NOT USED <br />HOOD INSTALLATION: <br />1. INSTALLATION OF VENTILATION SYSTEM WILL BE BY CONTRACTOR. EXHAUST <br />COLLARS WILL BE PROVIDED BY CONTRACTOR. HOODS SHALL BE INSTALLED IN <br />ACCORDANCE WITH NFPA AND ALL OTHER APPLICABLE LOCAL, STATE AND <br />NATIONAL CODES. SPECIAL ATTENTION MUST BE GIVEN TO CODES REGARDING <br />CLEARANCE TO SURROUNDING COMBUSTIBLE AND LIMITED COMBUSTIBLE <br />(NFPA96) CONSTRUCTION (WALLS, CEILINGS, ETC.). <br />2. CONTRACTOR IS RESPONSIBLE FOR DRILLING RETAINING BOLT HOLES INTO WALL <br />MOUNTING FLANGES AT TOP AND BOTTOM OF HOOD AND PROVIDING THE <br />HARDWARE. <br />3. CEILING ENCLOSURE FURNISHED BY HOOD MANUFACTURER WILL BE ATTACHED <br />IN THE FIELD BY CONTRACTOR. <br />4. DUCTWORK BETWEEN HOOD AND ROOF TOP CURB TRANSITION WILL BE <br />PROVIDED BY CONTRACTOR, <br />AIR FLOW REQUIREMENTS <br />1. CAPTIVE AIRE IS NOT LIABLE FOR IMPROPER FUNCTION OF THE SYSTEM CAUSED <br />BY CHANGES IN THE SYSTEM STATIC PRESSURE OR OVER ALL AIR FLOW VOLUME <br />FROM THE ORIGINAL SPECIFIED DESIGN POINTS. EXHAUST DUCT AIR FLOW <br />VELOCITY MUST BE BETWEEN 1500 AND 2200 FPM WITH WELDED DUCT. <br />2. EXHAUST AIR FLOW MUST BE BALANCED WITH OTHER EXHAUST & MAKE-UP AIR <br />SYSTEMS AND THE STORE HVAC SYSTEMS UPON INSTALLATION. TEST & BALANCE <br />IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR. FAN OPERATING <br />SPEED, BELTS AND PULLEYS SHOULD BE RECHECKED AFTER 60 DAYS TO ENSURE <br />PROPER PERFORMANCE. STATIC PRESSURE VALUES ARE GIVEN FOR THE HOOD <br />ONLY AND DO NOT INCLUDE DUCTWORK AND ROOFTOP FANS. <br />3. AIR FLOWS ARE NOTED IN MECHANICAL SCHEDULE. <br />4. CAPTIVE AIRE RESERVES THE RIGHT TO CHANGE SPECIFICATIONS TO MEET CODE <br />N.T.S. 16 <br />OR JOB REQUIREMENTS. <br />CONSTRUCTION <br />1. HOOD SHALL BE FABRICATED IN ACCORDANCE WITH NFPA BULLETIN #96 AND <br />SHALL BEAR THE NSF SEAL OF APPROVAL. HOODS SHALL BE LISTED UNDER UL <br />710 EXHAUST HOODS FOR COMMERCIAL COOKING EQUIPMENT UL FILE # <br />M H 18450. <br />FIRE EXTINGUISHING SYSTEM <br />1. FACTORY INSTALLED FIRE EXTINGUISHING SYSTEM PIPING SUPPLIED AND <br />INSTALLED IN ACCORDANCE WITH NFPA 96 BY FIRE SUPPRESSION INSTALLER. <br />2. CAUTION: FIRE EXTINGUISHING SYSTEM INSTALLED ON SITE MUST BE DONE IN <br />ACCORDANCE WITH AVTEC TO INSURE THAT PIPE DOES NOT INTERFERE WITH <br />HOOD PERFORMANCE. IMPROPER INSTALLATION MAY VOID UL LISTING. <br />FIELD DRILL FOR <br />MOUNTING TO <br />STRUCTURE - <br />FACTORY SUPPLIED SHROUD <br />SHIPPED LOOSE; ATTACHED BY <br />CONTRACTOR <br />(2) UL LISTED GLOBE LIGHTS <br />PAN RACK RETENTION CLIP <br />SKINNED ENDS WITH <br />FINISH ON BOTH <br />OUTER AND INNER <br />GENERAL INSTALLATION GUIDELINES: CONTINUED <br />BANDING - 304 SS <br />3. FIELD MEASURE AND LAYOUT DUCTWORK AS CLOSE AS POSSIBLE TO THE <br />3/4"W X MIN <br />ARCHITECTURAL DRAWING. DUCTWORK SHOULD NOT EXCEED TWO (2) <br />.015"THK <br />3"MIN LONGITUDINAL <br />RADIUS-90 DEGREE TURNS AND TEN (10) FEET IN LENGTH. CONSULT <br />OVERLAP AT <br />FACTORY 800/621-8560 X 4129 FOR DUCTWORK THAT EXCEEDS DESIGN <br />BLANKET JOINT <br />LIMITS --FAN PACKAGE MUST BE MODIFIED FOR SITE ADAPTATION. <br />4. POSITION THE FABRICATED DUCTWORK TO MATCH THE OULET LOCATION <br />ABOVE THE HOOD. THE DUCT MUST BE SIZED AT 7" X 7". <br />5. A CONTINUOUS LIQUID TIGHT WELD TO THE COLLAR TRANSITION AND <br />3"MIN PERIMETER <br />DUCTWORK WILL MEET ANY AND ALL CODE REQUIREMENTS. <br />OVERLAP AT <br />6. CONNECT THE DUCTWORK TO THE CURB TRANSITION TERMINATING AT <br />BLANKET JOINT <br />THE TOP OF THE VENTED CURB EXTENSION BELOW THE FAN BASE. DO <br />TWO LAYERS 1-1/2" THICK <br />NOT TERMINATE THE DUCTWORK AT THE ROOF -LINE. DUCTWORK MUST <br />FIREMASTER BLANKET FOR MIN. ONE <br />BE WELDED WITH A CONTINUOUS LIQUID TIGHT WELD AT EXHAUST FAN <br />1 1/2" HOUR FIRE RATING (STAGGER JOINTS <br />CURB TRANSITION. <br />10-1/2" 12"BETWEEN JOINTS) <br />7. ATTACH FACTORY SUPPLIED HINGE KIT AND GREASE TROUGH TO FAN <br />CURB PER NFPA96-2004. <br />8. ENCLOSE DUCT AS REQUIRED BY LOCAL, STATE AND NATIONAL FIRE <br />PROTECTION AND MECHANICAL CODES OBSERVING IN PARTICULAR THE <br />HOOD <br />CLEARANCE TO COMBUSTIBLE PROVISIONS. <br />EXHAUST <br />1-1/2" <br />9. CONNECT AND TEST THE HOODS FIRE SUPPRESSION SYSTEM. ONLY <br />DUCT <br />21 "TYP <br />PROFESSIONALLY QUALIFIED PERSONS SHOULD PERFORM THESE <br />10-1/2" <br />FUNCTIONS. <br />10. CHECK TO ENSURE PROPER PLACEMENT OF THE GREASE FILTERS AND <br />NOTE: <br />GREASE CUP. <br />1. WRAP GREASE DUCT CONTINUOUS AS SHOWN BELOW FOR ENTIRE LENGTH <br />11. REMOVE THE PROTECTIVE PVC COATING FROM ALL OF THE METAL <br />FROM KITCHEN HOOD CONNECTION TO EXHAUST FAN ON ROOF. <br />SURFACES PRIOR TO USE OF THE APPLIANCES. <br />2. BANDING REQUIREMENTS: USE 304 STAINLESS STEEL FOR MIN. ONE HOUR <br />12. RUN CHECK THE EXHAUST FAN AND FRYER INTERLOCK. <br />RATING <br />13. CERTIFIED TEST & BALANCE CONTRACTOR MUST TAKE FPM READINGS <br />3. WRAP SUPPORT HANGER SYSTEM INDEPENDENTLY WITH SAME THICKNESS <br />ACROSS THE FILTER BANK AND CONFIRM THAT EXHAUST FAN IS <br />FOR EXTERNAL FIRE THREAT CONDITIONS. <br />OPERATING AT OR ABOVE THE EXHAUST CFM DESIGN POINT. ANY AIR <br />FLOW LEVEL BELOW DESIGN POINT IS NOT ACCEPTABLE. DO NOT <br />LACCEPT EVELS. MOTOR RPM READINGS AS A SUBSTITUTE FOR FILTER AIRFLOW HOOD EXHAUST DUCT SYSTEM DETAIL <br />14. CALL FOR FUNCTIONAL INSPECTIONS AS REQUIRED. <br />15. APPLY FABRICATED TRIM (CONTRACTOR SUPPLIED) TO THE CEILING AND <br />WALL AS REQUIRED. FACTORY SUPPLIED SHROUD (ENCLOSURE <br />PANELS) FROM TOP OF HOOD TO CEILING SHOULD BE SCREWED TO <br />ANGLE AT TOP EDGE OF HOOD WITH SELF -TAPPING SS SCREWS. <br />16. CLEAN THE SURFACES OF THE HOOD WITH A MILD DETERGENT USING <br />CARE NOT TO SCRATCH OR DENT THE SURFACE. <br />17. CONTRACTOR RESPONSIBLE FOR REDIRECTING AIRFLOW FROM HVAC <br />DIFFUSERS WITHIN 6-FEET OF FRYER HOOD AWAY FROM HOOD AND <br />COVER DISCHARGE WITH PERFORATED PANEL. <br />18. CONTRACTOR RESPONSIBLE FOR REDIRECTING HVAC RETURNS WITHIN <br />10-FEET OF FRYER HOOD AWAY FROM HOOD. <br />19. CONTRACTOR RESPONSIBLE FOR STORE TEST & BALANCE OF HVAC AND <br />ALL KITCHEN EXHAUST AND SUPPLY FANS ACCORDING TO THE <br />MECHANICAL AIR FLOW BALANCE SCHEDULE. <br />N.T.S. 113 1 <br />FRYER HOOD EXHAUST FAN <br />NEMA 3R DISCONNECT FACTORY <br />WIRED FROM MOTOR TO <br />DISCONNECT THROUGH THE <br />BREATHER TUBE <br />WIRING NOTES. <br />v <br />1. FAN CONTROLS (E.G. ON/OFF SWITCH), THERMAL OVERLOAD PROTECTION AND <br />LIQUID TIGHT FLEXIBLE CONDUIT <br />WIRING FOR FAN TO BE FURNISHED BY OTHERS. <br />2. ANSUL, FAN AND FRYER INTERLOCK SHALL BE WIRED BY OTHERS ACCORDING <br />FIRE -PROOF INSULATION <br />TO SCHEMATIC FURNISHED WITH ARCHITECTURAL DRAWINGS. REMOVABLE <br />BOTTOM SIDE <br />VENTED CURB EXTENSION <br />FIELD DRILL FOR SKIRTS <br />z <br />GENERAL INSTALLATION GUIDELINES: MOUNTING TO <br />MIN. 16 GA. WELDED EXHAUST <br />1. MEASURE AND MARK THE DESIRED HEIGHT AND CENTERLINE OF THE HOOD ON STRUCTURE <br />ROOF SURFACE <br />00 <br />DUCT - EXTEND MIN. OF 18" <br />THE WALL. (REFER. TO THE ARCHITECT'S PLAN FOR THE DIMENSION) THE <br />ABOVE ROOF DECK PER NFPA <br />HEIGHT OF THE PLATE SHELF ABOVETHE FIXED FLOOR IS A CRITICAL <br />DIMENSION. <br />ROOF DECK <br />2. SECURE THE WALL MOUNTING FLANGES AT TOP AND BOTTOM OF HOOD TO A <br />GREASE TRAP <br />MINIMUM OF TWO (2) OR MORE WALL STUDS. <br />3. ALL MOUNTING AND/OR BRACING SHALL COMPLY WITH SEISMIC ZONE 3 <br />REQUIREMENTS. <br />NOT USED I N.T.S. 1 121 HOOD NOTES I N.T.S. 1 101 EXHAUST FAN I N.T.S. 1 9 1 <br />NOT USED I N.T.S <br />0 <br />(L OF PANEL <br />POINT <br />31 /4" <br />MAX. <br />ASTM 325, TYPE 3 <br />NUT & WASHER <br />SIZE AS PER LOADING <br />1/4 <br />WEB MEMBER <br />-EXTEND ANGLE BETWEEN <br />JOISTS, 6' MAX. <br />-L5X3X3/8 <br />STEEL PLATE WASHER <br />GRINNELL FIG. 60. <br />1/4 p OR EQUAL <br />�- C3 X 4.1 _:�\ <br />-JOIST WEB MEMBER <br />_ f �OF PANEL 3-1/4" MAX. <br />POINT <br />EXTEND ANGLE BETWEEN <br />JOISTS, 6' MAX. <br />STEEL PLATE <br />WASHER GRINNELL <br />` FIG. 60. OR EQUAL - <br />WELD L 2-1/2 x 