<br />PROJECT NV TE a
<br />E el
<br />1. ALL WORK SHALL BE IN STRICT ACCORDANCE WITH THE 2014 EDITION OF THE NATIONAL
<br />ELECTRICAL CODE (N.E.C) AND ALL LOCAL CODES AND ORDINANCES.
<br />E 2. ALL MATERIALS SHALL BE NEW AND OF DOMESTIC ORI61N AND SHALL BEAR UNDERWRITERS'
<br />LABEL WHERE APPLICABLE.
<br />3. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A
<br />FIR5T-CLA55 WORKMANLIKE MANNER. THE COMPLETED SYSTEM IS TO BE FULLY OPERABLE AND
<br />ACCEPTANCE OF THIS 5Y5TEM BY THE EN&INEI R/ARCHITECT MUST BE A CONDITION OF THE SUB
<br />CONTRACT.
<br />4. ALL WORK TO BE COORDINATED WITH OTHER TRADES TO AV011,7 INTERFERENCE WITH THE
<br />PROGRE55 OF CONSTRUCTION,
<br />5. CONTRACTOR TO GUARANTEE ALL MATERIALS AND WORKMAN5HIP FREE FROM DEFECTS FOR A
<br />A PERIOD OF NOT LESS THAN ONE (1) YEAR FROM DATE OF ACCEPTANCE,
<br />L 6. CORRECTION OF ANY DEFECTS TO BE COMPLETED WITHOUT ADDITIONAL GHAR6E AND TO
<br />INCLUDE REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY
<br />HAVE BEEN DAMAGED THEREBY.
<br />'I. ALL REQUIRED INSURANCE TO BE PROVIDED FOR PROTECTION A6AIN5T PUBLIC, LIABILITY OF
<br />PROPERTY DAMAGE FOR THE DURATION OF THE WORK.
<br />5. CONTRACTOR TO PAY FOR ALL PERMITS, UTILITY FEES, INSPECTIONS AND TE5TIN6.
<br />q. ELECTRICAL INSTALLATION TO MEET ALL STANDARD REQUIREMENTS OF LOCAL POWER AND
<br />TELEPHONE COMPANIES.
<br />10. MINIMUM WIRE 51ZE SHALL 13E #12 AHG, EXGLUDINC CONTROL HIRINCa. UNLESS OTHERHI5E NOTED,
<br />CONDUGTOR5 SHALL BE COPPER WITH THHN/THHN INSULATION. CONDUCTOR5 #12 AND SMALLER
<br />MAY BE 50UD; ALL THOSE #10 AND LARGER TO BE STRANDED.
<br />II. ALL UNDER t ROUND RAGEWAY5 SHALL BE OALVANIZED RIGID STEEL CONDUIT OR SCHEDULE 40
<br />PVC. ALL OTHER RACEHAY5 TO COMPLY WITH C60VERNIN6 CODES. MINIMUM CONDUIT
<br />UNDER AROUND SHALL BE 3/4" CONDUIT UNLE55 OTHERH15E NOTED.
<br />12. OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS, CAST ALLOY WITH THREADED
<br />HUB5 IN WET OR DAMP LOCATIONS, AND BE OF SPECIAL CONSTRUCTION FOR OTHER CLASSIFIED
<br />AREAS. ALL BOXES SHALL BE RECESSED (FLUSH) IN HALLS OR GEILIN65 WHENEVER POSSIBLE.
<br />B. DISCONNECT 5HITCHE5 SHALL BE H.P. RATED, GENERAL OR HEAVY DUTY WHERE INDICATED,
<br />QUICK -MAKE, QUICK -BREAK TYPE. ENCL05URI5 SHALL BE AS REQUIRED BY N.E.C. AND
<br />LOCATION (WEATHERPROOF, EXPLOSION- PROOF, ETC).
