL BE PROVIDED FOR FANS THAT ARE USED DURING CONSTRUCTION. AT THE TIME OF STARTING THE <br />BALANCING OF THE AIR DISTRIBUTION SYSTEM, NEW FILTERS SHALL BE INSTALLED. <br />4. THE CONTRACTOR IS RESPONSIBLE FOR THE PROPER LOCATION AND SIZE OF ALL SLOT, HOLES OR OPENINGS IN THE BUILDING <br />STRUCTURE PERTAINING TO HIS WORK, AND FOR THE CORRECT LOCATION OF SLEEVES, INSERTS, CORES, ETC. <br />5. THE CONTRACTOR SHALL SO COORDINATE THE WORK OF THE SEVERAL VARIOUS TRADES THAT IT MAY BE INSTALLED IN THE MOST <br />DIRECT AND WORKMANLIKE MANNER WITHOUT HINDERING OR HANDICAPPING THE OTHER TRADES. PIPING INTERFERENCES <br />SHALL BE HANDLED BY GIVING PRECEDENCE TO PIPE LINES WHICH REQUIRE A STATED GRADE FOR PROPER OPERATION. FOR <br />EXAMPLE SEWER LINES AND CONDENSATE PIPING SHALL TAKE PRECEDENCE OVER WATER LINES IN DETERMINATION OF <br />ELEVATIONS. WHERE THERE IS INTERFERENCE BETWEEN SEWER LINES AND CONDENSATE LINES, THE SEWER LINES SHALL HAVE <br />PRECEDENCE AND PROVISIONS SHALL BE MADE IN THE CONDENSATE LINES FOR LOOPING THEM AROUND THE SEWER LINES. IN <br />ALL CASES, LINES REQUIRING A STATED GRADE FOR THEIR PROPER OPERATION SHALL HAVE PRECEDENCE OVER ELECTRICAL <br />CONDUIT AND DUCTWORK. <br />6. ALL PIPING AND DUCTWORK IN FINISHED AREAS- EXCEPT WHERE NOTED TO THE CONTRARY- SHALL BE INSTALLED IN A CHASE, <br />FURRED SPACE, OR ABOVE CEILINGS, ETC. IN ALL CASES, PIPES AND DUCTS SHALL BE INSTALLED AS HIGH AS POSSIBLE. RUNS OF <br />PIPING SHALL BE GROUPED WHENEVER IT IS FEASIBLE TO DO SO. <br />7. PIPING SHALL BE INSTALLED TO PASS INSPECTIONS BY LOCAL PLUMBING INSPECTION DEPARTMENT, STATE AND FEDERAL <br />AUTHORITIES AND INSURANCE COMPANY HAVING JURISDICTION. ANY CHANGES OR ADDITIONS WHICH MAY BE NECESSARY TO <br />OBTAIN SUCH INSPECTIONS AND APPROVAL SHALL BE MADE BY THE CONTRACTOR AS PART OF THIS CONTRACT AND WITHOUT <br />ADDITIONAL COST TO THE OWNER. <br />8. PIPING, DUCTWORK OR EQUIPMENT SHALL NOT BE INSTALLED IN ELECTRICAL EQUIPMENT ROOMS OR ELEVATOR MACHINE <br />ROOMS EXCEPT AS SERVING ONLY THOSE ROOMS. OUTSIDE OF ELECTRICAL EQUIPMENT ROOMS, DO NOT RUN PIPING OR <br />DUCTWORK OR LOCATE EQUIPMENT, WITH RESPECT TO SWITCHBOARDS, PANEL BOARDS, POWER PANELS, MOTOR CONTROL <br />CENTERS, DRY TYPE TRANSFORMERS OR ROOF TOP AIR CONDITIONING UNIT ELECTRICAL PANELS. <br />9. PROVIDE ACCESS TO EQUIPMENT AND APPARATUS REQUIRING OPERATION, SERVICE OR MAINTENANCE WITHIN THE LIFE OF THE <br />SYSTEM. INCLUDING, BUT NOT LIMITED TO, MOTORS, VALVES, FILTERS, DAMPERS, SHOCK ABSORBERS, ETC. EQUIPMENT <br />LOCATED ABOVE LAY -IN TYPE CEILINGS IS CONSIDERED ACCESSIBLE. <br />10.DAMAGED EQUIPMENT SHALL BE REPAIRED OR REPLACED AT THE OPTION OF THE ARCHITECT. <br />F. ELECTRICAL WORK <br />1. ALL ELECTRICAL EQUIPMENT PROVIDED UNDER THIS DIVISION SHALL COMPLY WITH THE ELECTRICAL SYSTEM CHARACTERISTICS <br />INDICATED ON THE ELECTRICAL DRAWINGS AND SPECIFIED IN DIVISION 16. <br />2. EQUIPMENT UNIT MOTOR SPEED CONTROLS, STARTERS, SYSTEM CONTROLS, PILOT LIGHTS, PUSH -BUTTONS, ETC., SHALL BE <br />FURNISHED COMPLETE AS A PART OF THE MOTOR APPARATUS WHICH IT OPERATES. ALL COMPONENTS SHALL BE IN <br />CONFORMANCE WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE AND DIVISION 16. ALL MOTOR STARTERS SHALL <br />BE PROVIDED WITH AN H-O-A SWITCH AND CONTROL TRANSFORMER. ALL STARTERS AND DISCONNECT SWITCHES SHALL BE <br />FURNISHED UNDER DIVISION 15. COORDINATE INSTALLATION WITH ELECTRICAL CONTRACTOR PRIOR TO HIS WIRING OF <br />EQUIPMENT. <br />3. CONTROL WIRING (120V AND LESS) SHALL BE PROVIDED UNDER DIVISION 15 AND EXTENDED FROM THE STARTERS, CONTROL <br />TRANSFORMERS OR 120V POWER CIRCUITS INDICATED ON THE ELECTRICAL DRAWINGS. ALL WIRING FOR 120 VOLTS SHALL BE <br />DONE BY A LICENSED ELECTRICIAN. <br />4. ALL ELECTRICAL CHARACTERISTICS SHALL BE TAKEN FROM THE ELECTRICAL DRAWINGS AND SPECIFICATIONS AND COORDINATED <br />BEFORE EQUIPMENT IS ORDERED OR PURCHASED. <br />G. CUTTING AND PATCHING <br />1. THE CONTRACTOR SHALL ASSUME ALL COST OF, AND BE RESPONSIBLE FOR, ARRANGING FOR ALL CUTTING AND PATCHING <br />REQUIRED TO COMPLETE THE INSTALLATION OF HIS PORTION OF THE WORK. ALL CUTTING SHALL BE CAREFULLY AND NEATLY <br />DONE SO AS NOT TO DAMAGE OR CUT AWAY MORE THAN IS NECESSARY OF ANY EXISTING PORTIONS OF THE STRUCTURE. <br />2. ALL SURFACES SHALL BE PATCHED TO THE CONDITION OF THE ADJACENT SURFACES. <br />3. THE CONTRACTOR SHALL MAKE SUITABLE PROVISIONS FOR ADEQUATELY WATERPROOFING AT HIS FLOOR PENETRATIONS OF <br />WATER PROOF MEMBRANE FLOORS. THIS SHALL INCLUDE BUT NOT BE LIMITED TO FLOOR DRAINS, OPEN SIGHT DRAINS, HUB <br />DRAINS, CLEANOUTS, AND SLEEVES FOR THE VARIOUS PIPING. THIS ALSO APPLIES TO MEMBRANE ROOFING SYSTEMS. <br />4. ALL PENETRATIONS AND WATER PROOFING OF PENETRATIONS IN MEMBRANE ROOFING SYSTEMS SHALL BE COORDINATED WITH <br />AND PERFORMED BY THE MANUFACTURER/INSTALLER. <br />5. THE CONTRACTOR SHALL INSTALL, AS REQUIRED, IN CONCRETE, CARPENTRY OR MASONRY CONSTRUCTION, ALL NECESSARY <br />HANGERS, SLEEVES, EXPANSION BOLTS, INSERTS AND OTHER FIXTURES AND APPURTENANCES NECESSARY FOR THE SUPPORT OF <br />PIPE, DUCT, EQUIPMENT AND DEVICES FURNISHED UNDER EACH SECTION OF THE SPECIFICATION. <br />6. FOR WALLS BETWEEN INTERIOR AND BELOW GRADE AREA, THE LINK -SEAL SYSTEM AS MANUFACTURED BY THUNDERLINE <br />CORPORATION SHALL BE USED TO SEAL PIPE TO WALL PENETRATIONS. INSTALL SYSTEM IN ACCORDANCE WITH MANUFACTURER'S <br />INSTRUCTIONS. <br />7. ESCUTCHEONS SHALL BE INSTALLED ON ALL PIPES WHERE THEY PASS THROUGH FLOORS, CEILINGS, WALLS OR PARTITIONS IN <br />FINISHED AREAS WHERE EXPOSED TO VIEW. <br />8. WHERE AND HVAC OR PLUMBING REPLACEMENT SCOPE IS INDICATED, MECHANICAL CONTRACTOR SHALL PROVIDE FOR THE <br />DEMOLITION OF EXISTING SYSTEMS THAT ARE BEING REPLACED OR ABANDONED <br />H. ACCESS DOORS <br />1. FURNISH AND INSTALL ACCESS DOORS AT EACH POINT REQUIRED TO PROVIDE ACCESS TO CONCEALED VALVES, CLEANOUTS AND <br />OTHER DEVICES REQUIRING OPERATION, ADJUSTMENT OR MAINTENANCE. ACCESS