HVAC - GENERAL NOTES: <br />O <br />ti <br />et <br />n <br />o <br />Q Go <br />1. <br />THIS CONTRACTOR SHALL FURNISH ALL LABOR, SUPERVISION, MATERIALS, EQUIPMENT, <br />29. <br />THE DRAWINGS ARE GENERALLY DIAGRAMMATIC AND, EXCEPT WHERE DIMENSIONS ARE <br />46. <br />REFRIGERANT PIPES SHALL BE TYPE K HARD DRAWN COPPER. INSULATE <br />TOOLS, ETC. REQUIRED FOR A COMPLETE SYSTEM OF HEATING, VENTILATING AND AIR <br />SHOWN, ARE NOT INTENDED TO SHOW THE EXACT LOCATION OF PIPES, DUCTWORK, <br />REFRIGERANT PIPE WITH 3/4" ARMAFLEX CLOSED CELL INSULATION ON <br />CONDITIONING AS DESIGNATED ON THE DRAWINGS, INCLUDING ALL NECESSARY PARTS, <br />OUTLETS, FIXTURES, OR EQUIPMENT. <br />THE SUCTION LINE AND 1/2" ARMAFLEX CLOSED CELL INSULATION ON <br />ACCESSORIES, ETC. REQUIRED BY STATE OR LOCAL CODES OR TO SATISFACTORILY <br />THE LIQUID LINE. <br />COMPLETE THE INSTALLATION. <br />30. <br />ANY OFFSETS IN DUCTWORK OR PIPING OR CHANGES IN LOCATION OF EQUIPMENT <br />REQUIRED OR NECESSARY TO AVOID INTERFERENCE WITH STRUCTURE OR WITH THE <br />47. <br />THE DIVISION-15 DESIGN PROFESSIONAL'S CONTRACT SERVICES DOES NOT <br />2. <br />UNLESS NOTED OTHERWISE ON THE DRAWINGS, ALL WORK SHOWN ON THE H.V.A.C. <br />WORK OF OTHER TRADES SHALL BE MADE BY THIS CONTRACTOR AT NO ADDITIONAL <br />INCLUDE CONSTRUCTION PHASE SERVICE, THE ARCHITECTURAL DESIGN <br />DRAWINGS SHALL BE FURNISHED AND INSTALLED BY THIS CONTRACTOR. <br />COST TO THE OWNER. <br />PROFESSIONAL AND/OR THE OWNER WILL PROVIDE THE CONSTRUCTION <br />PHASE SERVICES. THE DIVISION-15 CONTRACTOR SHALL BE AWARE THAT THE <br />3. <br />ALL WORK SHALL BE PURCHASED AND INSTALLED PER ALL APPLICABLE INDUSTRY <br />31. <br />REFER TO BUILDING AND STRUCTURAL DRAWINGS FOR ALL DIMENSIONS OF BUILDING <br />ARCHITECTURAL DESIGN PROFESSIONAL AND/OR THE OWNER ARE SOLELY <br />STANDARDS, & ALL APPLICABLE LOCAL, STATE, & NATIONAL CODES. <br />SPACES, <br />RESPONSIBLE FOR THE INTERPRETATIONS OF THE CONTRACT DOCUMENTS <br />AND OBSERVATIONS OF THE WORK OF DIVISION-15 CONTRACTORS DURING <br />4. <br />DUCTWORK SHALL BE GALVANIZED STEEL AND CONSTRUCTED PER APPLICABLE <br />32. <br />MATERIALS AND EQUIPMENT SHALL BE PROVIDED BY FIRMS REGULARLY ENGAGED IN <br />THE CONSTRUCTION PHASE OF THIS PROJECT. ANY DEVIATION FROM THE <br />SMACNA STANDARDS. KITCHEN HOOD AND EXHAUST DUCTWORK SHALL BE CARBON <br />IN THE MANUFACTURE OF MECHANICAL EQUIPMENT OF TYPES AND SIZES SPECIFIED <br />CONTRACT DOCUMENTS BY DIVISION-15 CONTRACTORS MUST BE <br />STEEL (0.054 INCH MIN. IN THICKNESS). FABRICATED AND INSTALLED IN <br />HEREIN WHOSE PRODUCTS HAVE BEEN IN SATISFACTORY USE IN SIMILAR SERVICE <br />AUTHORIZED AND APPROVED BY THE ARCHITECTURAL DESIGN <br />ACCORDANCE WITH NFPA 96, SBC AND JMC. DUCTWORK SIZES SHOWN ON <br />FOR NOT LESS THAN FIVE YEARS. <br />PROFESSIONAL AND/OR THE OWNER BEFORE THE DEVIATION CAN BE <br />DRAWINGS ARE INTERIOR DIMENSIONS. <br />INCORPORATED INTO THIS PROJECT. DIVISION-15 CONTRACTORS SHALL BE <br />33. <br />UNLESS SPECIFICALLY INDICATED OTHERWISE IN THESE SPECIFICATIONS OR ON THE <br />HELD LIABLE FOR ALL DEVIATIONS FROM THE CONTRACT DOCUMENTS, <br />5. <br />DUCTWORK LOCATED INSIDE OF BUILDING, EXCEPT HOOD EXHAUST DUCT, SHALL BE <br />DRAWINGS, ALL EQUIPMENT AND MATERIALS SHALL BE INSTALLED IN ACCORDANCE <br />RECORDED OR UNRECORDED, THAT HAVE NOT BEEN AUTHORIZED AND <br />INTERNALLY INSULATED. INSULATE ALL RECTANGULAR OUTSIDE AIR, SUPPLY AIR, AND <br />WITH THE BEST RECOMMENDATIONS OF THE MANUFACTURER OF THE EQUIPMENT. <br />APPROVED BY THE ARCHITECTURAL DESIGN PROFESSIONAL AND/OR THE <br />RETURN AIR DUCTWORK WITH 1.5" THICK, 2#/SQ, FT. DENSITY DUCT LINER EQUAL TO <br />AUXILIARY PIPING, ELECTRIC CONNECTIONS, ETC., RECOMMENDED BY THE <br />OWNER. <br />FIBERGLAS. ALL TRAVERSE DUCT JOINTS SHALL BE SEALED WITH MASTIC OR MASTIC PLUS <br />MANUFACTURER OR REQUIRED FOR PROPER OPERATION SHALL BE FURNISHED <br />TAPE. ROUND DUCT SHALL BE EXTERNALLY INSULATED WITH 2" THICK, 3#/SQ. FT. DENSITY <br />AND INSTALLED COMPLETE. A COPY OF THE MANUFACTURER'S INSTALLATION <br />48. <br />THE DRAWINGS ARE INTENDED AS DESIGN ONLY AND INDICATE THE <br />DUCT WRAP EQUAL TO FIBERGLAS TYPE FRK. HOOD EXHAUST DUCT SHALL BE EXTERNALLY <br />RECOMMENDATIONS SHALL BE KEPT IN THE JOB SUPERINTENDENT'S OFFICE <br />GENERAL SCOPE OF THE DIVISION-15 WORK CONTEMPLATED AND DO NOT <br />WRAPPED WITH FIREMASTER INSULATION (NOT OTHERWISE PROVIDED) AS REQUIRED, IN <br />AND SHALL BE AVAILABLE TO THE ENGINEER'S REPRESENTATIVE AT ALL TIMES. <br />CONSTITUTE SHOP DRAWINGS AND SHOULD NOT BE USED AS SUCH. DIVISION - <br />ORDER TO MEET ALL APPLICABLE CODES, <br />15 DRAWINGS ARE GENERALLY DIAGRAMMATIC AND, EXCEPT WHERE <br />34. <br />OPERATING MAINTENANCE AND SERVICE MANUALS: <br />DIMENSIONS ARE SHOWN, ARE NOT INTENDED TO SHOW THE EXACT <br />6. <br />THIS CONTRACTOR SHALL FURNISH AND