<br />14. ALL GENERAL PURPOSE 5HITCHE5 AND RECEPTACLE5 SHALL BE THE PRODUCT OF A 51NOLE
<br />MANUFACTURER. CATALOG NUMBERS LISTED ARE LEVITON: HOWEVER, COMPARABLE DEVICES
<br />BY HUBBELL, PASS 4 SEYMOUR, OR ARROW HART HILL BE ACCEPTED. COLOR OF DEVICES AND
<br />PLATES SHALL BE AS DICTATED BY ARCHITECT/OWNER.
<br />A. 5WITCHE5: #1221-2 5ERI1-5.
<br />B. RECEPTACLES: #5362 SERIES.
<br />C. COVER PLATES: SMOOTH PLASTIC
<br />NOTE: ALL OTHER REQUIRED DEVICES SHALL MATCH IN COLOR AND STYLE.
<br />15. ALL RACEWAYS AND PIPES, SPACED IN OR THROUGH ANY CONCRETE 5LAB, SHALL BE SPACED
<br />A MINIMUM OF THREE TIMES THE DIAMETER OF THE LAR65E5T RACEWAY.
<br />16. IT 15 NOT THE INTENT OF THESE PLANS TO 5HOH EVERY MINOR DETAIL OF CONSTRUCTION. THE
<br />CONTRACTOR IS EXPECTED TO FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL
<br />SYSTEM, AND PROVIDE ALL NECE55ARY DEVICES AND GOMPONENT5 FOR EQUIPMENT TO BE
<br />PLACED IN PROPER HORKIN6 ORDER.
<br />I-1. ALL ELECTRICAL RACEWAYS (METALLIC AND NONMETALLIC) SHALL HAVE AN EQUIPMENT
<br />GROUND CONDUCTOR 51ZED IN ACCORDANCE HITH THE 2014 EDITION OF THE N.E.C.
<br />0. LOAD DATA IS BASED ON INFORMATION GIVEN ENGINEER AT THE TIME OF DESIGN. VERIFY ALL
<br />EQUIPMENT NAMEPLATE RATINGS BEFORE ORDERING.
<br />19. CIRCUITS 5HOHN ON PLANS ARE TO DETERMINE LOAD DATA AND PANEL SIZES. THE
<br />CONTRACTOR IS TO PROVIDE CIRCUITS AND ROUTING OF CONDUITS TO SUIT JOB CONDITIONS.
<br />20. FURNISH AND INSTALL DISCONNECT SWITCHES, WIRING, AND CONNECTIONS ON AIR CONDITIONING
<br />SYSTEM AS SHOWN ON PLANS. ELECTRICAL GONTRACTOR SHALL VERIFY AND COORDINATE WITH
<br />MECHANICAL CONTRACTOR RE6ARDIN6 SUPPLY AND INSTALLATION OF ALL REQUIRED
<br />CONTROLS.
<br />21. ALL 5HITCH6EAR SHALL BE THE PRODUCT OF A SINGLE MANUFACTURI=R. 5Y5TEM DE516N 15
<br />BA5ED ON THE SQUARE "D" COMPANY, HOWEVER, COMPARABLE EQUIPMENT BY EATON, G.E., AND
<br />SIEMENS HILL BE ACCEPTABLE. TANDEM AND HALF-5PAGE CIRCUIT BREAKERS SHALL NOT BE
<br />USED. PROVIDE ARC FLASH WARNING 516NA6E PER N.E.G. 110.16 FOR ALL SWITCHBOARDS AND
<br />PANELS.
<br />22. ALL UNDERGROUND PVC CONDUIT RUNS SHALL HAVE RI61D STEEL. ELBOWS AND RI61D STEEL
<br />SECTIONS AT SLAB PENETRATIONS. HHERE RIGID STEEL 15 USED, IT SHALL BE COMPLETELY
<br />COATED HITH AN ALKALI AND RUST-RE515TANT BITUMA5TIC PAINT, AND THREADS SHALL BE
<br />COATED HITH ZING CHROMATE.