DOORS SHALL BE 16 GAUGE STEEL, PRIME <br />COAT FINISH, WITH MOUNTING STRAPS, CONCEALED HINGES AND SCREWDRIVER LOCKS, DESIGNED FOR THE DOORS TO OPEN 180 <br />DEGREES. <br />2. ACCESS DOORS INSTALLED IN FIRE WALLS OR PARTITIONS SHALL BE UL LABELED TO MAINTAIN THE FIRE RATING OF THE WALL OR <br />PARTITION. <br />I. FLAME SPREAD AND SMOKE DEVELOPED PROPERTIES OF MATERIALS <br />1. MATERIALS AND ADHESIVES USED THROUGHOUT THE MECHANICAL AND ELECTRICAL SYSTEMS FOR INSULATION, AND JACKETS OR <br />COVERINGS OF ANY KIND, OR FOR PIPING OR CONDUIT SYSTEM COMPONENTS, SHALL HAVE A FLAME SPREAD RATING NOT OVER <br />25 WITHOUT EVIDENCE OF CONTINUED COMBUSTION AND WITH A SMOKE DEVELOPED RATING NOT HIGHER THAN 50. IF SUCH <br />MATERIALS ARE TO BE APPLIED WITH ADHESIVES, THEY SHALL BE TESTED AS APPLIED WITH SUCH ADHESIVES, OR THE ADHESIVES <br />USED SHALL HAVE A FLAME SPREAD RATING NOT OVER 25 AND A SMOKE DEVELOPED RATING NOT HIGHER THAN 50. <br />11. INSULATION <br />A. GENERAL PIPE INSULATION <br />1. FIBERGLASS SHALL BE ACCEPTABLE FOR INDOOR HOT & COLD DOMESTIC; HYDRONIC PIPING; AND INSULATED DRAINAGE PIPING. <br />PROVIDE PREFABRICATED FITTINGS FOR ELBOWS AND TEE'S. PROVIDE PREFAB PVC FITTINGS OR WHITE ALL SERVICE (INTEGRAL TO PREFAB <br />PIPING ELBOW) PIPING ELBOW JACKETING. PROVIDE PIPE LABELING FOR ALL INSULATED, JACKETED INDOOR PIPING. PVC JACKETING SHALL <br />NOT BE PERMITTED IN RETURN PLENUM AREAS. ALL JACKEING SEAMS SHALL BE SEALED AIR -TIGHT FOR CONTINUOUS VAPOR BARRIER. <br />2. FITTINGS AND VALVES SHALL BE INSULATED WITH PRE -FORMED FITTINGS, FABRICATED SECTIONS OF PIPE INSULATION, TANK <br />INSULATION, BLANKET INSULATION, OR INSULATING CEMENT. THICKNESS SHALL BE EQUAL TO ADJACENT PIPE INSULATION. FINISH SHALL BE <br />WITH PRE -FORMED PVC FITTING COVERS OR AS OTHERWISE SPECIFIED ON CONTRACT DRAWINGS. <br />3. FLANGES, COUPLINGS AND VALVE BONNETS SHALL BE COVERED WITH AN OVERSIZED PIPE INSULATION SECTION SIZED TO PROVIDE THE <br />SAME INSULATION THICKNESS AS ON THE MAIN PIPE SECTION. AN OVERSIZED INSULATION SECTI N HALL BE D T F RM A COLLAR <br />0 S USE O 0 <br />BETWEEN THE TWO INSULATION SECTIONS WITH LOW -DENSITY BLANKET INSULATION BEING USED TO FILL GAPS. JACKETING SHALL MATCH <br />THAT USED ON STRAIGHT PIPE SECTIONS. ROUGH CUT ENDS SHALL BE COATED WITH ITABLE R M TI A <br />SU WEATHER OR VAPOR ESISTANT AS C S <br />DICTATED BY THE SYSTEM LOCATION AND SERVICE. ON HOT SYSTEMS WHERE FITTINGS ARE TO BE LEFT EXPOSED, INSULATION ENDS SHOULD <br />BE BEVELED AWAY FROM BOLTS FOR EASY ACCESS. <br />B. INSULATION THICKNESS <br />1. DOMESTIC COLD WATER INSULATION SHALL BE 1" MINIMUM OR AS RE UIRED BY LOCAL ENERGY CODES. <br />Q <br />2. FOR MEDIA BELOW 60 DEGREES INSULATION SHALL BE 1" UP TO 1-'/," PIPE SIZE; 1.5" THICK UP TO 3" PIPE SIZE; AND 2" THICK BEYOND <br />3" PIPE SIZE. <br />3. CHILLED WATER PIPING INSULATION SHALL BE 1" UP TO 1-1/4" PIPE SIZE, 1.5" UP TO 3". <br />C. FIBERGLASS PIPE INSULATION <br />1. ONE PIECE FIBROUS GLASS PIPE INSULATION WITH FACTORY APPLIED ALUMINUM FOIL AND WHITE KRAFT PAPER FLAME RETARDANT <br />VAPOR BARRIER JACKET. <br />2. PROVIDE SELF-SEALING LONGITUDINAL JACKET LAPS AND BUTT STRIP . AVERA E T ER A ARE <br />S G H M L CONDUCTIVITY• 0.23 BTU/IN PER SQU <br />FOOT PER DEGREES F PER HOUR AT 75 DEGREES F MEAN TEMPERATURE. <br />3. PROVIDE INSULATION CEMENT FIBERGLASS REINFORCEMENT FABRI VAP R BARRI <br />C 0 ER COATING FOR CONTINUOUS AIR TIGHT <br />INSULATION WITH VAPOR BARRIER. <br />D. FOAMGLASS PIPE INSULATION <br />1. FOAM GLASS TYPE PIPE INSULATION SHALL HAVE MAXIMUM K_FACTOR OF 0.38 AT 50 DEGREES F MEAN TEMPERATURE. MINIMUM <br />DENSITY SHALL BE 8 LB/CU. FT., 1 1/2" THICK MINIMUM. PROVIDE MASTIC, FIBERGLASS REINFORCED STRAPPING TAPE TO ASSURE AIR -TIGHT <br />MOISTURE -PROOF INSULATION. PROVIDE WITH ALUMINUM JACKETING THAT SHALL BE 0.016" THICK WITH FITTING COVERS 0.024" THICK. <br />PROVIDE WITH 5 WATT/FT HEAT TRACING BELOW INSULATION FOR OUTDOOR, ABOVE -GROUND INSTALLATION. <br />2. PROVIDE FOAM GLASS INSERTS AT PIPE HANGERS, CLAMPS, OR OTHER SUPPORTS IN FIBERGLASS OR ELASTOMERIC PIPE INSULATION <br />INSTALLATIONS INSERTS SHALL BE SAME THICKNESS AS ADJOINING PIPE INSULATION. VAPOR SEAL SHALL BE AS HEREINBEFORE SPECIFIED. <br />ALUMINUM JACKETING SHALL NOT BE REQUIRED FOR INDOOR INSERTS (PVC OR WHITE ALL -SERVICE FOIL/KRAFTJACKETING MEDIA SHALL BE <br />USED). <br />E. ELASTOMERIC (CLOSED CELL FOAM) PIPE INSULATION <br />1. ELASTOMERIC SHALL BE PROVIDED FOR ALL REFRIGERANT PIPING AND OUTDOOR INSULATED PIPING AND MAY BE USED FOR INDOOR <br />DOMESTIC OR CONDENSATE PIPING. PIPING WILL REQUIRE JACKETING- ALUMINUM FOR OUTDOOR PIPING OR FOIL/WHITE KRAFT MEDIA OR <br />PVC FOR INDOOR PIPING. PROVIDE WITH FULL ADHESIVE ADHERING SEAMS AND JOINTS FOR CONTINUOUS VAPOR BARRIER. ELBOWS SHALL <br />BE FORMED BY CUTTING SEGMENTS AT 30 DEGREE ANGLES (3 SEGMENTS AT EACH 90 DEGREE BEND) WITH MASTIC AT ALL SEAMS. PROVIDE <br />PREFORMED JACKETING ELBOWS AT ALL PIPING ELBOWS. <br />F. FIBERGLASS BLANKET INSULATION FOR DUCTWORK (INDOOR DUCT ONLY <br />1. INSULATION SHALL BE BLANKET TYPE FIBERGLASS INSULATION WITH AVERAGE THERMAL CONDUCTIVITY NOT EXCEEDING 0.29 BTU_IN. <br />PER SQUARE FEET PER DEGREES F PER HOUR AT MEAN TEMPERATURE OF 75 DEGREES F. WITH A MINIMUM DENSITY OF 1 LB/CU. FT., 2" <br />THICK MINIMUM AND FOIL INSULATION FACE. PROVIDE FIRE RETARDANT ADHESIVE OR FOIL REINFORCED KRAFTTAPE, 3" WIDE AT ALL <br />SEAMS. SECURE INSULATION TO DUCT WITH 18 GAUGE TIE -WIRE OR 1/2" X 0.015" GALVANIZED STEEL STRAPS. PROVIDE COMPLETE AIR -TIGHT <br />VAPOR BARRIER FOR ALL DUCTWORK. STAPLES SHALL NOT BE PERMITTED FOR ANY INSULATION ATTACHMENT. PROVIDE GRAY SEALER FOR <br />SEALING JOINTS, PENETRATION AND PUNCTURES. <br />2. CONTINUE INSULATION THROUGH WALL AND CEILING OPENINGS AND SLEEVES, EXCEPT TERMINATE DUCT INSULATION AT FIRE <br />DAMPERS AND AT FLEXIBLE DUCT CONNECTIONS AT AIR HANDLING UNITS. <br />3. PROTECT INSULATION FROM PHYSICAL DAMAGE AT POINTS