1-1 /2 x 5/16 <br />` 1/4 p <br />BOTTOM CHORD ASTM 325, TYPE <br />OF ROOF JOIST NUT & WASHER, <br />ROD HANGER TOP & BOTTOM OF <br />ANGLE <br />JOIST WEB MEMBER <br />/---3-1 /4" MAX. <br />(�OF PANEL <br />POINT <br />�4"'-BOTTOM CHORD OF <br />ROOF JOIST <br />ASTM 325, TYPE 3 NUT <br />& WASHER <br />ROD HANGER <br />*LOADS LESS THAN 200 POUNDS <br />NOT USED N.T.S. 7 EQUIPMENT SUPPORT FROM BAR JOIST*_7 N.T.S. 6 <br />3 1/4" <br />MAX. FLUE HOOD <br />�- OUTSIDE AIR INTAKE HOOD <br />'CL OF PANEL <br />POINT <br />ASTM 325, TYPE 3 <br />NUT & WASHER <br />SIZE AS PER LOADING <br />BOTTOM CHORD / <br />OF ROOF JOIST 18" 18" BOTTOM CHORD OF <br />ROD HANGER ROOF JOIST <br />ROD HANGER <br />L5X3X3/8 <br />FLEXIBLE <br />CONNECTION (TYP) <br />ROOFTOP <br />UNIT <br />CONDENSATE DRAIN <br />MANUFACTURER'S <br />ROOF CURB <br />FLASHING & COUNTER FLASHING <br />ALL AROUND <br />STING ROOF <br />1" MIN. <br />LOCK TYPE WASHER - <br />........... <br />ROD HANGER SIZED AS NOTED: <br />AS RECOMMENDED BY MANUF. <br />OF EQUIP. SUPPORTED: AS <br />REQ'D. BY WEIGHT OF ITEM TO 1" MIN. <br />BE SUPPORTED <br />SUPPORT STRUCTURAL <br />STEEL MEMBER <br />SCHEMATIC ROD HANGER ATTACHMENT <br />IMPORTANT NOTE: <br />ALL SUPPORTS &/OR BRACING OF EQUIPMENT, CEILING <br />GRID, LIGHT FIXTURES, & ANY OTHER INSTALLED DEVICE <br />SHALL BE COMPLIANT WITH LOCAL SEISMIC ZONE <br />REQUIREMENTS, <br />NO EXCEPTIONS! <br />N.T.S. I rj 1 <br />1/4 <br />BOTH ENDS OF C3 <br />C3 X <br />ROD & BOTH JOIST <br />1/4 HANGER ANGLES SUPPLY AIR DUCT <br />(REFER TO FLOOR RETURN SMOKE DETECTOR IN R/A <br />BOTH ENDS OF C3 &BOTH BOTTOM CHORD PLAN FOR EXACT SIZE) AIR DUCT AND S/A DUCTS <br />JOIST ANGLES OF ROOF JOIST <br />*LOADS MORE THAN 200 POUNDS BUT LESS THAN 400 POUNDS <br />NOT USED N.T.S. 4 EQUIPMENT SUPPORT FROM BAR JOIST* N.T.S. 3 ROOFTOP UNIT N.T.S. 2 NOTES N.T.S. 1 <br />Z <br />O <br />w <br />0 <br />LL <br />r <br />00 <br />V <br />to <br />(1) <br />04 <br />o <br />N <br />�- <br />N <br />0 <br />w <br />O <br />z <br />Y <br />Z <br />*k <br />Q <br />O <br />x <br />U <br />coo <br />to J <br />m LL <br />J. <br />J <br />Q J <br />=0 J <br />hdhm <br />ui <br />Ln a <br />W <br />L coo N <br />Lf) <br />(� <br />N <br />10 <br />�J <br />10 <br />a <br />Lo <br />a= <br />`o <br />0'E <br />N <br />ON <br />x <br />O <br />Q <br />oL <br />7 <br />O <br />Z <br />wLo-Q <br />J <br />N <br />N <br />LO <br />� <br />LO <br />u U) <br />N <br />cy) <br />a <br />Z <br />O <br />o_ <br />V00 <br />14, <br />` %%JuunI4p4���''i <br />A . N <br />Q�°°0000000 <br />�t \ C ENSF <br />°° <br />* o° No. 65765 0 <br />�0 STATE OF °�= <br />% �b . <br />SHEET NUMBER <br />M 4 <br />