MINIMUM CODE REQUIRED OUTSIDE AIR VENTILATION RATES PER A 62R1 E20STOANDARD AzR EZ zRDzRD =Voz
<br />NET
<br />AREA
<br />CODE
<br />REQ D
<br />NUMBER
<br />PEOPLE
<br />CODE
<br />REQ D OA
<br />CODE
<br />REQ D OA
<br />ZONE AIR
<br />DISTRIBUTION
<br />TOTAL OA
<br />DEFAULT
<br />OCCUPANT
<br />AREA
<br />OUTDOOR
<br />AIR RATE
<br />BASED ON
<br />PEOPLE
<br />OUTDOOR
<br />AIR RATE
<br />BASED ON
<br />TOTAL
<br />EFFECTIVENESS
<br />REQUIRED
<br />BY
<br />DENSITY
<br />FLOOR
<br />PEOPLE
<br />VBz
<br />CODE
<br />OD
<br />AREA
<br />Az
<br />Ra
<br />Pz
<br />Rp
<br />AzRa+PzRp
<br />Ez
<br />Voz
<br />AREA -SERVED
<br />CATEGO YY
<br />P/1000 SF
<br />SF
<br />CFM/S.F.
<br />CFM
<br />PERSON(S)
<br />CFM/PERS
<br />CFM
<br />CFM
<br />CFM
<br />RETAIL
<br />SALES
<br />15
<br />10000
<br />0.12
<br />1200
<br />+
<br />80
<br />7.5
<br />375
<br />1575
<br />/
<br />0.8
<br />=
<br />1968
<br />RECEIVING
<br />STORAGE
<br />-
<br />1700
<br />0.12
<br />192
<br />+
<br />-
<br />-
<br />-
<br />192
<br />0.8
<br />=
<br />218
<br />TOTAL REQUIRED
<br />=
<br />2186
<br />TOTAL PROVIDED
<br />=
<br />2200
<br />IMPORTANT NOTES FOR CONTRACTOR AND SUBCONTRACTOR:
<br />ANY DISCREPANCIES OR OMISSIONS ON THESE DOCUMENTS MUST BE
<br />BROUGHT TO THE ATTENTION OF THE ARCHITECT PRIOR TO THE
<br />COMMENCEMENT OF CONSTRUCTION AND BID TO OWNER. FAILURE BY
<br />CONTRACTOR TO IDENTIFY DISCREPANCIES OR OMISSIONS WILL THEN
<br />BECOME THE RESPONSIBILITY OF THE CONTRACTOR.
<br />TENANT'S CONTRACTOR IS RESPONSIBLE FOR COMPLIANCE WITH
<br />ALL REQUIREMENTS WITHIN THE LANDLORD'S TENANT CRITERIA
<br />MANUAL, RULES AND REGULATIONS.
<br />MECHANICAL NOTE:
<br />COORDINATE EXACT LOCATION OF RTUS WITH STRUCTURAL AND
<br />ARCHITECT DWGS. SUPPLY AND RETURN DUCT MUST RUN THROUGH
<br />OPEN WEBBING OF ROOF TRUSSES. COORDINATE LOCATION OF
<br />DUCTWORK WITH ROOF TRUSSES INSTALLED (TYPICAL).
<br />REQUIRED 10'-0" MINIMUM SEPARATION BETWEEN EXHAUST AND,
<br />AIR -INTAKES. ALSO KEEP IN CONSIDERATION ADJACENT TENANT
<br />EQUIPMENT.
<br />FAN SCHEDULE
<br />TAG
<br />-
<br />EF-1
<br />EF-2 & 3
<br />SERVICE
<br />-
<br />EXHAUST
<br />EXHAUST
<br />AIR QUANTITY
<br />CFM
<br />75
<br />280
<br />EXT. STATIC PRESS.