OF SUPPORT WHERE INSULATION MUST CARRY LOAD IMPOSED BY SUPPORT. <br />COORDINATE THIS REQUIREMENT WITH TYPES OF HANGER AND SUPPORT USED. HANGERS THAT PENETRATE INSULATION SHALL BE SEALED <br />WITH MASTIC TO PRESERVE CONTINUOUS VAPOR BARRIER. <br />G. ELASTOMERIC (CLOSED CELL FOAM) DUCT LINER <br />1. INSTALL INSIDE OF DUCT WITH FULL ADHESIVE COVERAGE ATTACHMENTTO THE SURFACE TO WHICH IT IS APPLIED; 1" FOR INDOOR AND <br />1-1/2" FOR OUTDOOR. R VALUES SHALL BE R-4.2 FOR 1" AND R-6.2 FOR 1-1/2". FIBERGLASS DUCT LINER SHALL NOT BE PERMITTED UNDER <br />ANY CIRCUMSTANCES. PROVIDE WITH ANTIMICROBIAL PROTECTION. PROVIDE MASTIC AT ALL INTERIOR SEEMS FOR CONTINUOUS VAPOR <br />BARRIER. PROVIDE DUCT LINER AT FIRST FIVE FEET OF SUPPLY DUCT FOR REFRIGERATION/COOLING AIR HANDLING EQUIPMENT, UPSIZING <br />INDICATED DUCT SIZE TO ACCOUNT FOR INSULATION THICKNESS. FIBERGLASS DUCT LINER OR DUCT BOARD SHALL NOT BE PERMITTED. <br />VIBRATION ISOLATION <br />A. ALL MOTORIZED AIR MOVING AND FLUID MOVING EQUIPMENT PIECE SHALL BE PROVIDED WITH VIBRATION ISOLATION MOUNTING OR <br />SUPPORTS. <br />B. PAD -TYPE ISOLATORS SHALL BE NEOPRENE IN -SHEAR ISOLATION PADS WITH CROSSED DOUBLE RIBS. A STEEL SHIM PLATE SHALL BE <br />PROVIDED BETWEEN THE TWO LAYERS. PADS SHALL BE MOLDED USING OIL RESISTANT 25,000 PSI TENSILE STRENGTH NEOPRENE. <br />C. HANGING ISOLATORS FOR ITEMS 300 LBS OR LESS SHALL BE BRIDGE -BEARING NEOPRENE MOUNTINGS AND SHALL HAVE A MINIMUM <br />STATIC DEFLECTION OF 0.2" AND ALL DIRECTIONAL SEISMIC CAPABILITY. THE ELEMENTS SHALL PREVENT THE CENTRAL THREADED SLEEVE AND <br />ATTACHMENT BOLT FROM CONTACTING THE CASTING DURING NORMAL OPERATION. THE SHOCK ABSORBING NEOPRENE MATERIALS SHALL <br />BE COMPOUNDED TO BRIDGE -BEARING SPECIFICATIONS. MASON HD, KINETICS <br />D. HANGING ISOLATORS FOR EQUIPMENT ABOVE 300 LBS SHALL BE STEEL SPRING -TYPE INCORPORATING STEEL HOUSING, NEOPRENE OR <br />LDS RUBBER SPRING CUP SIZED FOR 1" DEFLECTION. INSTALL SPRING IN PLUMB CONFIGURATION WITH MAXIMUM 1" DEFLECTION FROM ANY <br />HORIZONTAL DISTORTION. THE ELEMENTS SHALL PREVENT THE CENTRAL THREADED SLEEVE AND ATTACHMENT BOLT FROM CONTACTING <br />THE CASTING DURING NORMAL OPERATION. CONTRACTOR SHALL SELECT SPRING COLOR/RATING BASED ON EQUIPMENT WEIGHT. AMBER <br />BOOTH SH, KINETICS SH, MASON 30 OR EQUIVALENT. <br />IV. DUCTWORK AND FITTINGS <br />A. MATERIAL AND TYPE <br />1. DUCT CONSTRUCTION SHALL CONFORM TO THE RECOMMENDATIONS OF THE SMACNA HVAC DUCT CONSTRUCTION MANUAL. <br />DUCTBOARD SHALL NOT BE PERMITTED. <br />2. RIGID, SQUARE DUCTWORK SHALL BE CONSTRUCTED OF LOCK FORMING QUALITY GALVANIZED STEEL SHEETS PER ASTM A527. <br />GALVANIZED COATING SHALL BE NOT LESS THAN 1.25 OUNCES (TOTAL FOR BOTH SIDES) PER SQUARE FOOT OF SHEET. DUCTWORK SHALL BE <br />CLASSIFIED AND CONSTRUCTED SMACNA PRESSURE CLASSES: +2 FOR SUPPLY AND -2 FOR RETURN AND EXHAUST. DUCTWORK GAUGE SHALL <br />BE 26 GAUGE UP TO 30" AND 22 GAUGE ABOVE 30" IN CROSS SECTIONAL HEIGHT, WIDTH, OR DIAMETER. <br />3. CONCEALED ROUND DUCTS UP TO 12" IN DIAMETER IN PRESSURE CLASSES 2" AND LOWER SHALL BE LONGITUDINAL SEAM <br />CONSTRUCTION. <br />4. EXPOSED ROUND DUCTWORK OR ROUND ABOVE 12" SHALL BE SPIRAL LOCK_SEAM CONSTRUCTION. ROUND FITTINGS SHALL BE FUSION <br />WELDED BUT SEAM TYPE WITH ALL WELDS CONTINUOUS ALONG SEAMS. ALL DIVIDED FLOW FITTINGS SHALL BE MANUFACTURED AS <br />SEPARATE FITTINGS _TAP COLLARS WELDED INTO SPIRAL DUCT SECTIONS WILL NOT BE PERMITTED. ALL DIVIDED FLOW FITTINGS 12" IN <br />DIAMETER AND SMALLER SHALL HAVE RADIUSED ENTRANCE PRODUCED BY MACHINE OR PRESS FORMING; ALL DIVIDED FLOW FITTINGS 14" <br />AND LARGER SHALL HAVE CONICAL ENTRANCE PRODUCED BY MACHINE OR PRESS FORMING. ALL DIVIDED FLOW ENTRANCES SHALL BE FREE <br />OF WELD BUILD-UP, BURRS AND IRREGULARITIES. FITTINGS SHALL BE OF THE SAME MANUFACTURER AS THE DUCTWORK. <br />5. DUCT SEALANT SHALL BE POLYMERIC RUBBER BASE MASTIC, MINERAL IMPREGNATED WOVEN FIBER TAPE WITH ADHESIVE, OR <br />HEAT_SHRINK WITH ADHESIVE. TAPE THICKNESS UP TO 10" = 2"; UP TO 20" = 3"; OVER 20" = 4" <br />6. INSULATED FLEXIBLE DUCT SHALL BE CLASS 1 AIR DUCT IN ACCORDANCE WITH UL 181 AND SHALL COMPLY WITH NFPA 90A AND 90B. <br />INSULATED FLEXIBLE DUCT SHALL CONSIST OF AN INNER FILM LAYER FOR MINIMUM WORKING PRESSURE OF 6" WATER GAUGE BONDED TO A <br />STEEL OR ALUMINUM SPRING WIRE HELIX, FIBERGLASS INSULATION, AND A VAPOR BARRIER JACKET. INSULATION SHALL HAVE A MAXIMUM <br />U_VALVE OF .23 BTU/HR/SQFT/DEG F AT 75 DEGREES F MEAN TEMPERATURE. VAPOR BARRIER JACKET SHALL HAVE A MAXIMUM VAPOR <br />TRANSMISSION RATE OF 0.1 GRAINS/SQ. FT./HR/INCH HG (PERM). THE ASSEMBLY SHALL HAVE A MAXIMUM FLAME AND SMOKE RATING OF <br />25/50 PER ASTM E84 AND NFPA 255. FLEXIBLE DUCTS SHALL BE INSTALLED IN AN EXTENDED CONDITION FREE OF SAGS AND KINKS, USING <br />ONLY THE MINIMUM LENGTH REQUIRED TO MAKE THE CONNECTION. ABRUPT BENDS AND TURNS THAT CRIMP THE DUCT AND RESTRICT AIR <br />FLOW SHALL NOT BE PERMITTED. HORIZONTAL SUPPORTS SHALL BE 3/4" WIDE, 22 GAUGE FLAT GALVANIZED STEEL SHEET BANDING <br />MATERIAL. FLEXIBLE DUCTS SHALL BE SUPPORTED ON 36" CENTERS. MAXIMUM LENGTH OF FLEXIBLE DUCT IN PRESSURE CLASS 2" AND <br />BELOW SHALL BE 12 FEET. FLEXIBLE DUCT SHALL NOT BE USED ABOVE INACCESSIBLE CEILINGS. <br />7. GREASE DUCT SERVING TYPE I HOODS SHALL BE 16 GAUGE BLACK IRON OR 18 GAUGE STAINLESS STEEL WELDED WITH AIR TIGHT SEAM. <br />PROVIDE DUCT CLEANOUTS AT ALL CHANGES OF DIRECTION. FOR INSTALLATIONS THAT WILL RESULT IN A DUCT OR SECTION OF DUCT WITHIN <br />18" OF COMBUSTIBLE MATERIAL, PROVIDE FIRE -RATED INSULATION AS REQUIRED FOR A ZERO INCH CLEARANCE TO COMBUSTIBLE INSTALLED <br />PER MANUFACTURER'S AND/OR RATING AGENCY REQUIREMENTS COMPLETE WITH ALL REQUIRED PENETRATION TREATMENTS, NUMBER IF <br />INSULATING LAYERS AND APPROVED PREFABRICATED, RATED ACCESS PANELS. DO NOT PROVIDE VENTED ROOF CURBS FOR FIRE WRAPPED <br />GREASE EXHAUST DUCTS. <br />8. DISHWASHER EXHAUST DUCT SHALL BE STAINLESS STEEL. <br />B. DAMPERS <br />1. DAMPERS SHALL BE SINGLE BLADE BUTTERFLY TYPE IN DUCTS UP TO AND INCLUDING 18" X 12" SIZE; FOR DUCTS LARGER THAN 18" X <br />12", IN EITHER OR BOTH DIMENSIONS, THE DAMPERS SHALL BE THE MULTI_BLADE TYPE. SINGLE BLADE BUTTERFLY DAMPER SHALL BE <br />CONSTRUCTED OF NOT LESS THAN 16_GAUGE GALVANIZED STEEL BLADE MOUNTED IN A GALVANIZED STEEL FRAME. FOR RECTANGULAR <br />DAMPERS, THE TOP AND BOTTOM EDGES OF THE BLADE SHALL BE CRIMPED TO STIFFEN THE BLADE. DAMPER SHALL BE PROVIDED WITH AN <br />EXTENDED ROD TO PERMIT INSTALLATION OF A DAMPER REGULATOR. <br />2. MULTI_BLADE DAMPERS SHALL BE THE OPPOSED BLADE TYPE, CONSTRUCTED OF NOT THAN 16_GAUGE GALVANIZED STEEL BLADES <br />MOUNTED IN GALVANIZED STEEL CHANNEL FRAME. BLADE SPACING SHALL NOT EXCEED 6 INCHES AND THE TOP AND BOTTOM EDGES OF THE <br />BLADES SHALL BE CRIMPED TO STIFFEN THE BLADES. DAMPER BLADES SHALL BE INTERCONNECTED BY RODS AND LINKAGES TO PROVIDE <br />SIMULTANEOUS OPERATION OF ALL BLADES. DAMPERS SHALL BE PROVIDED WITH EXTENDED RODS TO PERMIT INSTALLATION OF DAMPER <br />OPERATORS. <br />3. DUCT MOUNTED DIAL REGULATORS WITH OPERATING HANDLE SHALL BE PROVIDED OR DAMPERS WHICH ARE LOCATED ABOVE HARD <br />CEILINGS OR INACCESSIBLE LOCATIONS. CONCEALED CEILING MOUNTED DIAL REGULATORS SHALL BE PROVIDED ON VOLUME CONTROL <br />DAMPERS WHICH ARE LOCATED ABOVE HARD CEILINGS. CONCEALED REGULATORS SHALL BE PROVIDED WITHIN DIFFUSER FACE WITH SCREW <br />ADJUSTMENT. <br />4. PROVIDE DAMPERS AT ALL SUPPLY AND RETURN DUCT RUN OUTS TO EACH AIR DISTRIBUTION DEVICE WITH ACCESSIBLE ADJUSTMENT <br />LEVER OR DIAL -TYPE REGULATOR ACTUATOR. <br />C. DUCT FITTINGS <br />1. SPIN_IN COLLARS SHALL BE GALVANIZED STEEL FOR USE WITH RECTANGULAR OR SQUARE SHEET METAL DUCTWORK. SPIN -IN COLLARS <br />SHALL HAVE AIR SCOOP (FOR SUPPLY DUCTS) AND DAMPER (SUPPLY AND RETURN). <br />2. TURNING VANES SHALL BE INSTALLED IN ALL 90 DEGREES SQUARE AND RECTANGULAR ELBOWS AND AT OTHER LOCATIONS SHOWN ON <br />THE DRAWINGS WITH THE EXCEPTION OF KITCHEN EXHAUST. <br />3. CURVED ELBOWS SHALL HAVE A CENTERLINE RADIUS NOT LESS THAN 1 1/2 TIMES THE DUCT WIDTH. <br />4. DISSIMILAR METALS SHALL BE ISOLATED TO PREVENT GALVANIC CORROSION. JOINTS NOT PROVIDED WITH GASKETS SHALL BE ISOLATED <br />WITH 1/161NCH MINIMUM THICKNESS ASPHALT IMPREGNATED BUILDING PAPER. <br />5. PROVIDE DAMPERS AT RETURN DUCT AND OUTSIDE AIR DUCT CONNECTIONS DOWNSTREAM OF ANY DUCT CONNECTIONS OR TAKE <br />OFFS. <br />6. FLEXIBLE DUCT CONNECTIONS SHALL BE NON-COMBUSTIBLE GLASS FABRIC DOUBLE COATED WITH NEOPRENE 30 OZ. PER SQUARE YARD. <br />7. FIRE DAMPERS SHALL BE THE FOLDING BLADE FUSIBLE LINK TYPE CONFORMING TO UL 555 AND LABELED FOR INSTALLATION IN FIRE <br />RATED WALLS AND FLOORS. DAMPERS IN FLOOR SHALL HAVE SPRING OPERATOR. DAMPERS, EXCEPT FOR LOWER SECTIONS OF A MULTIPLE <br />SECTION ASSEMBLY, AND THOSE INSTALLED BEHIND GRILLES AND REGISTERS, SHALL HAVE BLADES OUT OF THE AIR STREAM WHEN DAMPER <br />IS IN THE OPEN POSITION. DAMPERS IN WALLS OR FLOORS RATED 2 HOURS OR LESS SHALL BE RATED FOR 1 1/2 HOURS; DAMPERS IN WALLS <br />RATED 3 OR 4 HOUR SHALL BE RATED FOR 3 HOURS. DAMPERS SHALL BE CONSTRUCTED OF GALVANIZED STEEL. PROVIDE AT EACH FIRE <br />RATED WALL PENETRATION (REFER TO ARCH. DRAWINGS) <br />8. SMOKE DAMPERS SHALL BE THE MULTI -BLADE TYPE CONFORMING TO UL 555S WITH AN ASSEMBLY TEMPERATURE RATIN F 2 <br />G 0 50 <br />DEGREES F. DAMPER SHALL BE CONSTRUCTED OF GALVANIZED STEEL AND SHALL BE PROVIDED WITH A FACTORY-M UNTED ELE RI <br />0 CT C <br />DAMPER OPERATOR, SUITABLE FOR OPERATION ON 120V, 60 HZ SUPPLY. PROVIDE AT EACH SMOKE BARRIER LOCATION (REFER TO ARCH <br />DRAWINGS . <br />9. DUCT -TO -DUCT JOINTS IN ROUND DUCT UP TO AND INCLUDING 60" IN DIAMETER SHALL BE MADE BY USING SLEEVE COUPLINGS, <br />REINFORCED BY ROLLED BEADS. DUCT -TO -FITTING JOINTS IN ROUND DUCT UP TO AND INCLUDING 60" IN DIAMETER HALL BE MADE Y <br />S B <br />SLIP_FIT OF THE PROJECTING COLLAR ON THE FITTING INTO THE DUCT. SLEEVE SHALL BE THE SAME GAUGE GALVANIZED STEEL AS TH D <br />E UCT; <br />INSERTION LENGTH OF SLEEVE COUPLING AND FITTING COLLAR SHALL BE NOT LESS THAN 2". AFTER THE JOINT IS SLIPPED TO ETHER E <br />G SH ET <br />METAL SCREWS SHALL BE INSTALLED FOR ECHANICAL STRENGTH• SCREWS SHALL BEE UALLY PA ED N M RE T A <br />M Q S C 0 0 H N 12" ON CENTERS <br />AND WITH A MINIMUM OF 3 SCREWS IN EACH JOINT. SCREWS SHALL BE PLACED AT 1/2" FROM THE JOINT BEAD. DUCT -TO -DUCT JOINTS IN <br />DUCTS UP TO AND INCLUDING 12" IN DIAMETER FOR PRESSURE CLASS 2" AND BELOW MAY BE THE BEADED -CRIMP TYPE AND EACH JOINT <br />SHALL BE FASTENED WITH SHEET METAL SCREWS, EQUALLY SPACED, NOT MORE THAN 12" ON CENTERS AND WITH A MINIMUM OF 3 SCREWS <br />IN EACH JOINT. THE BEADED -CRIMP JOINT SHALL PROVIDE AT LEASTA 1 LAP TO ACCOMM DATE THE HEET META <br />0 S L SCREWS <br />10. ALL DUCT JOINTS LONGITUDINAL TRANSVERSE AND DUCT PENETRATIONS SHALL BE SEALED USING METHODS OUTLINED IN SMACNA <br />HVAC AIR DUCT LEAKAGE TEST MANUAL. <br />11. DUCT COLLARS SHALL BE PROVIDED WHERE DUCTS PASS THROUGH MASONRY WALLS AND PARTITIONS WHICH EXTEND FULL HEIGHT TO <br />THE UNDERSIDE OF THE STRUCTURE AND SHALL BE FABRICATED FROM 22 GAUGE GALVANIZED STEEL SHEET. DUCT COLLAR SHALL BE <br />PROVIDED ON BOTH SIDES OF WALL AND PARTITION EXCEPT OLLAR HALL BE M TTED <br />S S C 5 0 I ON THAT SIDE OF THE WALL ON WHICH <br />REGISTERS AND GRILLES ARE INSTALLED. FLANGES SHALL BE INSTALLED TIGHT AGAINST THE WALL. THE SPACE BETWEEN THE DUCT AND THE <br />WALL SHALL BE PACKED WITH FIBERGLASS BLANKET IN ULATION. <br />S <br />12. DUCT HANGERS AND SUPPORTS SHALL BE IN ACCORDANCE WITH SMACNA HVAC DUCT CONSTRUCTION STANDARDS. IN ADDITION, <br />HANGERS SHALL BE SPACED NOT OVER 8'_0" ON CENTERS. FOR RECTANGULAR DUCTS, WITH LONGEST DIMENSIONS UP THROUGH 60" <br />HANGERS, THE HANGERS SHALL BE GALVANIZED STEEL STRAP TYPE; WITH LONGEST DIMENSION 61" AND LARGER, HANGERS SHALL BE <br />TRAPEZE TYPE CONSTRUCTED OF GALVANIZED STEEL ANGLES