<br />23. THE EL.ECTRIGAL CONTRACTOR SHALL MEET AND COORDINATE WITH THE LOCAL UTILITY
<br />COMPANIES AT THE 51TE PRIOR TO CONSTRUCTION, AT THAT TIME, THE CONTRACTOR SHALL
<br />COORDINATE ALL RELATED HORK HITH THE UTILITY COMPANIES' REPRESENTATIVES TO MEET
<br />THE OWNER'S SCHEDULE.
<br />24. ALL ELECTRICAL GONDUCTOR5 SHALL BE INSTALLED IN AN APPROVED RAGEHAY.
<br />25. CONTRACTOR SMALL BE RESPONSIBLE FOR 5EALING ALL CONDUIT PENETRATIONS MADE
<br />THROUGH FIRE RATED HALLS, CEILIN65, SLABS, ETC. PENETRATION SEALS SHALL BE PER U.L.
<br />ASSEMBLY STANDARDS.
<br />26. CONDU.IT.SY_5TEM_REQUIREMENTS=_
<br />UNDERGROUND - PVC HITH RIGID c4O THROUGH SLAB.
<br />ABOVE FINISH FLOOR, CEILING-6, ETC. (INDOOR) - EMT WITH DIECA5T SET SCREW FITTIN66.
<br />GALVANIZED RICAD CONDUITS - ABOVE GRADE AND WHERE SUSCEPTIBLE TO PHYSICAL
<br />DAMA6,155.
<br />FLEXIBLE CONDUITS - INDOOR, ONLY SHORT RUNS NOT TO EXCEED 6-0"
<br />5EALTITE - OUTDOOR, ONLY SHORT RUNS NOT TO EXCEED 6'-0"
<br />21.
<br />THE FOLLOWING APPLICABLE COLOR CODES SHALL BE IMPLEMENTED AND P05TED IN ALL
<br />PANELS, DISCONNECT SHITCHE5, ETC., PER NEC ARTICLES 200.6(D) AND 215.12,
<br />120/205V., 3--PH.
<br />PHASE 'A' BLACK
<br />PHASE 'B' RED
<br />PHASE 'G' BLUE
<br />NEUTRAL WHITE
<br />GROUND GREEN
<br />150L. GROUND 6REEN/YELLOH
<br />28. CFI RECEPTACLES
<br />ALL RECEPTACLES WITHIN 51X FEET OF A HATER SOURCE SHALL BE A 6FI RECEPTACLE OR
<br />PROTECTED BY A 6FI BREAKER PER NFPA 10 (NEC) ARTICLE 210b. THIS NOTE APPLIE5 TO
<br />ALL SHEETS.
<br />2Q. PROVIDE ALL REQUIRED O-IOV WIRING TO O-IOV DIMMABLE FIXTURES AND CONTROLS AS
<br />REQUIRED. THI5 O--IOV LOW VOLTAGE HIRING IS NOT 5HOHN ON PLANS FOR DRAWING CLARITY.
<br />30. ALL OUTDOOR RECEPTACLES SHALL BE HEATHER RE-515TANCE RATED, CGF{-TYPE WITH "HET
<br />WHILE IN USE" COVERS.
<br />31. WHERE HIRE SIZES ARE SHORN ON PLANS OR IN PANEL SCHEDULE, THE SAME HIRE SIZE, A5 A
<br />MINIMUM, SHALL BE CARRIED THROUGHOUT THE CIRCUIT UNLE55 5PECIFICAL.LY NOTED
<br />OTHERWISE ON PLANS.
<br />NqD
<br />MG GABLE NOTES
<br />._ .
<br />• BRANCH CIRCUITS MAY BE METAL CLAD GABLE TYPE (MG), PROVIDED:
<br />• WHERE PANEL 15 FLUSH MOUNTED
<br />THE CABLE SHALL RUN IN WALL CAVITY.
<br />WHERE PANL I5W-9 AGF MOUE.