<br />IN. H2O
<br />0.225
<br />0.225
<br />FAN TYPE
<br />-
<br />CEILING
<br />CEILING
<br />DRIVE
<br />-
<br />DIRECT
<br />DIRECT
<br />SONES
<br />-
<br />1.0
<br />4.0
<br />MOTOR
<br />CFM/WATTS
<br />30.2 WATTS
<br />99.4 WATTS
<br />FAN SPEED
<br />RPM
<br />900
<br />1500
<br />POWER
<br />V/0
<br />115V/1 of
<br />115V/10
<br />CONTROL
<br />-
<br />W/LIGHT SWITCH
<br />W/LIGHT SWITCH
<br />LOCATION
<br />-
<br />CEILING
<br />CEILING
<br />MANUFACTURER
<br />-
<br />COOK
<br />COOK
<br />MODEL
<br />-
<br />GC-146
<br />GC-422
<br />NOTES
<br />®
<br />01
<br />1
<br />01 VIBRATION ISOLATORS, BACKDRAFT DAMPER, HANGING
<br />KIT, FAN SPEED CONTROLLER, PLUG DISCONNECT.
<br />RTU-1 THRU 5:
<br />UNIT SHALL BE CONTROLLED BY ITS ELECTRONIC 7-DAY PROGRAMMABLE T-STAT. UNIT SUPPLY FAN SHALL RUN
<br />CONTINUOUSLY IN THE OCCUPIED MODE, CYCLE WITH HEATING AND COOLING WHILE UNOCCUPIED. UPON A RISE IN SPACE
<br />TEMPERATURE, UNIT COMPRESSOR AND CONDENSER FANS SHALL ACTIVATE IN STAGE TO SATISFY SPACE. UPON A DROP
<br />IN SPACE TEMPERATURE, ELECTRIC HEAT SHALL BE ACTIVATED IN STAGE TO SATISFY SPACE TEMPERATURE. OCCUPANCY
<br />SCHEDULE SHALL BE SET OCCUPIED/UNOCCUPIED BASED ON TENANT SPECIFIC REQUIREMENTS. THERMOSTAT SHALL BE
<br />SET FOR OCCUPIED COOLING 75 , OCCUPIED HEATING 70 ; UNOCCUPIED COOLING 80 ; UNOCCUPIED HEATING 60'. ALL TIME
<br />AND TEMPERATURE SETPOINTS SHALL BE VERIFY BY LANDLORD AND TENANT PRIOR TO PROGRAMMING. THERMOSTAT
<br />SHALL BE PROGRAMMED BY MECHANICAL CONTRACTOR IN THE PRESENCE OF TENANT'S REPRESENTATIVE.
<br />MAX. 20'
<br />TRANSITION
<br />SECURE WITH TWO 1
<br />#8 S/S SCREWS
<br />MIRO PIPE SUPPORTS
<br />RIGID POLYCARBONATE RESIN
<br />ROOFING
<br />AINUM STRAP
<br />CRADLE
<br />PROVIDE TREAD PIECE
<br />UNDER SUPPORT
<br />ROOF INSULATION METAL ROOF DECK
<br />ROOF PIPE SUPPORT DETAIL
<br />NO SCALE
<br />NOTES: 1) NO WOOD ALLOWED
<br />2) SPACING FOR PVC PIPE - 5'-0-
<br />SPACING FOR STEEL PIPE = 10'-0-
<br />LEVEL
<br />E::3--HDENTIFICATION G WITH UNIT ROOF MOUNTED
<br />NUMBER AND A EA SERVED PACKAGE A/C UNIT
<br />0.25 D (e MIN. PER SMACNA)
<br />RECTANGULAR DUCT
<br />N
<br />N
<br />VOLUME DAMPER
<br />TTING WITH LOCKING TYPE VOLUME DAMPER.
<br />ALL TAKEOFF EQUAL TO FLEXMASTER STO.
<br />DUCT OR ROUND SHEET METAL DUCT. FLEX
<br />MAX. 8'-0- LONG, USE CLAMP TO ATTACH
<br />DUCTS AND SEAL SUPPORT
<br />EVERY FOUR FEET FROM STRUCTURE
<br />BRANCH DUCT DETAILS
<br />NO SCALE
<br />U JOIST (TYP.)
<br />NOTE: INSULATE ALL COLLARS. SEAL TO
<br />PLENUM AND FLEX INSULATION
<br />DUCT RISER/LEVELING DETAIL
<br />NOT TO SCALE
<br />**I/4- LAG BOLTS THRU UNIT FRAME
<br />AND CURB. 6. ON CENTER. AVOID
<br />DRILLING COIL AREA. APPLIES TO ALL
<br />SIDES.
<br />MINIMUM 8- CLEARANCE REQUIRED
<br />BETWEEN BOTTOM OF EQUIPMENT AND
<br />TOP OF FINISHED ROOF. ADD SHIMS AS
<br />REQUIRED.