WITH ROUND HANGERS RODS. SIZES FOR STRAP HANGERS AND TRAPEZE <br />ANGLES AND RODS SHALL BE BASED ON DUCT SIZE AS SCHEDULED IN THE SMACNA HVAC DUCT CON TRUCTION STANDARD . <br />S S <br />13. FOR ROUND DUCTS; THE HANGERS SHALL BE THE GALVANIZED STEEL STRAP HANGERS. SIZES AND NUMBER FOR STRAP HANGERS SHALL <br />BE BASED ON DUCT SIZE AS SCHEDULED IN THE SMACNA HVAC DUCT CONSTRUCTION STANDARDS. <br />D. ROOF CAPS <br />1. UNLESS OTHERWISE SPECIFIED, ROOF INTAKE AND EXHAUST CAPS SHALL BE ROUND, MINIMUM 16 GAUGE SPUN -ALUMINUM WITH <br />CONTINUOUSLY WELDED CURB CAP. PROVIDE WITH MANUFACTURER'S ROOF CURB. PROVIDE SLOPED CURB FOR PITCHED ROOFS. EXHAUST <br />ROOF HOODS PROVIDED WITH BACKDRAFT DAMPER. OA HOODS SHALL BE PROVIDED WITH A 120/1 MOTORIZED DAMPER TO CLOSE WHEN <br />EQUIPMENT SERVED IS POWERED DOWN UNLESS INDIVIDUAL MOTORIZED DAMPERS ARE INDICATED AT EQUIPMENT BRANCHES. <br />E. LOUVERS <br />1. LOUVERS SHALL BE STATIONARY ALUMINUM, 4" DEEP WITH DRAINABLE BLADES, HIDDEN MULLION, ALL 0.081" ALUMINUM WALL <br />THICKNESS, AND KYNAR FINISH TO BE COORDINATED WITH ARCHITECT FOR COLOR. LOUVER SIZED FOR 50% FREE AREA FOR 800 FPM <br />AIRSPEED TO PREVENT WATER ENTRAINMENT. PROVIDE EACH LOUVER WITH A MINIMUM 18" DEEP FULL SIZE PLENUM WITH DUCT <br />CONNECTION SIZED AS INDICATED. PROVIDE OUTDOOR AIR SUPPLY LOUVERS INLET PLENUMS WITH ELASTOMERIC LINER AND PROVIDE <br />MOTORIZED DAMPER AT CONNECTED DUCT. LAYOUT BASIS IS RUSKIN ELF375DX. PROVIDE WITH INSECT SCREENING AT LOUVER FACE. <br />V. HVAC EQUIPMENT <br />A. CONTRACTOR SHALL VERIFY REASONABLE OPERATION OF EXISTING UNIT TO REMAIN IN USE AND MAKE ANY REPAIRS OR COMPONENT <br />REPLACEMENT REQUIRED TO HAVE THE UNITS OPERATE A FULL CAPACITY. ALL RUST AND EXTERIOR DAMAGE SHOULD BE REPAIRED AND <br />PAINTED. A TECHNICIAN'S REPORT SHOULD BE ATTAINED AND DELIVERED TO THE OWNER FOR APPROVAL FOR EXISTING EQUIPMENT REPAIRS. <br />B. ALL NEW AND REUSED UNIT ACCESS AND CONNECTION OPENINGS SHALL BE SEALED WITH PROVIDED GROMMETS, GASKETS FOR AIR <br />TIGHT CONSTRUCTION WITH CONTINUOUS CASE INSULATION. CONTRACTOR TO REPAIR OR REPLACE DAMAGED DOORS, SEALS, GASKETS, <br />GROMMETS ETC... THAT PREVENT AIR -TIGHT CASING. <br />C. ALL EXHAUST SHALL BE DUCTED FROM UNIT OUTLET TO ROOF CAP INLET OR LOUVER WITH CONTINUOUSLY SEALED DUCTING. NO <br />EXHAUST SHALL BE OPENED INTO THE BUILDING EXTERIOR. PROVIDE ENCLOSED DUCT TRANSITION TO EACH ROOF CAM OR WALL LOUVER. <br />D. ALL AIR MOVING EQUIPMENT SHALL BE PROVIDED WITH VIBRATION ISOLATION AND FLEXIBLE DUCT CONNECTIONS. <br />E. CONTRACTOR SHALL PROVIDE GRAVITY DRAINAGE FOR ALL CONDENSATE -PRODUCING HEATING/COOLING EQUIPMENT VIA GRAVITY <br />DRAINAGE OR CONDENSATE PUMP IF GRAVITY DRAINAGE CANNOT BE ACHIEVED. <br />F. PROVIDE 2 SETS OF FILTERS FOR EACH FILTERED HVAC EQUIPMENT PIECE. PROVIDE FILTER AT INITIAL START-UP, JUST BEFORE TEST AND <br />BALANCE AND AGAIN AT TURN OVER TO OWNER. ALL AIR INLETS AND UTLETS SHALL BE EALED WI H F T R M <br />0 S T IL E EDIA DURING GENERAL <br />CONSTRUCTION PRIOR TO TEST AND BALANCE. <br />G. ROOFTOP UNITS <br />1. PROVIDE PACKAGED DX ROOFTOP UNITS MANUFACTURED BY TRANE, LENNOX, AAON, CARRIER, OR YORK. PROVIDE WITH CAPACITIES <br />AND ACCESSORIES PER UNIT SCHEDULE. PROVIDE CUSTOM SLOPED ROOF CURBS FOR ROOFS WITH GREATER THAN 2% SLOPE. PROVIDE <br />VIBRATION ISOLATION TYPE ROOF CURBS FOR UNITS DIRECTLY OVER MUSIC REHEARSAL, PERFORMANCE OR OTHER ASSEMBLY AREAS. ALL <br />UNITS SHALL BE PROVIDED WITH A MOTORIZED OA DAMPER OR ECONOMIZER, COIL GUARDS, HINGED ACCESS PANELS, SUPPLY AND RETURN <br />SMOKE DETECTORS, STAINLESS STEEL DRAIN PAN AND BURNER (FOR GAS UNITS). PROVIDE EACH RTU WITH CONVENIENCE RECEPTACLE <br />(SEPARATE CIRCUIT) AND DISCONNECT. OTHERWISE COORDINATE WITH THE ELECTRICAL CONTRACTOR FOR FIELD -MOUNTED DISCONNECT <br />AND RECEPTACLE. ROUTE ALL CONDENSATE PIPING TO NEAREST ROOF DRAIN OR OTHER LOCALLY APPROVED LOCATION WITH THE REQUIRED <br />AIR GAP. NO PIPING SHALL SIT ON THE ROOF SURFACE. SHIFT EXISTING OR NEW VENTS OR EXHAUST TERMINATIONS OR SHIFT UNITS AS <br />NEEDED TO ASSURE 10' BETWEEN ANY EXHAUST OR FLUE AND THE RTU INTAKE. <br />2. ADAPTER CURBS MAY BE USED WITH SPECIFIC ENGINEER APPROVAL OF SPECIFICALLY SUBMITTED ROOF CURBS (MAXIMUM OF 18" CURB <br />HEIGHT). CONTRACTOR SHALL BE RESPONSIBLE FOR STRUCTURAL ANALYSIS OF EXISTING CURBS AND UNIT SUPPORTS FOR ADAPTER CURB <br />CONNECTIONS. <br />G. SPLIT SYSTEMS <br />1. INDOOR UNITS SHALL BE INSTALLED DEAD LEVEL WITH PROVISIONS FOR POSITION, CONDENSATE DRAINAGE AND REFRIGERANT PIPE <br />CONNECTIONS THAT DO NOT BLOCK EQUIPMENT SERVICE OR FILTER ACCESS. PROVIDE CONDENSERS WITH ANTI -SHORT CYCLE TIMER, <br />CRANKCASE HEATER, LOW AMBIENT CONTROLS, COIL GUARDS. INDOOR AND OUTDOOR PIECES SHALL BE BY IDENTICAL MANUFACTURER <br />LISTED BY THE MANUFACTURE AS COMPATIBLE. CASED COOLING COILS SHALL BE SPECIFICALLY LISTS AND WITH MATCHING SIZE WHEN USED <br />WITH A FURNACE. FURNACES SHALL BE HIGH EFFICIENCY FOR USE WITH PVC FLUE AND INTAKE REQUIRING FLUE CONDENSATE NEUTRALIZER <br />AND DRAIN. <br />2. REFRIGERANT PIPING SHALL BE RUN PARALLEL TO BUILDING WALLS IN WHICH INSTALLED UNLESS OTHERWISE INDICATED ON THE <br />DRAWINGS WITH CONTINUOUS ELASTOMERIC INSULATION AND JACKETING INDOOR AND OUT. PROVIDE WITH AIR TIGHT VAPOR <br />ENCAPSULATION BY USE OF MASTIC AND JACKETING. PROVIDE PIPE HANGER WITH SADDLES AT PIPE SUPPORTS FOR REFRIGERANT PIPING. <br />TYPE L OR K (UNDERGROUND) COPPER TUBING INTENDED FOR ACR APPLICATIONS- DEHYDRATED, CHARGED WITH NITROGEN, AND PLUGGED <br />BY THE MANUFACTURER. PROVIDE FORMED FITTINGS, SUCH AS ELBOWS (SHALL BE LONG SWEEP) AND TEES, ALL JOINTS SHALL BE BRAZED <br />WITH OXY-ACETYLENE TORCHES BY A QUALIFIED TECHNICIAN. SOFT COPPER TUBING SHALL NOT BE ALLOWED UNLESS NOTED ON THE <br />DRAWINGS. <br />3. PROVIDE INDOOR UNITS LOCATED ABOVE CEILINGS WITH SLOPED SECONDARY DRAIN PAN WITH A CAPPED VALVE AND THREADED HOSE <br />OUTLET. UNIT AND EXTERIOR DRAIN PAN SUPPORT SHALL