<br />CONTRACTOR SHALL PROVIDE METAL STUDS WITH DRYWALL TO
<br />CREATE A CAVITY TO RUN THE MC GABLE WITHIN.
<br />• MG CABLE MAY BE USED FOR 20 AMP CIRCUITS IN WALLS OR ABOVE
<br />ACGE551BLE CEILINGS.
<br />• MC: CABLE WIRE GAUCP5 SHALL BE AS 5HOWN ON PANEL SCHEDULE.
<br />• MC GABLE SHALL ONLY BE USED WHERE ALLOWED BY N.E.C. SECTION
<br />330.10, WHERE APPROVED BY THE BUILDING OFFICIAL, AND ACCEPTED
<br />BY THE OHNERR.
<br />« MC CABLE SHALL BE INSTALLED PER N.E.G. 350.
<br />• ALL GABLE RUNS SHALL BE CONCEALED FROM VIEW AND ROUTED
<br />PARALLEL AND PERPENDICULAR TO BUILDING LINES.
<br />• MG CABLE MAY NOT BE USED IN OPEN STRUCTURE AREA, EXPOSED, OR
<br />OTHERWISE V151BLE TO CUSTOMERS.
<br />• NO MC GABLE CAN BE USED IN DAMP OR WET LOCATIONS.
<br />N43B
<br />2017 FLORIDA BUILDING CODE, ENERGY CONSERVATION (6TH EDITION)
<br />SECTION C405.6 ELECTRIC POWER
<br />6405b.3 VOLTAGE DROP
<br />THE CONDUCTORS FOR FEEDERS AND BRANCH CIRCUITS COMBINED SHALL BE
<br />SIZED FOR A MAXIMUM OF 5 % VOLTAGE DROP TOTAL.
<br />G405.6.4.1 QRAHINGS
<br />CONSTRUCTION DOCUMENTS HEREBY REQUIRE THAT WITHIN 30 DAYS AFTER.
<br />THE DATE OF SYSTEM ACCEPTANCE, RECORD DRAWINGS OF THE ACTUAL
<br />INSTALLATION SHALL BE PROVIDED TO THE BUILDING OWNER., INGLUDING:
<br />I. A 51N6LE-LINE D{ACRAM OF THE BUILDING ELECTRICAL DISTRIBUTION
<br />SYSTEM.
<br />2. FLOOR PLANS INDICATING LOCATION AND AREA SERVED FOR ALL
<br />DISTRIBUTION.
<br />0405.6.4.2 MANUAL5
<br />CONSTRUCTION DOCUMENTS HEREBY REQUIRE THAT AN OPERATING MANUAL
<br />AND MAINTENANCE MANUAL BE PROVIDED TO THE BUILDING OHNER. THE
<br />MANUALS SHALL INCLUDE, AT A MINIMUM, THE FOLLOWING:
<br />1. SUBMITTAL DATA STATING EQUIPMENT RATING AND SELECTED OPTIONS
<br />FOR EACH PIECE OF EQUIPMENT REQUIRING MAINTENANCE.
<br />2. OPERATION MANUALS AND MAINTENANCE MANUALS FOR EACH PIECE OF
<br />EQUIPMENT REQUIRING MAINTENANCE. REQUIRED ROUTINE MAINTENANCE
<br />ACTIONS SHALL BE CLEARLY IDENTIFIED.
<br />3. NAMES AND ADDR.E55E5 OF AT LEAST ONE QUALIFIED SERVICE AGENCY.
