PARTIAL FLOOR PLAN - MECHANICAL <br />1 /4" = V-0" <br />f Z f 3` <br />( I <br />A1................... _ - <br />B <br />GENERAL <br />STOCK <br />KEY PLAN <br />1/16" = 1'-0" <br />CODE REQUIRED OUTSIDE AIR VENTILATION RATES <br />NET <br />AREA <br />CODE O.A. <br />PEOPLE <br />CODE O.A. <br />TOTAL OA <br />CFM <br />OA <br />REQ D <br />REQ D <br />INSTALLED <br />INSTALLED <br />AREA <br />OUTDOOR <br />BASED ON <br />NO. <br />OUTDOOR <br />BASED ON <br />REQUIRED <br />PROPOSED <br />PROPOSED <br />ZONE & AREA <br />OCCUPANCY <br />SF <br />AIR RATE <br />FLOOR <br />PEOPLE <br />AIR RATE R. <br />PEOPLE <br />CODE <br />ACTUAL <br />ACTUAL <br />CATEGORY <br />RA <br />AREA <br />CFM/SF <br />CFM <br />CFM/PERSON <br />CFM <br />CFM <br />CFM <br />CFM <br />CONSULT ROOM <br />EXAM RM <br />96 <br />0.06 <br />6 <br />+ <br />2 <br />5.0 <br />10 <br />= <br />16 <br />150 <br />1 30 <br />TOTAL <br />96 <br />6 <br />+ <br />2 <br />10 <br />= <br />16 <br />150 <br />30 <br />AIR TERMINAL SCHEDULE <br />TAG <br />AREA <br />RANGE <br />NECK OR NOMINAL <br />OVERALL SIZE <br />BORDER <br />TYPE <br />BLOW <br />O.B.D. <br />PRICE MODEL OR <br />CFM <br />SIZE IN. <br />IN. <br />DAMPER <br />LISTED EQUAL <br />SAD <br />CONSULT ROOM <br />125 - 200 <br />8 DIA. <br />24 X 24 <br />LAY -IN <br />PLAQUE <br />360 DEG. <br />NONE <br />SEE <23 08 01> <br />TAG <br />CONSULT ROOM <br />125 - 200 <br />8 DIA <br />24 X 12 <br />LAY -IN <br />LOUVERED <br />NA <br />PRICE 630L OR 530L <br />NOTES: <br />1. AIR TERMINAL DEVICES SHALL BE FACTORY COATED STEEL <br />2. TERMINAL DEVICES SHALL HAVE A WHITE FACTORY FINISH TO MATCH ADJACENT CEILING GRID OR <br />SHALL MATCH THE ADJACENT DUCT OR EXTERNAL INSULATION SURFACE COLOR IN GENERAL SALES <br />AREA WITH OPEN CEILING. <br />3. TOTAL STATIC PRESSURE DROP ACROSS AN AIR TERMINAL SHALL NOT EXCEED 0.20 IN. WC. <br />4. ACCEPTABLE MANUFACTURERS: KRUEGER, METALAIRE, NAILOR, PRICE, TITUS, TUTTLE AND BAILEY. <br />5. DUCT INSULATION (IF APPLICABLE) SHALL EXTEND DOWN OVER TOP AND SIDES OF SUPPLY DIFFUSERS. <br />GENERAL NOTES I <br />1, GENERAL ; <br />1.1 REFER TO ALL OTHER DRAWINGS AND SPECIFICATIONS FOR <br />ADDITIONAL WORK OR CLARIFICATIONS. <br />2. AIR DISTRIBUTION: <br />2.1. DUCTWORK SHALL BE SPIRAL GALVANIZED STEEL METAL PER <br />SMACNA. REFER TO SPECIFICATION 23 30 00. INTERNAL LINING <br />IS NOT PERMITTED IN THE SUPPLY DUCTWORK. <br />2.2. FLEXIBLE DUCT LENGTH SHALL NOT EXCEED 5'-0". USE ONLY <br />ON FINAL CONNECTION TO SUPPLY AIR DIFFUSER, RETURN AIR <br />GRILLE OR DIFFUSER, AND TRANSFER GRILLE OR DIFFUSER, 90' <br />TURNS ARE NOT ALLOWED, OFFSET ANGLES SHALL BE KEPT <br />TO A MINIMUM. SEE DETAIL 1 /M-111. <br />2.3. INSTALL AND ADJUST SUPPLY AIR DIFFUSERS AND GRILLES TO <br />AVOID LIGHT FIXTURES STRIATION AND SIGNAGE SWINGING <br />FROM AIRFLOW. LOCATE DIFFUSERS IN ACCORDANCE WITH THE <br />ARCHITECTURAL REFLECTED CEILING PLAN. <br />2.4. PAINT THE INTERIOR SURFACE OF DUCTS (WHERE VISIBLE) <br />THROUGH GRILLES, DIFFUSERS ETC. USE FLAT 'DTM' (DIRECT <br />TO METAL) NON-SPECULAR BLACK PAINT. PAINT SHALL BE IN <br />COMPLIANCE TO FMC 602.2.1. MATERIALS WITHIN PLENUMS <br />SHALL BE NONCOMBUSTIBLE OR SHALL HAVE A A FLAME <br />SPREAD INDEX OF NOT MORE THAN 25 AND A SMOKE <br />DEVELOPMENT INDEX NOT MORE THAN 50 WHEN TESTED IN <br />ACCORDANCE WITH ASTM E 84 OR U.L. 723. <br />2.5. SUPPLY AND/OR RETURN AIR CEILING PLENUMS ARE NOT <br />PERMITTED. <br />2.6. DIFFUSERS AND GRILLES SHALL MATCH EXISTING STYLE WITH <br />FACTORY FINISH TO MATCH CEILING GRID. <br />2.7. ALL VOLUME DAMPERS SHALL BE FLAGGED WITH STREAMERS <br />FOR EASY IDENTIFICATION ESPECIALLY WHEN COVERED WITH <br />INSULATION. <br />2.8. AIR BALANCING: BALANCE AIR TO INDICATED QUANTITIES <br />WITHIN A TOLERANCE OF PLUS OR MINUS 107o. ADJUST <br />SUPPLY AIR GRILLE BLADES TO MEET COMFORT CONDITIONS IN <br />WORKING AREA PER MANUFACTURER'S RECOMMENDATIONS. <br />3. INSULATION: <br />3.1. INSULATE DUCTWORK PER SPECIFICATION 20 07 00. <br />REFERENCE KEYED NOTES <br />DIVISION 23 - MECHANICAL <br />NEW 24"x24" VAV DIFFUSER MOUNTED IN GRID CEILING. <br />PROVIDE CARNES MODEL #SHPV-24-08-11 THERMAFUSER. <br />23 08 01 <br />SET COOLING TO 72'F, SET HEATING TO 70'F. ROUTE DUCT TO <br />EXISTING MAIN. PROVIDE MANUAL VOLUME DAMPER AFTER <br />TAKE -OFF. <br />23 08 02 <br />NEW BRANCH CONNECTION TO EXISTING DUCTWORK. <br />RELOCATE EXISTING SUPPLY DIFFUSER TO LOCATION <br />23 08 03 <br />SHOWN ON PLAN. BALANCE EXISTING DIFFUSER TO <br />LISTED CFM. <br />TRANSFER AIR GRILLE - PROVIDE (2) 24" x 12". <br />GRILLE WITH FIXED LOUVERS, 3/4" SPACING, 45 DEG. <br />23 08 04 <br />DEFLECTION. CONNECT LOUVER'S WITH 8"0 DUCT FOR <br />AIR TRANSFER. COORDINATE LOCATION WITH LIGHTING <br />PLAN. <br />I FIRE PROTECTION NOTES I <br />1. DESIGN -BUILD CONTRACTOR SHALL