BE INDEPENDENT SUCH THAT DRAIN PAN CAN BE REMOVED WITHOUT AFFECTING <br />AIR HANDLING UNIT INSTALLATION. <br />4. THE PREFERENCE SHALL BE A FLOAT SWITCH IN THE EXTERNAL DRAIN PAN TO SHUT THE UNIT DOWN. IF NOT ALLOWED BY CODE OR <br />INSPECTOR, ROUTE THE CONDENSATE TO A CONSPICUOUS LOCATION- OVER A MOP SINK OR SERVICE SINK IF POSSIBLE. <br />5. FOR LONG REFRIGERANT LINE LENGTHS ABOVE 100', PROVIDE ALL ACCESSORIES, ACCUMULATORS, RESIZED PISTONS AND LINE SETS PER <br />MANUFACTURER REQUIREMENTS. <br />6. FLOOR MOUNTED VERTICAL UNITS SHALL BE MOUNTED ON A 24" TALL, FULL SIZE RETURN PLENUM WITH METAL GAUGE SUFFICIENT TO <br />SUPPORT UNIT WEIGHT. <br />H. FANS -GENERAL <br />1. FANS SHALL BE TESTED AND RATED IN ACCORDANCE WITH AMCA 210. <br />2. ALL FANS SHALL BE SUPPORTED INDEPENDENT OF CONNECTED DUCT OR CEILING SUPPORTS AND PROVIDED WITH FLEXIBLE <br />INLET/OUTLET CONNECTIONS. <br />3. FAN WHEELS SHALL BE STATICALLY AND DYNAMICALLY BALANCED. <br />4. FANS SHALL BE DIRECT DRIVE WITH SPEED CONTROLLER, DIRECT DRIVE ECM. FANS SHALL NOT BE BELT DRIVE UNLESS SPECIFICALLY <br />NOTED ON PLANS. V-BELT DRIVES SHALL BE DESIGNED FOR NOT LESS THAN 150% OF CONNECTED DRIVING CAPACITY AND MOTOR SHEAVES <br />SHALL BE ADJUSTABLE TO PROVIDE NOT LESS THAN 20% SPEED VARIATION. SHEAVES SHALL BE SELECTED TO DRIVE THE FAN AT A SPEED TO <br />PRODUCE THE SCHEDULED CAPACITY INDICATED ON THE DRAWINGS WHEN SET AT THE APPROXIMATE MIDPOINT OF THE SHEAVE <br />ADJUSTMENT. MOTORS WITH V-BELT DRIVES SHALL BE PROVIDED WITH ADJUSTABLE BASES. <br />5. SAFETY/DISCONNECT SWITCHES (UNLESS SCHEDULED AS UNIT -INTEGRAL) AND STARTERS SHALL BE PROVIDED <br />6. BY ELECTRICAL CONTRACTOR AND SHALL CONFORM TO REQUIREMENTS OF ELECTRICAL DRAWINGS AND SPECIFICATIONS. MECHANICAL <br />CONTRACTOR SHALL COORDINATE MOUNTING LOCATION TO MAINTAIN MAINTENANCE CLEARANCES. ALL THREE PHASE FANS SHALL BE <br />PROVIDED WITH STARTER AND/OR CONTACTORS AS REQUIRED TO CONTROL FANS AND AUXILIARY DEVICES SUCH AS CONTROLS SYSTEM <br />TIE-IN OR DAMPER ACTUATION. <br />L CENTRIFUGAL ROOF FANS <br />1. FANS SHALL BE CENTRIFUGAL ROOF EXHAUSTERS WITH WATERPROOF DESIGN SO THAT WATER CANNOT ENTER THE BUILDING <br />THROUGH FAN HOUSING WHETHER OR NOT FAN IS OPERATING. FAN SHALL BE EQUIPPED WITH A BACKDRAFT DAMPER ON INLET, A BIRD <br />SCREEN ON OUTLET AND A FACTORY FABRICATED ROOF CURB. GENERAL EXHAUST LAYOUT BASIS (NON- KITCHEN APPLICATIONS)- COOK ACED <br />2. FAN SHALL HAVE A ONE-PIECE ALUMINUM HOUSING ENCLOSING THE MOTOR AND DRIVE, AN ALUMINUM SHROUD ENCLOSING THE FAN <br />WHEEL, AND AN ALUMINUM CURB CAP. CURB CAP SHALL HAVE A 1 INCH WIDE BY 1/4 INCH THICK FOAM RUBBER GASKET FACTORY APPLIED <br />TO UNDERSIDE PERIMETER OF CURB CAP. AN INTERNAL POWER WIRING POST SHALL EXTEND FROM MOTOR COMPARTMENT THROUGH <br />CURB CAP. WHERE WIRING POST PENETRATES HOUSING AND CURB CAP, PENETRATION SHALL BE SEALED. <br />3. FAN WHEEL SHALL BE FORWARD CURVED OR BACKWARD INCLINED CENTRIFUGAL TYPE OF ALUMINUM CONSTRUCTION. FAN WHEEL <br />SHALL BE STATICALLY AND DYNAMICALLY BALANCED. ON BELT DRIVE UNITS, SHAFT BEARINGS SHALL BE SELF -ALIGNING, PILLOW BLOCK BALL <br />TYPE. BEARINGS NOT PERMANENTLY SEALED AND LUBRICATED SHALL HAVE EXTENDED GREASE FITTINGS FOR EASY ACCESS. <br />4. MOTOR AND DRIVE SHALL BE LOCATED IN A VENTILATED COMPARTMENT OUTSIDE OF THE AIR STREAM. FAN SHALL HAVE FACTORY <br />INSTALLED DISCONNECT SWITCH PRE -WIRED TO MOTOR AND MOUNTED WITHIN MOTOR COMPARTMENT. MOTOR AND DRIVE SHALL BE <br />MOUNTED ON VIBRATION ISOLATORS. <br />5. KITCHEN EXHAUST FANS SHALL BE UL 762 RATED AND PROVIDED WITH POWER/CONTROL WIRING OUTSIDE OF FAN HOUSING AND <br />CURB. FANS SHALL BE MOUNTED WITH 18" MINIMUM HEIGHT FROM FAN BASE TO ROOF /FLASHING AND DISCHARGE HEIGHTA MINIMUM <br />OF 40" ABOVE ROOF SURFACE. SIDE INLET FANS SHALL BE PROVIDED WITH INLET HEIGHT SUCH THAT ALL ROOF MOUNTED HORIZONTAL <br />DUCT CAN BE MOUNTED 20" ABOVE ROOF. PROVIDE NON -VENTED CURB FOR FIRE -WRAP APPLICATIONS AND VENTED CURB FOR ENCLOSURE <br />SHAFT APPLICATIONS. <br />6. LOCATE EXHAUST FAN DISCHARGE 10' FROM ANY INTAKE OR BUILDING OPENING OR 2' ABOVE SAID OPENINGS IF CODE ALLOWS. <br />J. IN-LINE/CEILING FANS <br />1. FAN SHALL BE IN -LINE CENTRIFUGAL TYPE WITH SQUARE OR RECTANGULAR HOUSING AND BACKDRAFT DAMPER. FANS SHALL BE <br />DESIGNED FOR HORIZONTAL OR VERTICAL MOUNTING. LAYOUT BASIS IS COOK GN/GC. <br />2. FAN HOUSING SHALL BE STEEL WITH FACTORY APPLIED BAKED ENAMEL PAINT ON EXTERIOR. HOUSING SHALL BE INTERNALLY <br />INSULATED WITH 1/2" THICK (MINIMUM) COATED FIBERGLASS INSULATION. INSULATION SHALL COMPLY WITH ASTM E84 AND NFPA 255 FOR <br />MAXIMUM RATINGS OF FLAME SPREAD RATING OF 25 AND SMOKE DEVELOPED RATING OF 50. HOUSING SHALL HAVE MOUNTING BRACKETS <br />AT EACH CORNER. <br />3. FAN WHEEL SHALL BE BACKWARD INCLINED CENTRIFUGAL TYPE OF ALUMINUM CONSTRUCTION. ON BELT DRIVE UNITS, SHAFT <br />BEARINGS SHALL BE SELF -ALIGNING, PILLOW BLOCK BALL TYPE. BEARINGS NOT PERMANENTLY LUBRICATED AND SEALED SHALL HAVE <br />EXTENDED GREASE FITTINGS. <br />4. MOTOR AND DRIVE SHALL BE MOUNTED ON VIBRATION ISOLATORS. FAN SHALL HAVE A FACTORY INSTALLED DISCONNECT SWITCH <br />MOUNTED ON EXTERIOR OF HOUSING AND PRE -WIRED TO FAN MOTOR. <br />5. PROVIDE ALUMINUM GRILLE OPTION FOR CEILING MOUNTED FANS. FANS SHALL BE ROUTED TO ROOF CAP OR LOUVER SIZED AT 800 <br />FPM OUTLET AIRSPEED. <br />VI. PIPING <br />A. USE DIELECTRIC UNIONS WHERE DISSIMILAR METALS ARE JOINED TOGETHER. <br />B. DOMESTIC WATER & PUMPED CONDENSATE <br />1. UNDERGROUND WATER SERVICE PIPING 3" IN ZE AND LAR ER HAL <br />SI G S L BE CLASS 50 DUCTILE IRON PIPE, AWWA C151, WITH HUB AND <br />SPIGOT, PUSH_ON JOINTS, AND CLASS 50 OR GREATER MECHANICAL JOINT DUCTILE IRON FITTINGS ALL CEMENT LINED PER AWWA C104. <br />MECHANICAL JOINTS FOR DUCTILE IRON PIPE SHALL BE MADE WITH A F LL ER <br />0 OW GLAND GASKET BOLTS AND NUTS. PUSH ON JOINTS F R <br />0 <br />DUCTILE PIPE SHALL BE MADE WITH A NE PIE E L RI AT <br />0 C UB C ED