INSTALL ALL STARTERS, DISCONNECTS, AND ALL <br />BEFORE COMPLETING WORK AND BEFORE REQUESTING FINAL PAYMENT, THIS <br />LOCATION OF PIPES, DUCTWORK, OUTLETS, FIXTURES, OR EQUIPMENT. <br />CONTROL DEVICES (NOT OTHERWISE PROVIDED) FOR ALL H.V.A.C. EQUIPMENT. ELECTRICAL <br />CONTRACTOR SHALL COMPILE AND DELIVER FOUR INDEXED, HARD COVER, <br />THE ARCHITECTURAL DESIGN PROFESSIONALS, THE OWNER AND THE <br />CONTRACTOR WILL FURNISH & INSTALL ALL POWER WIRING. THIS CONTRACTOR SHALL <br />THREE-RING BINDERS CONTAINING: <br />DIVISION-1EARCH 5 CONTRACTOR(S) ACKNOWLEDGE AND UNDERSTAND THAT THE <br />FURNISH & INSTALL ALL CONTROL WIRING. ALL WIRING SHALL BE INSTALLED IN CONDUIT. <br />I. NAMES, ADDRESSES, AND TELEPHONE NUMBERS OF THIS CONTRACTOR AND <br />CONTRACT DOCUMENTS FOR DIVISION-1ACKNOWLEDGE <br />WORK MAY CONTAIN ERRORS, <br />ALL EQUIPMENT SUPPLIERS, SYSTEMS INSTALLATION SUBCONTRACTORS, <br />OMISSIONS, INCONSISTENCIES, CONFLICTS, CODE VIOLATIONS AND IMPROPER <br />OMISSISI <br />7. <br />GENERAL CONTRACTOR WILL PROVIDE ALL REQUIRED OPENINGS IN FLOORS AND EXTERIOR <br />AND SERVICE COMPANIES. <br />USE MATERIALS. SUCH DEFICIENCIES WILL BE CORRECTED WHEN <br />WALLS FOR INSTALLATION OF H.V.A.C. EQUIPMENT, PIPING AND/OR DUCTWORK. <br />II. MECHANICAL INSTALLATION DRAWINGS (AS -BUILT) WITH ITEMS IDENTIFIED BY <br />IDENTIFIED. <br />NAME/MARK/NUMBER. <br />LL <br />THE DIVISION-15 CONTRACTOR(S) SHALL AGREE TO CAREFULLY STUDY THE <br />8. <br />CONDENSATE DRAIN PIPE SHALL BE SCH. 40 P.V.C. INSULATED WITH 1/2" ARMAFLEX, <br />III. MANUFACTURER'S DESCRIPTIVE LITERATURE, FINAL APPROVED SHOP DRAWINGS, <br />CONTRACT DOCUMENTS AND REPORT ONCE IN WRITING THE DIVISION - <br />OR EQUAL, INSULATION. MIN. SIZE SHALL BE 3/4". <br />PERFORMANCE DATA, CURVES, RATINGS, DIAGRAMS, SPARE PARTS AND <br />15 DESIGN PROFESSIONAL ANY DEFICIENCIES THE CONTRACTOR(S) MAY <br />REPLACEMENT PARTS LISTS, INSTALLATION AND OPERATING INSTRUCTIONS, <br />DISCOVER. THE DIVISION-15 CONTRACTOR(S) FURTHER AGREES TO REQUIRE <br />9. <br />UNOCCUPIED AMBIENT NOISE LEVEL FOR H.V.A.C. SYSTEM SHALL BE NO MORE THAN <br />MAINTENANCE AND SERVICE MANUALS FOR: <br />EACH SUBCONTRACTOR TO LIKEWISE STUDY THE DOCUMENTS AND REPORT <br />25 dB AS MEASURED ON AN "A" WEIGHTED SCALE. <br />A. EACH ITEM OF EQUIPMENT <br />AT ONCE ANY DEFICIENCIES DISCOVERED. THE DIVISION-15 CONTRACTOR(S) <br />B. VALVES AND SPECIALTIES <br />SHALL RESOLVE ALL REPORTED