<br />SECTION C408 SYSTEM COMMISSIONING
<br />G40& 3.1 FUNCTIONAL TE5TING:
<br />I. PRIOR TO PA551N6 FINAL INSPECTION, THE RE615TERED DESIGN
<br />FROFE55IONAL SHALL PROVIDE EVIDENCE THAT THE LIG1-1TIN6 CONTROL
<br />SYSTEMS HAVE BEEN TESTED TO ENSURE THAT CONTROL HARDWARE AND
<br />5OFTHARE ARE CALIBRATED, ADJUSTED, PROGRAMMED AND IN PROPER
<br />WORKING CONDITION IN ACCORDANCE H1TH THE CONSTRUCTION
<br />DOCUMENTS AND MANUFACTURER'S INSTRUCTIONS. FUNCTIONAL TESTING
<br />SHALL BE IN ACCORDANCE HITH 5ECTIONS G40&.3.1.1 AND 040&3.1.2 FOR
<br />THE APPLICABLE CONTROL TYPE.
<br />N40A
<br />MUTES
<br />1. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN AND INTERIOR
<br />E ELEVATIONS FOR COORDINATION OF LOCATIONS OF LIC14TIN6
<br />j+�I FIXTURES.
<br />� `� 2. (EX) DENOTE-5 EXI5TINC LI&HT FIXTURE OR DEVICE TO REMAIN A5-15.
<br />E FIELD VERIFY QUANTITIES AND LOCATIONS.
<br />3. (R) DENOTES RELOCATED EXISTING L16HT FIXTURE OR DEVICE.
<br />COORDINATE HITH OWNER'S REPRESENTATIVE.
<br />A 4. GROUND CONDUCTOR SHALL BE INSTALLED IN ENTIRE RACEWAY
<br />SYSTEM INCLUDING WALL 5HITC.HE5 AND FLEXIBLE CONDUIT TO LI&HT
<br />L FIXTURES.
<br />5. ALL TELEPHONE/DATA/VOICE JACKS AND CABLING TO BE PROVIDED
<br />AND INSTALLED BY OTHERS, UNLESS OTHERWISE NOTED ON DRAWINGS.
<br />6. REUSE EXI5TIN6 JUNCTION BOXES, CONDUIT AND HIRING HHERE
<br />APPLICABLE. REMOVE AND DISPOSE OF ALL UNUSED CONDUIT AND
<br />WIRING BACK TO ITS SOURCE.
<br />1. CONTRACTOR SHALL REFER TO INTERIOR ARCHITECTURAL DRAHIN05
<br />FOR FOR COORDINATION OF MOUNTING HEIGHTS AND/OR LOCATIONS
<br />OF ALL WIRINGS DEVIGE5.
<br />8. THE CONTRACTOR 5HALL REMOVE ALL PXISTIN& WIRINC7 AND
<br />EQUIPMENT MADE UNNECESSARY BY THE RENOVATION. ALL MATERIALS
<br />REMOVED SHALL BE DISPOSED OF BY THE CONTRACTOR.
<br />9. ELECTRICAL CONTRACTOR SHALL VERIFY AND COORDINATE ALL
<br />DEVIGP TYPES, LOCATIONS AND QUANTITIES WITH OHNER'5
<br />REPRESENTATIVE AND PROVIDE AGGORDINOLY.
<br />10. LIGHTING 5WITCHE5 SHALL BE GROUPED WITH ONE PLATE AND
<br />LOCATED APPROXIMATELY 2 INCHES FROM DOOR FRAME (STRIKE
<br />SIDE) UNLF-55 OTHERWI5E NOTED.
<br />11. ALL EXPOSED CONDUIT SHALL BE RUN PARALLEL TO OR AT R16HT
<br />ANCLE5 TO STRUCTURE.
<br />N23B
<br />L E V rND
<br />E
<br />MOUNTING HEI6HT5 SHOWN ARE MAXIMUM/MINIMUM
<br />NOT
<br />ALL DEVIGE5 5HOHN IN LE6PND ARE REQUIRED.
<br />HANDICAPPED ACGE551BILITY 5TANDARD5 - THEY SHALL
<br />REVIEW POY�F-R AND LIGHTING PLANS AND DETAILS FOR
<br />NOT BE ALTERED WITHOUT WRITTEN AUTHORIZATION.
<br />ITEMS WHICH APPLY TO THIS PROJECT.