COMPRESSION RUBBER GASKET AS PER AWWA Clll. <br />2. UNDERGROUND STEEL PIPE AND FITTINGS INCLUDING THE PORTION THROUGH THE FLOOR SHALL BE PROTECTED AGAINST CORROSION <br />BY APPLICATION OF PROTECTIVE COATINGS. PRIOR TO COATING, PIPE AND FITTINGS SHALL BE CLEANED OF ALL RUST, SCALE, DIRT AND OIL. <br />PIPES AND FITTINGS SHALL BE GIVEN TWO COATS OF A COAL -TAR BASE BITUMINOUS PROTECTIVE COATING, EACH HAVING A DRY FILM <br />THICKNESS OF 7-9 MILS. THE COMBINED THICKNESS OF BOTH COATS COMBINED SHALL BE 15-18 MILS. <br />3. UNDERGROUND WATER SERVICE PIPING 2 1 2" IN SIZE AND SMALLER T A P - <br />O DINT 1' 0" ABOVE THE FINISHED FLOOR SHALL BE. TYPE "K" <br />HARD DRAWN COPPER TUBING, ASTM B88, WITH BRAZED JOINTS AND WROUGHT COPPER, ANSI B16.22, OR CAST BRONZE, ANSI B16.18, <br />SOCKET FITTINGS.. BRAZED JOINTS SHALL BE MADE USING BCUP-5 BRAZING ALLOY WITH A COMPATIBLE FLUX. <br />4. ABOVE -GROUND WATER PIPING - 4" AND SMALLER SHALL BE. TYPE "L" HARD DRAWN COPPER TUBING, ASTM B88, WITH SOLDERED <br />JOINTS AND WROUGHT COPPER, ANSI B16.22, OR CAST BRONZE, ANSI B16.18, SOCKET FITTINGS. SOLDER JOINTS SHALL BE MADE USING A <br />95-5 TIN -ANTIMONY SOLDER (NO -LEAD SOLDER) WITH A COMPATIBLE FLUX. <br />5. UNDERGROUND WATER PIPING TO TRAP PRIMERS OR HVAC CONDENSATE PUMP DISCHARGE SHALL BE. TYPE "L" SOFT DRAWN COPPER <br />TUBING, ASTM B88, WITHOUT FITTINGS. <br />6. FLANGED JOINT SHALL BE MADE WITH RING TYPE N N-METALLI ASK T L <br />0 C G E S BO TS AND NUTS. <br />7. THREADED JOINTS AT EQUIPMENT CONNECTIONS SHALL BE MADE UP WITH TEFLON TAPE. AFTER CUTTING BUT PRIOR TO THREADING, <br />PIPE SHALL BE REAMED AND SHALL HAVE BURRS REMOVED. <br />8. GROOVED MECHANICAL JOINTS: GROOVED JOINTS FOR COPPER AND GALVANIZED STEEL PIPES SHALL BE INSTALLED USING BOLTED <br />MECHANICAL COUPLING, PRESSURE -RESPONSIVE GASKET ALONG WITH GROOVED AND FITTINGS. LAYOUT BASIS SHALL BE ANVIL GRUV-LOCK, <br />9. DIELECTRIC ADAPTERS SHALL BE PROVIDED BETWEEN COPPER AND IRON PIPE CONNECTIONS AND BETWEEN FERROUS AND <br />NONFERROUS PIPING OR EQUIPMENT. <br />10. UNDERGROUND WATER PIPING SHALL HAVE A MINIMUM COVER OF 3'- 0" TO THE TOP OF THE PIPE. <br />11. INSTALL WATER HAMMER ARRESTORS ABOVE CEILING ON THE HOT AND COLD WATER BRANCH LINES SERVING A BATTERY OF FIXTURES; <br />ON THE COLD WATER BRANCH LINES SERVING INDIVIDUAL FLUSH VALVE WATER CLOSETS AND URINALS; AND ELSEWHERE AS INDICATED ON <br />THE DRAWINGS. PROVIDE ACCESS PANEL FOR WHA LOCATED ABOVE HARD CEILINGS. <br />12. VACUUM BREAKERS SHALL BE PROVIDED ON ALL HOSE OUTLETS, HOSE BIBS AND HYDRANTS UNLESS THE DRAWINGS INDICATE THAT A <br />BACKFLOW PREVENTER IS TO BE PROVIDED ON THE PIPING SERVING THE OUTLET. <br />13. INSTALL 1/2" CW LINE FROM NEAREST CW MAIN OR BRANCH LINE TO ALL FLOOR DRAINS WITH TRAP PRIMER FOR TRAP PRIMING. <br />UNDERGROUND PIPING FROM TRAP PRIMER TO FLOOR DRAINS SHALL BE INSTALLED WITHOUT FITTINGS. TRAP PRIMERS SHALL BE PROVIDED <br />FOR ALL FLOOR DRAINS AND HUB DRAINS. <br />14. CONNECT HOT AND COLD WATER PIPING SYSTEM TO EQUIPMENT AS INDICATED, AND COMPLY WITH EQUIPMENT MANUFACTURER'S <br />INSTALLATION INSTRUCTIONS. PROVIDE SHUT-OFF BALL VALVE AND UNION FOR EACH CONNECTION, PROVIDE DRAIN VALVE ON DRAIN <br />CONNECTIONS. PROVIDE SINGLE SHUTOFF BALL VALVE FOR HEADERS SERVING HOT OR COLD WATER TO MULTIPLE FIXTURES WITHIN A <br />SINGLE WALL OR CHASE. PROVIDE ACCESS PANEL FOR VALVES INSTALLED ABOVE HARD CEILINGS. <br />15. ALL DOMESTIC WATER SERVICE AND SUPPLY PIPING INSTALLED UNDER THIS DIVISION SHALL BE DISINFECTED WITH CHLORINE BEFORE IT <br />IS PLACED INTO OPERATION. THE CHLORINATING MATERIAL SHALL BE LIQUID CHLORINE CONFORMING TO FED. SPEC. BB-C-120 AND SHALL BE <br />INTRODUCED TO THE SYSTEM BY EXPERIENCED OPERATORS ONLY. THE CHLORINE SOLUTION APPLIED TO THE PIPING SECTIONS OR SYSTEM <br />SHALL CONTAIN AT LEAST FIFTY PARTS PER MILLION OF AVAILABLE CHLORINE AND SHALL REMAIN IN THE SECTIONS OR SYSTEM FOR A PERIOD <br />OF NOT LESS THAN SIXTEEN (16) HOURS. DURING THE DISINFECTION PERIOD ALL VALVES SHALL BE OPENED AND CLOSED AT LEAST FOUR <br />TIMES. ATTHE END OF THE RETENTION PERIOD, NO LESS THAN 50 PPM OF CHLORINE SHALL BE PRESENT IN THE EXTREME END OF THIS <br />SYSTEM. AFTER THEDISINFE I PERI DTH <br />CT ON 0 E CHLORINATED WATER SHALL BE FL <br />USHER FROM THE Y TEM WI H L <br />S S T C EAR WATER UNTIL THE <br />RESIDUAL CHLORINE CONTENT IS NOT GREATER THAN TWO -TENTHS - (0.2) - PARTS PER MILLION. THE CONSTRUCTION MANAGER SHALL <br />SUBMIT TO THE ARCHITECT WRITTEN CERTIFICATION THAT THE SYSTEM WAS DISINFECTED. CERTIFICATION SHALL INCLUDE NAME OF <br />PROJECT, NAME OF OWNER, NAME OF OPERATORS, DATE OF DISINFECTION, TIMES OF DISINFECTION PERIOD, MAXIMUM CHLORINE LEVEL <br />AND RESIDUAL CHLORINE LEVEL. <br />C. NATURAL GAS <br />1. ABOVE-GR ND <br />OU MAXIMUM 2 1 2' GAS PIPING SHALL BE BLACK STEEL PIPE .S HED LE 4 <br />/ C U 0, ASTM A53 WITH STANDARD WEIGHT <br />WROUGHT STEEL SO KET-WELDFITTIN P <br />C GS ER ASTM A234 OR THREADED CONNECTIONS. PIPE SIZES 3" AND UP OR WITH PRESSURE ABOVE <br />5PSI SHALL ONLY BE PERMITTED WITH SOCKET -WELDED JOINTS (NO THREADED CONNECTIONS). <br />2. STEEL GAS PIPING TO BE INSTALLED UNDERGROUND SHALL BE FURNISHED WITH A FACTORY APPLIED COATING WHICH SHALL CONSIST <br />OF A RESILIENT, EXTRUDED, POLYETHYLENE SLEEVE WHICH IS SEALED TO THE PIPE. THE PLASTIC COATING SHALL BE NOT LESS THAN 25 MILS <br />THICK AND SEALED TO THE PIPE WITH A HOT APPLIED ADHESIVE WHICH RETAINS ITS ELASTICITY IN HOT AND COLD ENVIRONMENTS. <br />3. FIELD APPLIED WRAPPING TAPE FOR FITTINGS AND JOINTS SHALL BE COAL TAR WITH HEAVY VINYL OR POLYESTER FILM BACKING <br />MEETING FEDERAL SPECIFICATION HH-T-30A, TAPECOAT CT OR TAPECOAT 20 OR JT JOINT COATINGS, INC., WITH PRIMER, APPLICATION <br />PROCEDURES AND HEATING IN ACCORDANCE WITH THE TAPE MANUFACTURER'S RECOMMENDATIONS. <br />4. ARRANGE WITH THE UTILITY COMPANY TO PROVIDE GAS SERVICE TO INDICATED LOCATION WITH SHUTOFF AT TERMINATION. MAKE <br />ALL ARRANGEMENTS WITH