VISIT THE SITE, REVIEW <br />EXISTING SPRINKLER SYSTEM, PREPARE SHOP DRAWINGS AND <br />HYDRAULIC CALCULATIONS FOR THE PROPOSED REMODEL IN <br />COMPLIANCE WITH LATEST NFPA 13 AND LOCAL APPLICABLE <br />BUILDING CODES AND FIRE DEPARTMENT ORDINANCES. THE <br />CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS BEFORE <br />STARTING ANY WORK. <br />I MECHANICAL LEGEND I <br />® SUPPLY AIR <br />z RETURN OR EXHAUST AIR <br />F-- VOLUME DAMPER <br />O THERMOSTAT (MOUNT 5'-0" UP, UNLESS <br />OTHERWISE NOTED) <br />SENSOR FOR THERMOSTAT; (MOUNT 6'-0" <br />UP ON COLUMN) OR UNLESS NOTED <br />OTHERWISE. <br />XXXS CFM SUPPLY AIR <br />XXXR CFM RETURN AIR <br />RTU ROOF TOP UNIT <br />CFM CUBIC FEET PER MINUTE <br />EWH ELECTRIC WALL HEATER <br />BBH BASEBOARD HEATER <br />FD FIRE DAMPER WITH ACCESS DOOR <br />SAD SUPPLY AIR DIFFUSER <br />SAG SUPPLY AIR GRILLE <br />SAR SUPPLY AIR REGISTER <br />RAG RETURN AIR GRILLE <br />EAG EXHAUST AIR GRILLE <br />X EXISTING TO REMAIN <br />XO EXISTING TO BE REMOVE <br />XR EXISTING RELOCATED <br />XRR EXISTING TO BE REMOVED AND RELOCATED <br />N NEW <br />HANGER <br />RIGID RADIUS <br />ELBOW WITH <br />INSULATION <br />CEILING — <br />DIFFUSER <br />OR GRILLES <br />ROUND SPIRAL <br />DUCTWORK <br />j��lll <br />METAL <br />DRAW <br />I ~~ BAND <br />VOLUME DAMPER AT <br />TAKE OFF (TYPICAL). <br />VOLUME DAMPER SHALL <br />HAVE A SINGLE 24 GA <br />MIN. BLADE, POSITION <br />ARM W/LOCKING WING <br />NUT PER SMACNA <br />2005, FIG. 7-4. <br />NOTE: <br />1. TOP OF DIFFUSER AND BOTTOM OF RIGID ELBOW SHALL BE <br />ALIGNED, NOT TO EXCEED 12" HORIZONTAL OFFSET. <br />� SUPPLY FLEXIBLE DUCTWORK <br />(D0Oo <br />zzQ� <br />0 <br />z Lu L6 <br />�z0o <br />WZ_J <br />W <br />W <br />J z p ❑ <br />UQ- <br />z LL <br />LL (D W <br />uJ W <br />W ❑ <br />. o <br />0 <br />z <br />LL]W Q <br />Q Q ❑w w H 0 <br />Q0H0�-Z�Q2 <br />H0Z� LLI =QCL�Q�� <br />=z0-zWOJO� <br />W<F- 0�HLdLL <br />UZQO>cAJU=LLD <br />Wa6 O wQ F- <br />u <br />wa <br />wLcQUOQzQ <br />z <br />O_ <br />F- <br />a <br />W U <br />a w <br />o 0 U) <br />m Z <br />Of O <br />O 0 <br />> <br />W LLI <br />❑ w <br />� m <br />-10 <br />z <br />CV <br />Lo <br />Lo <br />Z OM <br />> M <br />w J J <br />w m LL <br />J <br />J <br />J <br />d_ <br />J 0- <br />04 <br />j .0a. <br />W <br />N <br />m <br />CDW <br />o <br />LU <br />W_ <br />Q <br />F- <br />> <br />N <br />w of <br />M-1 11 <br />