DEFICIENCIES WITH THE DIVISION-15 DESIGN <br />10. <br />PROVIDE THERMOSTAT - "HONEYWELL" VISION PRO -COMMERCIAL. FOR UNITS WITH ECONOMIZER - <br />C. CONTROLS <br />PROFESSIONAL PRIOR TO AWARDING ANY SUBCONTRACTS OR STARTING ANY <br />WHITE RODGERS G3272C. <br />D. SPECIAL ITEMS <br />WORK WITH THE CONTRACTOR'S OWN EMPLOYEES. IF DEFICIENCIES CANNOT <br />11. <br />COMPLY WITH LOCAL SEISMIC BRACING REQUIREMENTS FOR ALL HVAC EQUIPMENT. <br />IV. WHERE DIAGRAMS ARE TOO LARGE FOR THE BINDER, ARRANGE MANILA <br />BE RESOLVED BY THE DIVISION-15 DESIGN PROFESSIONAL AND THE <br />ALL SEISMIC BRACING DEVICES SHALL BE SUBMITTED TO THE STRUCTURAL ENGINEER <br />POCKETS WITH REINFORCED HOLES TO HOLD FOLDED DRAWINGS. <br />STEP <br />V. STEP PROCEDURES FOR STARTING AND STOPPING THE SYSTEMS, <br />CONTRACTOR(S) WITHOUT ADDITIONAL TIME OR ADDITIONAL EXPENSE, THE <br />FOR REVIEW. THE SHOP DRAWINGS SHALL BEAR THE SEAL OF A LICENSED <br />NORRMM AL OPERATION AND MAINTENANCE INSTRUCTIONS. <br />DIVISION-15 DESIGN PROFESSIONAL AND THE CONTRACTOR SHALL SO <br />PROFESSIONAL ENGINEER WITH MIN. FIVE YEARS EXPERIENCE IN THE DESIGN <br />INFORM THE OWNER AND/OR THE ARCHITECTURAL DESIGN PROFESSIONAL IN <br />OF SEISMIC BRACING SYSTEMS. ALL SEISMIC RESTRAINTS SHALL BE IN ACCORDANCE <br />35. <br />THIS CONTRACTOR SHALL DESIGNATE AND MAINTAIN A COMPLETE UP-TO-DATE SET <br />WRITING. ANY WORK THAT IS PERFORMED RELATED TO THE DEFICIENCIES <br />WITH ALL APPLICABLE BUILDING CODES. <br />OF CONTRACT DRAWINGS, PRINTS, AND SPECIFICATIONS FOR RECORDING CHANGES <br />PRIOR TO RECEIPT OF INSTRUCTIONS FROM THE DIVISION-15 DESIGN <br />MADE TO THE DRAWINGS AND SPECIFICATIONS DURING THE CONSTRUCTION PHASE OF <br />PROFESSIONAL, THE OWNER OR ARCHITECTURAL DESIGN PROFESSIONAL WILL <br />12. <br />INSTALL H.V.A.C. EQUIPMENT AS NOTED ON THE DRAWINGS. PROVIDE ACCESS TO <br />THIS PROJECT. THESE DRAWINGS SHALL BE AVAILABLE AT THE JOB SITE FOR <br />BE DONE AT THE CONTRACTOR'S RISK. <br />EQUIPMENT PER CODE REQUIREMENTS. <br />REVIEW BY THE ENGINEER, ARCHITECT, AND THE OWNER. DRAWINGS SHALL BE <br />REFER BUILDING AND STRUCTURAL DRAWINGS FOR DIMENSIONS OF <br />MAINTAINED IN A NEAT CONDITION AND SHALL CLEARLY SHOW ANY CHANGES FROM <br />BUILDING SPACES. <br />13. <br />AIR DISTRIBUTION SHALL BE TITUS, OR OTHER APPROVED EQUAL. PROVIDE OPPOSED <br />ORIGINAL CONTRACT DRAWINGS AND SPECIFICATIONS. <br />BLADE DAMPERS WHERE INDICATED. ALL ALUMINUM