<br />FLASHING & COUNTER
<br />FLASHING. SEE ARCH. D
<br />P.T. W.D. NAILER
<br />ROOF INSULATION
<br />ROOF STRUCTURE
<br />FROM
<br />DUCT N
<br />TO DROP DIFFUSER
<br />EXIBLE CANVAS
<br />VECTION (TYP.)
<br />AIR DEVICE SCHEDULE
<br />MARK
<br />TYPE
<br />MATERIAL
<br />FINISH
<br />ACCESSORIES
<br />MANUFACTURER
<br />AND MODEL
<br />REMARKS
<br />CD
<br />CEILING
<br />DIFFUSER
<br />ALUMINUM
<br />BAK. WHT.
<br />ENAMEL
<br />OBD
<br />PRICE
<br />SCD
<br />RRC
<br />RETURN
<br />REGISTER
<br />ALUMINUM
<br />BAK. WHT.
<br />ENAMEL
<br />OBD
<br />PRICE
<br />630FL
<br />'
<br />TGC
<br />TRANSFER
<br />GRILLE
<br />ALUMINUM
<br />BAK. WHT.
<br />ENAMEL
<br />PRICE
<br />630FL
<br />'
<br />SRC
<br />SUPPLY
<br />REGISTER
<br />ALUMINUM
<br />BAK. WHT.
<br />ENAMEL
<br />OBD
<br />PRICE
<br />620FS
<br />RTU UNIT SCHEDULE
<br />MARK
<br />-
<br />(N)RTU-2
<br />N)RTU-3 & 5
<br />SUPPLY AIR
<br />CFM
<br />1,750
<br />4,750
<br />OUTSIDE AIR
<br />CFM
<br />350
<br />925
<br />EXT. STATIC PRESSURE
<br />IN. H2O
<br />0.5
<br />0.8
<br />FAN SPEED
<br />RPM
<br />1350
<br />1096
<br />MOTOR
<br />HP
<br />1
<br />3.8
<br />POWER
<br />VOLTS/PH.
<br />208V/30
<br />208V/30
<br />MCA
<br />AMPS
<br />45
<br />100
<br />MOCP
<br />AMPS
<br />45
<br />100
<br />FILTER TYPE
<br />-
<br />2"-30%
<br />2"-30%
<br />TOTAL COOLING CAPACITY
<br />BTUH
<br />58,300
<br />142,000
<br />SENSIBLE COOLING CAPACITY
<br />BTUH
<br />52,784
<br />131,438
<br />ENT. AIR TEMP.
<br />'F/E
<br />79.4/66.7
<br />79.1 /66.2
<br />LVG. AIR TEMP
<br />E/'F
<br />57/56.1
<br />57.3/56.2
<br />HEATING CAPACITY
<br />KW
<br />15.0
<br />30.0
<br />EER
<br />BTU/WATT
<br />14 SEER
<br />11.0
<br />AMBIENT TEMP.
<br />'F
<br />95
<br />95
<br />UNIT WEIGHT(TOTAL)
<br />LBS.
<br />688
<br />1224
<br />MANUFACTURER
<br />-
<br />LENNOX
<br />LENNOX
<br />MODEL NO.
<br />-
<br />ZCB060S4B
<br />ZCA150S4M
<br />NOTES
<br />®
<br />01
<br />(
<br />01 ELECTRIC COOLING/ CTR NG ,OFTOP UNIT WITH 18" ROOF CURB, SINGLE POINT POWER
<br />CONNECTION, PROVI OKE DETECTO IN SUPPLY AIR DUCT, WINTER START UP, W.P.
<br />DISCONNECT BY ELNS
<br />L DIVI AIL GUARD, RAIN HOOD, 7 DAY PROGRAMMABLE T-STAT
<br />WITH CLEAR LOCKABLE BOX, ECONOMIZER, ENTHALPY SENSOR, FIELD INSTALLED DRAIN PAN
<br />OVERFLOW SWITCH, CORROSION RESISTANT BIRD SCREENS. COORDINATE WITH TENANT PRIOR TO
<br />PURCHASING. DISCONNECT BY ELECTRICAL DIVISION.