UTILITY AS TO THE EXTENT OF ITS WORK, AND PAY ALL COSTS, FEES AND SECURE PERMITS INVOLVED TO OBTAIN <br />SERVICE FOR THE BUILDING. <br />5. PROVIDE SHUTOFF IN GAS SERVICE PIPE AT ENTRY IN BUILDING, EXT/END PIPE TO GAS METER LOCATION INDICATED; PROVIDE PARTS <br />AND ACCESSORIES REQUIRED BY UTILITY TO CONNECT TO METER. <br />6. PROVIDE VALVE AND UNION SHALL BE PROVIDED AT EACH CONNECTION TO A PIECE OF EQUIPMENT. EQUIPMENT PROVIDED WITH A <br />FLANGED INLET SHALL HAVE A FLANGED CONNECTION. <br />7. DRIP LEGS, 6-INCHES LONG, SHALL BE PROVIDED IN GAS PIPING AT ENDS OF HORIZONTAL RUNS, AT THE BASE OF RISERS AND AT <br />CONNECTIONS TO EQUIPMENT. DRIP LEG CAP SHALL BE REMOVABLE WITH MINIMUM 4" BETWEEN CAP AND WALL OR ROOF. <br />8. GAS PIPING WITHIN THE BUILDING SHALL BE RUN ABOVE FLOOR SLAB. <br />9. PRESSURE REGULATORS ARE TO BE PROVIDED ON ALL EQUIPMENT IF NOT PROVIDED AS PART OF THE EQUIPMENT. COORDINATE <br />INLET/OUTLET PRESSURES WITH ACTUAL DELIVERED PRESSURE AND EQUIPMENT INLET PRESSURES. CONTRACTOR SHALL ARRANGE FOR <br />ADJUSTMENT OF GAS PRESSURE TO PREVENT EXCESSIVE OR INSUFFICIENT GAS PRESSURE TO ALL EQUIPMENT PIECES. <br />10. PROVIDE FLEX HOSE CONNECTION TO ALL INDOOR APPLIANCES NOT SUPPLIED WITH THE EQUIPMENT PIECE BY THE OWNER OR <br />EQUIPMENT PROVIDER. <br />11. THREADED JOINTS SHALL BE MADE WITH A MIXTURE OF GRAPHITE AND OIL APPLIED TO MALE THREADS ONLY. AFTER CUTTING AND <br />PRIOR TO THREADING, PIPE SHALL BE REAMED AND SHALL HAVE BURRS REMOVED. <br />12. WELDED JOINTS SHALL BE FUSION WELDED IN ACCORDANCE WITH ANSI B31, SECTION 6. <br />13. FLANGED JOINTS SHALL BE FACED TRUE, PROVIDED WITH GASKET AND MADE SQUARE AND TIGHT. <br />14. BRAZED JOINTS SHALL BE MADE UP USING BCUP-5 BRAZING ALLOY WITH A COMPATIBLE FLUX. <br />15. ALL STEEL FITTINGS AND JOINTS IN UNDERGROUND PIPING SHALL BE FIELD -COATED USING A PRIMER AND FLEXIBLE POLYETHYLENE TAPE <br />AND THE SAME MANUFACTURER AS THE PIPE COATING. DAMAGED COATING SHALL BE REPAIRED WITH PRIMER AND TAPE AS SPECIFIED FOR <br />FITTINGS AND JOINTS. <br />D. SANITARY WASTE &VENT, STORM, GREASE WASTE <br />1. UNDERGROUND SANITARY, WASTE AND VENT PIPING, AND STORM DRAINAGE PIPING, AND INDOOR PIPING ABOVE 8" IN SIZE SHALL BE <br />SERVICE WEIGHT (COATED) CAST IRON SOIL PIPE AND FITTINGS, ASTM A74, WITH GASKET HUB AND SPIGOT JOINTS, ASTM C564. GASKET <br />JOINTS FOR CAST IRON PIPE SHALL BE MADE WITH LUBRICATED NEOPRENE COMPRESSION GASKETS. PVC SHALL BE PERMITTED IF ALLOWED <br />BY LOCAL CODE. UNDERGROUND PVC PIPING SHALL BE SCHEDULE 40 PVC WITH SOLVENT WELD JOINTS MEETING ASTM D-1785 AND ASTM <br />D-2665. <br />2. ABOVE -GROUND SANITARY, WASTE AND VENT AND STORM DRAINAGE PIPING 8" AND SMALLER SHALL BE SERVICE WEIGHT CAST IRON <br />SOIL PIPE AND FITTINGS, ASTM A888 AND CISPI 301, WITH STANDARD NO -HUB COUPLINGS. PVC SHALL BE PERMITTED OUTSIDE OF RETURN <br />AIR PLENUMS WITH OWNER APPROVAL. NEOPRENE RUBBER GASKET AND MINIMUM 24 GAUGE TYPE 304 STAINLESS STEEL SHIELD AND FOUR <br />STAINLESS STEEL BANDS FOR SIZES 1 1/2" THROUGH 4", SIX BANDS MINIMUM FOR SIZED 5" AND LARGER. 6" PIPE AND UP: NEOPRENE <br />ELASTOMERIC GASKET AND SERIES 300 STAINLESS STEEL SHIELD AND MULTIPLE DRAW BANDS AND SCREW CLAMPS CONFORMING TO ASTM <br />C-564 AND CISPI STANDARD 310-90. ABOVE -GROUND SANITARY PIPING, LOCATED OUTSIDE OF RETURN AIR PLENUMS MAY ALSO BE <br />SCHEDULE 40 PVC WITH SOLVENT WELD JOINTS MEETING ASTM D-1785 AND ASTM D-2665 PER OWNER APPROVAL. <br />3. ALL WASTE PIPING 1" IN SIZE AND SMALLER SHALL BE TYPE "L" HARD DRAWN COPPER TUBING, ASTM B88, WITH SOLDERED JOINTS AND <br />WROUGHT COPPER, ANSI B16.22, OR CAST BRONZE, ANSI B16.18, SOCKET FITTINGS. SOLDERED JOINTS FOR TYPE'L' COPPER TUBING AND <br />CAST DMV BRONZE PIPE SHALL BE MADE WITH 95-5 TIN -ANTIMONY (NO LEAD) SOLDER AND COMPATIBLE FLUX. <br />E. PIPING HANGERS <br />1. PROVIDE CLEVIS SUPPORTS WITH BEAM CLAMP, CONCRETE ANCHORS (CONCRETE STRUCTURE), SCREWED BRACKET (WOOD <br />STRUCTURE). PROVIDE HANGER OUTSIDE OF INSULATION WITH RIGID FOAM GLASS INSULATION SECTION AT HANGERS. PROVIDE 16 GAUGE <br />PIPING SADDLE AT EACH HANGER. NO WELDING OR CUTTING OF STEEL STRUCTURAL MEMBERS SHALL BE PERMITTED. LAYOUT BASIS SHALL BE <br />ANVIL 260. <br />2. PROVIDE SEISMIC HANGERS PER DRAWING REQUIREMENTS. <br />3. HANGER INSTALLATION FOR HOT WATER PIPING SHALL NOT PREVENT MOVEMENT FOR PIPING EXPANSION. <br />4. SPACING AS FOLLOWS: <br />STEEL PIPE: 1/2" TO 1-1/4" - 7' ; 1-1/2" TO 2-1/2" - 9' ; 3"&4" -12' ; 6"&8" - 17' ; 10" AND UP- 22' <br />COPPER PIPE: 1/2" TO 1" - 5' ; 1-1/4" TO 2" - 7' ; 2-1/2" AND UP - 9' <br />CAST IRON: 10' WITH SUPPORT AT EACH JOINT, TAKEOFF, AND FITTING. <br />PVC DRAINAGE (140 DEG F SERVICE UP TO 6"- 80 DEG F ABOVE 6"): UP TO 3" - 3' ; 4" TO 6" - 4' ; ABOVE 6" - 8' <br />PVC VENT (80 DEG F SERVICE): UP TO 1-1/2" - 5' ; 2"-3" - 6' ; ABOVE 3" 7' <br />U <br />ICI <br />� <br />�� <br />�/ <br />O <br />U) <br />W <br />O <br />CD <br />`T <br />V <br />A <br />m <br />N <br />y <br />W <br />O <br />w <br />A <br />N <br />U t� <br />� <br />� Z <br />w <br />11` <br />W <br />E-( cr <br />0 <br />Lo U <br />Ui <br />w � <br />0 <br />Q <br />� <br />1O Lu <br />V <br />W <br />ir - <br />x = <br />T I- <br />C'7 <br />U U <br />z <br />= <br />N� <br />N <br />U <br />cr <br />N <br />� <br />v1 <br />ui <br />z_ <br />cn <br />D <br />m <br />• <br />A4 <br />• <br />14 <br />SIN HA <br />♦ .• AGE Ng •.y 0. <br />♦ 1 i <br />♦ � <br />o : 0. 7 •• . o <br />v <br />• r <br />* rn <br />• : Q <br />STAT OF ; �% w <br />i % z <br />P• <br />.� w <br />D <br />/ONA E . <br />m <br />Q <br />U <br />Z <br />Q <br />Q <br />ui <br />`1 <br />cn <br />Z <br />Q <br />m <br />w <br />w <br />J <br />•, <br />• <br />CONTRACT DATE: 08.13.2017 <br />BUILDING TYPE: ONE-OFF <br />PLAN VERSION: <br />SITE NUMBER: <br />STORE NUMBER: <br />SUNRISE EATERY <br />5915 GALL BLVD. <br />ZEPHYRHILLS, FL <br />MECHANICAL <br />SPECIFICATIONS <br />M0.2 <br />PLOT DATE: <br />