CONSTRUCTION. <br />49. <br />RESTROOM FACILITIES SHALL BE VENTILATED AS INDICATED ON THE DRAWINGS, <br />36. <br />THIS CONTRACTOR SHALL PREPARE, UPON COMPLETION OF THE PROJECT, FINAL <br />& PER CODE. <br />14. <br />CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK FITTING INTO PLACE IN A <br />RECORD DRAWINGS ON REPRODUCIBLE DRAFTING MEDIA TO THE SAME SCALE AS THE <br />SATISFACTORY AND NEAT WORKMANLIKE MANNER IN EVERY PARTICULAR TO THE <br />CONTRACT DRAWINGS SHOWING THE CHANGES MADE TO THE DRAWINGS DURING THE <br />50. <br />COMPLIANCE WITH ALL APPLICABLE LOCAL, STATE, AND NATIONAL CODES IS <br />APPROVAL OF THE ENGINEER. PAINT EXPOSED DUCTWORK PER ARCHITECT. <br />CONSTRUCTION PHASE OF THIS PROJECT, AND THE DRAWINGS SHALL SHOW EXACT <br />SPECIFICALLY REQUIRED. <br />INSTALLED LOCATIONS AND SIZES OF ALL PIPING, DUCTWORK AND EQUIPMENT <br />15. <br />CONTRACTOR SHALL CONFER WITH ALL OTHER CONTRACTORS REGARDING THE <br />INSTALLED BY THIS CONTRACTOR. ALL UNDERGROUND WORK SHALL BE DIMENSIONED <br />51. <br />FRYER HOOD SUPPRESSION SYSTEM <br />LOCATION AND SIZE OF PIPES, EQUIPMENT, FIXTURES, CONDUIT, DUCTS, OPENINGS, <br />FROM A REFERENCE SUCH AS A WALL OR COLUMN CENTER LINE. MARKED UP <br />SWITCHES, OUTLETS, ETC., IN ORDER THAT THERE MAY BE NO INTERFERENCE <br />PRINTS OF CONTRACT DRAWINGS WILL NOT BE ACCEPTED AS FINAL RECORD <br />MANUFACTURERS: ANSUL, KIDDE, OR APPROVED EQUAL, <br />BETWEEN THE INSTALLATION OR THE PROGRESS OF THE WORK OF ANY CONTRACTOR <br />DRAWINGS. <br />ON THE PROJECT. <br />FEATURES: WET CHEMICAL FIRE EXTINGUISHING SYSTEM INCLUDING <br />16. <br />THE OWNER MAY CHANGE THE LOCATION OF ANY EQUIPMENT FIVE FEET AND ANY <br />37. <br />IT IS TO BE CLEARLY UNDERSTOOD THAT THE SYSTEMS INCLUDED UNDER THIS <br />DETECTORS, CONTROL HEADS, PRESSURE CYLINDERS, PULL STATIONS, MAIN <br />GAS SHUT-OFF VALVE AND NOZZLES TO PROVIDE A COMPLETE AUTOMATIC <br />PIPING, DUCTWORK, CONDUIT, ETC., TEN FEET IN ANY DIRECTION WITHOUT EXTRA <br />DIVISION OF THE SPECIFICATIONS WILL NOT BE ACCEPTED UNTIL ALL ACCEPTANCE <br />TESTS HAVE BEEN MADE, FINAL TESTING AND BALANCING WORK IS COMPLETE, AND <br />FIRE EXTINGUISHING SYSTEM IN CONFORMANCE WITH N.F.P.A. 96 AND U.L. <br />CHARGE, PROVIDED SUCH CHANGES ARE MADE PRIOR TO INSTALLATION OF <br />THE INSTALLATION IS OPERATING PROPERLY. <br />300. CONCEAL ALL PIPING EXCEPT THAT WHICH HAS BEEN SPECIFICALLY <br />MECHANICAL EQUIPMENT. <br />APPROVED BY THE OWNER'S INSPECTOR. <br />17. <br />ALL REFERENCES TO CONTRACTORS IN SPECIFICATIONS AND DRAWINGS SHALL REFER <br />38. <br />AFTER COMPLETION OF ALL WORK AND TESTS AND AT SUCH TIME AS DESIGNATED BY <br />TO THE RESPECTIVE TRADE CONTRACTOR PERFORMING THAT PORTION OF THE WORK. <br />THE ENGINEER, THIS CONTRACTOR SHALL PROVIDE NECESSARY SKILLED PERSONNEL <br />SYSTEM SHALL BE PROVIDED BY THE CONTRACTOR. THE CONTRACTOR <br />TO OPERATE THE ENTIRE INSTALLATION FOR A PERIOD OF ONE DAY OF EIGHT (8) <br />SHALL BE RESPONSIBLE FOR SUBMITTAL OF EXTINGUISHING SYSTEM FOR <br />18. <br />SHOULD THERE BE ANY DISCREPANCIES OR A QUESTION OF INTENT, REFER THE <br />HOURS. DURING THIS TIME, THIS CONTRACTOR SHALL FULLY INSTRUCT THE OWNER'S <br />APPROVAL BY LOCAL AUTHORITIES. <br />MATTER TO THE ENGINEER FOR A DECISION BEFORE ORDERING ANY EQUIPMENT OR <br />REPRESENTATIVES IN THE COMPLETE OPERATION, ADJUSTMENT, AND MAINTENANCE <br />MATERIALS, OR BEFORE STARTING ANY RELATED WORK. <br />OF THE EQUIPMENT AND SYSTEMS. <br />FIRE SUPPRESSION SYSTEM SHALL BE INSTALLED TO PROTECT THE <br />EXHAUST DUCT AND FRYER HOOD FOR THE DOUBLE GAS FRYER. INSTALL <br />19. <br />WHERE WORK CONNECTS TO THAT OF ANOTHER TRADE OR TO PIPING OR EQUIPMENT <br />39. <br />THIS CONTRACTOR SHALL GUARANTEE ALL WORK DONE BY HIM AGAINST DEFECTS IN <br />GAS SOLENOID SHUT-OFF VALVE IN GAS LINE SERVING THE APPLIANCE <br />IN PLACE, FIELD MEASUREMENTS SHALL BE MADE TO MAKE CONNECTING WORK COME <br />MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE YEAR AFTER DATE OF <br />BEING SERVED BY THE FRYER HOOD. VALVE SHALL SHUT-OFF GAS AND <br />TRUE AND LINE UP WITH THE ITEM BEING CONNECTED. <br />ACCEPTANCE BY THE OWNER. THIS GUARANTEE SHALL BE PRESENTED TO THE <br />ELECTRICAL TO THE APPLIANCE WHEN SUPPRESSION SYSTEM IS ACTIVATED. <br />OWNER IN WRITING AND ANY AND ALL DEFECTS DEVELOPING WITHIN THIS STATED <br />20. <br />MINOR ITEMS AND ACCESSORIES OR DEVICES REASONABLY INFERRED AS NECESSARY <br />PERIOD SHALL BE REMEDIED TO THE FULL SATISFACTION OF THE OWNER BY THIS <br />TO THE COMPLETE AND PROPER INSTALLATION AND OPERATION OF ANY SYSTEM <br />CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER. <br />SHALL BE PROVIDED BY THE CONTRACTOR FOR SUCH SYSTEM, WHETHER OR NOT <br />THEY ARE SPECIFICALLY CALLED FOR BY THE SPECIFICATIONS OR DRAWINGS. <br />40. <br />THE ONE-YEAR GUARANTEE FOR ITEMS OF EQUIPMENT THAT THE OWNER ELECTS