<br />PROVIDE PLUG FOR MAINTENANCE
<br />CONDENSATE
<br />HORIZONTAL AIR SCOOP MAX. TONS PIPE SIZE
<br />2 3/4"
<br />5 1"
<br />ROUND SUPPLY AIR DUCT. CONNECT 30 1 1/4-
<br />BRANCH TO SUPPLY AIR DUCT DROP, 50 1 1/2"
<br />ABOVE CONCENTRIC DIFFUSER.
<br />tk
<br />VOLUME DAMPER
<br />UCT DROP (FLEXIBLE
<br />OT ALLOWED)
<br />NOTE:
<br />INSTALL HORIZONTAL AIR SCOOP HAVING A CONTINUOUSLY CURVED
<br />CROSS SECTION AND BALANCING DAMPER AT DUCT CONNECTION TO
<br />DIVERT SUPPLY AIR INTO THE CONNECTED DUCTWORK. LENGTH OF SCOOP
<br />SHALL BE LIMITED TO THE WIDTH OF THE SUPPLY AIR ANNULAR SPACE.
<br />TYPICAL SUPPLY BRANCH
<br />CONNECTION DETAIL
<br />EDGE OF ROOF TOP UNIT,
<br />ROOF CAP OR FAN.
<br />FAN MAIN FRAME
<br />-GASKET BETWEEN UNIT AND
<br />FULL PERIMETER OF CURB
<br />SEALANT AT ALL SCREW
<br />PENETRATIONS BY HVAC
<br />TREATED WOOD NAILER
<br />18- FABRICATED, MIN 14GA. CURB BY HVAC
<br />INSTALLED BY GENERAL CONTRACTOR SHIM
<br />AS REQUIRED TO LEVEL UNIT.
<br />INSULATION
<br />SPACER BLOCK, BETWEEN —
<br />CURB de DECK IF REQUIRED
<br />FOR LEVELING
<br />--DUCT ROOF OPENING AS
<br />REQUIRED FOR DUCTWORK
<br />+•'1/rO BOLTS, NUTS, A
<br />AND
<br />SUPPORT FRAMING, SEE
<br />STRUCTURAL SHEETS FOR
<br />WASHERS ON 6- CENTERS.
<br />ADDITIONAL INFORMATION.
<br />APPLIES TO ALL SIDES
<br />"REINFORCING SHOWN IS FOR
<br />170-MPH WAND LOAD DESIGN.
<br />ROOF CURB DETAIL
<br />NOT TO SCALE
<br />OUTSIDE AIR
<br />INTAKE
<br />INSULATED
<br />SUPPLY TRANSITION
<br />ROOF JOIST
<br />PROVIDE CLEANOUT AT EACH CHANGE
<br />OF DIRECTION OR EVERY 30'
<br />DRAIN LINE. SLOPE WITH FLOW
<br />A 1/8-/FT TO DRAIN OR OUTSIDE
<br />A
<br />NO SCALE
<br />ROOF TOP UNIT
<br />INSULATED PANELS
<br />(TYP.)
<br />I
<br />I 1
<br />I I
<br />I I
<br />I I
<br />I I
<br />I I
<br />I I
<br />I I
<br />I I
<br />A = FAN PRESSURE + 1 INCH
<br />DRAW THRU APPLICA
<br />INSULATED
<br />RETURN TRANSITION
<br />—ROOF CURB
<br />DIFFUSER EVEN WITH
<br />BOTTOM OF TRUSS
<br />ALUMINUM CONCENTRIC DIFFUSER
<br />BY PLENUMS INCORPORATED
<br />RTU AND CONCENTRIC AIR DIFFUSER DETAIL
<br />NO SCALE
<br />NOTES:
<br />OSUPPLY/ RETURN TRANSITION PACKAGE AND ROOF CURB SHALL BE PROVIDED BY THE CONTRACTOR
<br />AND ASSEMBLED IN THE FIELD. FIELD FABRICATED TRANSITIONS WILL NOT BE ACCEPTED.
<br />02 CURB AND CONCENTRIC DUCT KIT MUST BE INSTALLED PRIOR TO SETTING RTU IN PLACE. ALIGN RTU
<br />SUPPLY OPENING WITH TO MATCH SUPPLY OPENING IN CONCENTRIC DUCT.
<br />03 FIELD BAFFLES MAY BE REQUIRED FOR BALANCING.