<br />E
<br />[Z]
<br />LINEAR LIGHT FIXTURE, LETTER INDICATES TYPE
<br />E I
<br />MAIN 5WITCA-1 OARD
<br />G
<br />00
<br />DOWN LIGHT FIXTURE, LETTER INDICATE5 TYPE
<br />MAIN DISTRIBUTION PANEL
<br />T
<br />I-0 c
<br />WALL BRACKET Li6HT FIXTURE, LETTER INDICATES TYPE
<br />O
<br />SPECIAL NOTES, SEE PLANS
<br />Q
<br />1-16HT FIXTURE ON LEMER6l NGY CIRGUIT/NI&HT LIGHT (NL.J
<br />r'" �I CONCEALED IN HALL
<br />ORS A5 SHOWN ON PANEL SCHEDULE.CEILIN U.O.N.
<br />'
<br />®
<br />EXIT LIGHT (ARROW INDICATES DIRECTION)
<br />BATTERY POWERED ENS"ReENGY LIGHT
<br />CONDUIT CONCEALED _ BELOW FLOOR
<br />SLAB HEUN U.O.N. GRADE
<br />f ~ WI CCONDUCTORS AS SHOWN ON PANEL SCHEDULE
<br />�j
<br />mm
<br />�'
<br />fU HEAD REMOTE EXTERIOR MOUNTED ENER&ENCY L16HT.
<br />'" .,- ._ _. J
<br />CONDUIT EXPOSED ON WALL OR CEILING WITH CONDUCTORS AS
<br />SHOWN ON PANEL. SCHEDULE. U.O.N.
<br />(2) HEAD REMOTE EXTERIOR MOUNTED EMERGENCY 1-1614T.
<br />� ``�,� TM-EV15ION 5Y5TEM EMPTY CONDUIT WITH PULL WIRE
<br />L
<br />FLEXIBLE. CONDUIT NOT TO EXCEED 6 FEET IN L.EN(9TH
<br />TRACK L16HTIN6
<br />DG
<br />� � D.C. VOLTAGE WIRING 010 WIRE IN 1/2" CONDUIT)
<br />5°
<br />SINGLE POLE 'SWITCH, LOWLY. CASE LETTER INDICATES LIGHT
<br />CONTROLLED, MOULT 46" A.F.F. U.O.N.
<br />WIREMOLD (SIZE AND L.EN6TH AS NOTED)
<br />S2
<br />DOUBLE POLE SWITCH, MOUNT 46" A.F.F. U.O.N.
<br />53
<br />THREE-WAY SWITCH, MOUNT 46" A.F.F. U.O.N.
<br />/
<br />CONDUIT SEAL -OFF FITfIN6
<br />S4
<br />POUR -WAY SWITCH, MOUNT 46" A.F.F. U.O.N.
<br />PADDLE FAN WITH BACKBOX CAPABLE OF 5UPPORTIN6 100 LB.
<br />Sp
<br />SIN6L E POLE SWITCH WITH PILOT LIGHT, MOUNT 4&" A.F.F.
<br />LOAD
<br />U.O.N.
<br />5K
<br />KEY OPERATED 5IN6L.E POLE SWITCH, MOUNT 46" A.F.F. U.O.N.
<br />c:m
<br />T.V. CAMERA
<br />Sr
<br />FAN CONTROLLER, MOUNT 46" A.F.F. U.O.N.
<br />0
<br />T.V. MONITOR
<br />S°
<br />DIMMER SWITCH, WATTS A5 NOTED, MOUNT 46" A.F.F. U.O.N.
<br />TELEVISION OUTLET, PROVIDE SINGLE 5AN& BOX WITH 3/4"
<br />CONDUIT WITH PULL WIRE AND INSULATING BU"SHIN6 STUBBED INTO
<br />SINGLE RECEPTACLE, AMPS AS NOTED, MOUNT lb" A.F.F.
<br />CEILING SPACE. MOUNT BOX 0" A.F.F. U.Q.N.