TO <br />BEGIN USING FOR HIS BENEFIT BEFORE THE COMPLETION OF THE ENTIRE PROJECT <br />21. <br />CAREFULLY CHECK AND COORDINATE THE LOCATION AND LEVEL OF ALL PIPES, <br />SHALL BEGIN AT THE DATE OF "BENEFICIAL USE" BY THE OWNER. THIS DATE OF <br />DUCTS, ETC. RUN PRELIMINARY LEVELS AND CHECK WITH ALL OTHER CONTRACTORS <br />"BENEFICIAL USE" SHALL BE ESTABLISHED JOINTLY BY THE ENGINEER, ARCHITECT, <br />SO THAT CONFLICTS IN ALL LOCATIONS MAY BE AVOIDED. <br />THIS CONTRACTOR, AND THE OWNER. THIS CONTRACTOR SHALL PREPARE A LETTER <br />STATING THAT THE OWNER HAS REQUESTED "BENEFICIAL USE". THIS LETTER SHALL <br />22. <br />ALL MATERIALS SHALL BE NEW AND OF THE QUALITY SPECIFIED. APPARATUS AND <br />BE SIGNED BY THE OWNER, THIS CONTRACTOR, AND THE ARCHITECT. <br />MATERIALS USED IN THIS WORK WHICH ARE SUBJECT TO APPROVAL BY <br />UNDERWRITERS (UL) SHALL BEAR THE UNDERWRITERS LABEL OF APPROVAL. <br />41. <br />THE OWNER, IN ORDER TO MAINTAIN THE INDOOR AIR QUALITY FOR THIS FACILITY IN <br />COMPLIANCE WITH BUILDING CODES, SHOULD PROVIDE A CONTINUING MAINTENANCE <br />23. <br />MANUFACTURER'S TRADE NAMES OR CATALOG NUMBERS USED IN THESE <br />PROGRAM FOR THE HEATING, VENTILATING AND AIR CONDITIONING (H.V.A.C.) SYSTEMS. <br />SPECIFICATIONS AND INDICATED ON THE DRAWINGS ARE NOT TO BE CONSIDERED AS <br />THE H.V.A.C. SYSTEMS FOR THIS FACILITY WERE DESIGNED TO MEET OR EXCEED THE <br />PROPRIETARY. THEIR PURPOSE IS TO DENOTE TYPE, SIZE, QUALITY, AND DESIGN OF <br />INDOOR AIR QUALITY REQUIREMENTS OF ASHRAE 62-1989. <br />EQUIPMENT. <br />42. <br />SHOULD SPACE USAGE OR OCCUPANCY CHANGE IN THE FUTURE, IT IS THE OWNER'S <br />24, <br />WHERE EQUIPMENT IS SPECIFIED AS "OR EQUAL", IT SHALL MEAN EQUAL AS <br />RESPONSIBILITY TO MAINTAIN COMPLIANCE WITH APPLICABLE VENTILATION AND/OR <br />APPROVED BY THE ENGINEER. <br />INDOOR AIR QUALITY STANDARDS. <br />25. <br />THE CONTRACTOR IS FREE TO OFFER FOR CONSIDERATION SUBSTITUTE ITEMS OF <br />43. <br />GAS PIPE SHALL BE SCHEDULE 40 BLACK STEEL. UNDERGROUND GAS PIPE SHALL <br />EQUIVALENT TYPE, SIZE, QUALITY, AND PERFORMANCE AFTER THE CONTRACT IS <br />BE COATED AND WRAPPED. PROVIDE CATHODIC PROTECTION AS REQUIRED. GAS PIPE <br />SIGNED; HOWEVER, HE SHALL BE PREPARED TO FURNISH SPECIFIED MATERIALS AND <br />IN CONCEALED SPACES, REGARDLESS OF PRESSURE SHALL BE WELDED. ALL PIPE <br />EQUIPMENT WHERE SUBSTITUTIONS ARE REJECTED ON HIS ORIGINAL SUBMITTAL. <br />EXPOSED