<br />04 SUPPLY AND RETURN DUCT SHALL BE INTERNALLY LINED. RETURN DUCT SHALL BE MOUNTED WITHIN
<br />THE JOIST SPACE.
<br />MECHANICAL GENERAL NOTES:
<br />• IN GENERAL, PLANS AND DIAGRAMS ARE SCHEMATIC ONLY AND SHOULD NOT BE
<br />SCALED.
<br />• INTENT OF THESE NOTES AND MECHANICAL NOTES ON DRAWINGS IS TO CLARIFY THE
<br />SCOPE OF WORK AND ALERT CONTRACTOR OF EXISTING CONDITIONS. CONTRACTOR TO
<br />VISIT SITE AND VERIFY ALL CLEARANCES BEFORE FABRICATION OF DUCTWORK AND
<br />PROVIDE ADDITIONAL OFFSET AND/OR CHANGES IN DUCT SIZES TO MEET FIELD
<br />CONDITIONS AND COORDINATE WITH ELECTRICAL, PLUMBING AND FIRE PROTECTION
<br />SUBCONTRACTOR BEFORE ANY CONSTRUCTION WORK.
<br />• COORDINATE AIR DEVICE LOCATIONS WITH LIGHTING FIXTURES AND FIRE SPRINKLER
<br />HEADS.
<br />• DUCT DIMENSIONS SHOWN ON DRAWINGS ARE CLEAR INSIDE DIMENSIONS.
<br />• ALL SUPPLY AND RETURN DUCTWORK SHALL BE EXTERNALLY INSULATED SHEET METAL
<br />CONSTRUCTION IN ACCORDANCE WITH LATEST SMACNA STANDARDS.
<br />• ALL WALL MOUNTED THERMOSTATS AND/OR TEMPERATURE SENSORS SHALL BE
<br />INSTALLED AT AN ELEVATION OF 48" ABOVE FINISHED FLOOR TO THE TOP UNLESS
<br />OTHERWISE NOTED ON DRAWINGS. LOCATION OF THE WALL MOUNTED THERMOSTAT
<br />SHALL BE COORDINATED WITH OTHER TRADES FOR A NEAT APPEARANCE. FINAL
<br />LOCATION OF THERMOSTAT SHALL BE SUBJECT TO THE APPROVAL OF THE ENGINEER
<br />OR HIS REPRESENTATIVE IN THE FIELD.
<br />• ALL SUPPLY AIR DIFFUSERS SHALL BE 4-WAY THROW UNLESS OTHERWISE NOTED.
<br />• CONTRACTOR SHALL PROVIDE A COPY OF THE TEST AND BALANCE REPORT AT THE
<br />FINAL INSPECTION. THIS REPORT MUST BE REVIEWED AND APPROVED BY THE
<br />ENGINEER PRIOR TO THE FINAL ACCEPTANCE.
<br />• FLEXIBLE AND RIGID ROUND DUCT TAKE -OFFS FOR DIFFUSERS SHALL BE THE SAME
<br />SIZE AS DIFFUSER NECK. MAXIMUM FLEXIBLE DUCT LENGTH SHALL BE 8'-0".
<br />• ALL MECHANICAL WORK SHALL MEET ALL THE REQUIREMENTS OF THE "2017 FBC
<br />MECHANICAL, 6TH EDITION".
<br />• LOCATIONS OF DUCT MOUNTED SMOKE DETECTORS SHOWN ON THE DRAWINGS ARE
<br />REFERENCE LOCATIONS ONLY. THE FINAL PLACEMENT OF THE DETECTOR IN THE
<br />DUCTWORK SHALL MEET THE REQUIREMENTS OF THE MANUFACTURER'S INSTALLATION
<br />INSTRUCTIONS. PROVIDE A PRESSURE DIFFERENTIAL TEST AND THE MANUFACTURER'S
<br />TEST KIT. A COPY OF ALL TEST DATA WILL BE MADE AVAILABLE AT THE FINAL
<br />INSPECTION. PROVIDE READILY ACCESSIBLE DUCT ACCESS DOOR FOR INSPECTING AND
<br />SERVICING THE DETECTOR. DIVISION 16 SHALL FURNISH DETECTOR, DIVISION 15 SHALL
<br />INSTALL DETECTOR, AND DIVISION 16 SHALL WIRE DETECTOR. CONFIRM SMOKE
<br />DETECTORS HAVE AUDIBLE ALARM, OR CAUSE SUPERVISORY SIGNAL TO BE INDICATED
<br />AT A CONSTANTLY ATTENDED LOCATION. PROVIDE FUNCTIONAL TEST OF FAN
<br />SHUTDOWN PRIOR TO C.O., IN ACCORDANCE WITH NFPA 90A.
<br />• ALL EXHAUST DUCTS SHALL BE GALVANIZED SHEET METAL.
<br />• PROVIDE ALL SERVICE CLEARANCES FOR ROOFTOP UNITS PER MANUFACTURERS
<br />RECOMMENDATIONS.
<br />• PROVIDE 24 VOLT AUTOMATIC DAMPERS IN ALL OUTSIDE AIR DUCTS.
<br />• COORDINATE ALL WORK WITH LANDLORD'S BASE BUILDING ROOFING
<br />CONTRACTOR, FIRE PROTECTION CONTRACTOR AND ALARM CONTRACTOR.
<br />• ALL ROOF MOUNTED EQUIPMENT SHALL HAVE PERMANENT NAMEPLATES
<br />IDENTIFYING TENANT SERVED.
<br />MECHANICAL LEGEND
<br />SYMBOL DESCRIPTION
<br />Js NEW DUCTWORK, PIPING, OR EQUIPMENT
<br />0
<br />0
<br />CD
<br />RRC
<br />TGC
<br />TGC
<br />(E)
<br />FLEXIBLE DUCT
<br />DUCTWORK TRANSITION
<br />SUPPLY OR OUTSIDE AIR DUCT SECTION
<br />RETURN OR EXHAUST DUCT SECTION
<br />SUPPLY AIR DEVICE. CLEAR TRIANGLE
<br />SIDES INDICATE AIR FLOW PATTERN
<br />RETURN OR EXHAUST AIR DEVICE
<br />WALL MOUNTED THERMOSTAT
<br />MOTORIZED DAMPER
<br />SMOKE DETECTO
<br />AV PERATURE SENSOR
<br />UNDERCUT DOOR 1"
<br />CEILING DIFFUSER
<br />RETURN REGISTER AT CEILING
<br />TRANSFER GRILLE AT CEILING
<br />SUPPLY REGISTER AT CEILING
<br />EXISTING
<br />SUPPLY DUCT
<br />.,—SEE BRANCH DUCT DETAIL
<br />INSULATED ROUND
<br />FLEXIBLE DUCT
<br />(MAX. 8'-0- LONG)
<br />SIZE TO MATCH
<br />DIFFUSER NECK.
<br />ROUND METAL DUCT
<br />(EXTERNAL INSULATION) INSULATION
<br />CEILING --CEILING DIFFUSER
<br />CEILING DIFFUSER RUNOUT DETAIL
<br />NO SCALE
<br />r
<br />U
<br />Nv-I
<br />Zw�
<br />Ono „ 0 �
<br />��� CE
<br />00
<br />U)co
<br />00
<br />rr
<br />Ln
<br />U Lu w
<br />w 0 m
<br />W Q ti
<br />xvlz=(6
<br />U < 0 c)
<br />9N�
<br />ON
<br />y J
<br />LL
<br />94
<br />I4
<br />Engineering
<br />Professionals, Inc.
<br />Mechanical Engineers
<br />EB-0006437
<br />1717 N. Howard Avenue
<br />Tampa, FL 33607 (813) 251-6848
<br />101111111111t1®
<br />icl® ®®®®
<br />C:j N,•,�
<br />No.,75420
<br />d
<br />A, E OF
<br />4
<br />% /3/-//
<br />SHANE R. HAMeUMN P.E.
<br />FLORIDA LICENSE #75420
<br />0
<br />0
<br />0
<br />0
<br />CONTRACT DATE: 08.01.2018
<br />BUILDING TYPE: N/A
<br />PLAN VERSION: N/A
<br />SITE NUMBER: N/A
<br />STORE NUMBER: N/A
<br />TENANT FINISH
<br />GALL BLVD
<br />ZEPHYRHILLS, FL 33541
<br />FINISH PLAN
<br />PHASE 2
<br />SCHEDULES,
<br />NOTES AND
<br />DETAILS
<br />M2
<br />PLOT DATE: 9/07/2018
<br />
|