TO PRESSURE ABOVE 1 PSI SHALL BE WELDED. <br />26. <br />SHOULD ANY PART OF THE PLANS OR SPECIFICATIONS BE FOUND TO BE IN <br />CONFLICT WITH APPLICABLE CODES OR ORDINANCES, THIS CONTRACTOR SHALL NOTIFY <br />44 <br />REFERENCE PROJECT SUMMARY ON SHEET T1 (TITLE SHEET) FOR ALL APPLICABLE CODES. <br />THE ENGINEER PRIOR TO SUBMITTING HIS BID. <br />45. <br />MOUNT SMOKE DETECTORS IN SUPPLY AIR AND RETURN AIR DUCTWORK TO SHUT <br />27. <br />THIS CONTRACTOR SHALL MAKE APPLICATION TO THE LOCAL BUILDING CODE <br />DOWN FANS IN AIR CONDITIONING EQUIPMENT UNITS UPON DETECTION OF SMOKE. <br />ENFORCEMENT OFFICIALS TO OBTAIN ALL INSPECTION PERMITS REQUIRED, AND SHALL <br />DETECTORS SHALL BE IONIZATION TYPE. DETECTOR IN RETURN AIR DUCT SHALL BE <br />PAY ALL NECESSARY FEES FOR SAME. HE SHALL, AT THE CONCLUSION OF THE <br />MOUNTED UPSTREAM FROM OUTSIDE CONNECTION. HVAC CONTRACTOR SHALL MOUNT <br />INSTALLATION, SECURE A CERTIFICATE OF INSPECTION, PROPERLY SIGNED BY THE <br />THE SMOKE DETECTORS IN THE DUCTWORK. THE ELECTRIC CONTRACTOR SHALL <br />CONTROLLING BUILDING CODE ENFORCEMENT DEPARTMENT, WHICH SHALL STATE THAT <br />WIRE THE DETECTORS AS REQUIRED. <br />ALL RULES HAVE BEEN COMPLIED WITH AND THAT THE WORK IS SATISFACTORY. AT <br />PROJECT COMPLETION, THIS CONTRACTOR SHALL SUBMIT CERTIFICATE OF INSPECTION <br />FOR DELIVERY TO THE OWNER. <br />28. <br />THE DRAWINGS FOR THE WORK UNDER THIS DIVISION OF THE SPECIFICATIONS ARE <br />INTENDED AS DESIGN ONLY, AND THEY INDICATE THE REQUIRED GENERAL SCOPE OF <br />THE WORK. THEY ARE NOT SHOP DRAWINGS, AND SHOULD NOT BE USED AS SUCH. <br />O <br />z <br />Y <br />z <br />Q* <br />Q O <br />a <br />x <br />U <br />J <br />W <br />Z W <br />W �_ <br />C� p <br />Z <br />0013 <br />(0 J <br />m U. <br />J <br />I- an ca <br />V J <br />L <br />L9>- <br />= <br />ui a <br />W <br />Ln <br />V <br />U) <br />FA <br />J10 <br />d� <br />c <br />L0 <br />3 <br />se <br />L0 <br />N <br />E <br />0 <br />m <br />N <br />o <br />cK <br />Q <br />cK <br />2 <br />7t: <br />Z <br />- <br />a <br />Lr) <br />� <br />W <br />N <br />a <br />�LO <br />M <br />LO <br />a` <br />N <br />0, <br />Z <br />4O� <br />0 <br />w <br />Oro``' A/� �'''''•. <br />�I �pP 000000000 F ., <br />►` - 000° �� C E NSA°, o00pp� � <br />�k o° 00 <br />No. 65765 000 <br />00 * o° <br />o STATE OF a <br />0v �00� 4DR Iq� � � <br />SHEET NUMBER <br />z N M5 <br />0 <br />W <br />ix <br />