<br />U.O.N.
<br />G.-
<br />DUPLEX RECEPTACLE, MOUNT Ib" A.F.F. U.U.N.
<br />`©
<br />DISCONNECT 5WITCH
<br />DUPLEX RECEPTACLE, MOUNT A50VE COUNTER HEIGHT U.O.N.
<br />DISCONNECT DESIGNATION (SIZE/POLES/FUSE) "NP' INDICATES
<br />NON -FUSED; "PE" INDICATES DUAL ELEMENT FUSES.
<br />G�JADRAPLEX RECEPTACLE, MOUNT IB" A.F.F. U.O.N.
<br />MAGNETIC MOTOR STARTER
<br />!
<br />DUPLEX RECEPTACLE, HORIZONTALLY MOUNTED.
<br />`o
<br />COMBINATION MACPNETIC MOTOR 5TARTER/0I5CONNECT SWITCH
<br />OoA
<br />I PH, 25OV. RECEPTACLE, AMPS AS NOTED, MOUNT lid" A.F.F.
<br />FT1
<br />DRY TYPE TRANSFORMER
<br />U.O.N.
<br />0-1
<br />SPECIAL RECEPTACLE AS NOTED
<br />®
<br />CONTACTOR (A5 NOTED)
<br />Q
<br />FLOOR MOUNTED DUPLEX RECEPTACLE
<br />T;G
<br />TIME CLOCK
<br />em
<br />e4ZOLAVL7 FAULT INTERRUPTER RECEPTACLE, LEVITON ik78g4--R,
<br />r�ic
<br />PHOTOCELL.
<br />MOUNT ABOVE COUNTER HEIGHT U.O.N.
<br />MOTOR PERMANENTLY CONNECTED WITH FLEXIBLE CONDUIT
<br />I a.
<br />DUPLEX RECEPTACLE, 150L.ATW 6ROUNP TYPE, LEVITON
<br />05362-161 MOUNT AT 15" A.F.F. U.O.N.
<br />ELECTRIC DUCT HEATER.
<br />I:
<br />DUPLEX RECEPTACLE, SPLIT WIRED, MOUNT IB" A.F.F. U.O.N.
<br />THERMOSTAT. PROVIDE EaAN6 BOX WITH C. BBIED
<br />WwPt
<br />DUPLEX RECEPTACLE, WEATHER-RE'515TANT AND 6FI RATED,
<br />Q
<br />MOSINUNT
<br />INTO Ci=1LIN6 SPACE, MOUNT 60" A.F.F. UA.N. !COORDINATE WITH
<br />RD E WITH
<br />LEVITON vW`iMq-TRpK WITH WEATHERPROOF BOX AND
<br />MECHANICAL DRAWIN65 PRIOR TO RG H-•IN)
<br />COVER. MOUNT AT IV' A.F.F. U.O.N.
<br />PUSHBUTTON, MOUNT 45" A.F.F. U.O.N.
<br />DUPLEX OUTLET WITH USB CONNECTION. LEVITON *T832
<br />(WITH COLOR TO MATCH OTHER DEVICE5 IN THE AREA).
<br />DOOR CHIME WITH TRANSFORMER
<br />TELE/DATA OUTLET, PROVIDE 4" SGd. BOX WITH 1--6AN6 MUD
<br />O
<br />SAKE,
<br />RINCY, AND 3/4" CONDUIT WITH PULL WIRE AND IN51JL.ATIN6
<br />BUISHIN& STUBBED INTO CEILING SPACE, MOUNT ABOVE
<br />0
<br />JUNCTION BOX (FLUSH MOUNT IN FINISHED AREAS U.O.N)
<br />COUNTER HEIGHT U.O.N.
<br />TELE/DATA OUTLET, PROVIDE 4" 50, BOX WITH I -GANG MUD
<br />■
<br />DEVICE A5 NOTED
<br />RING, AND 5/4" CONDUIT WITH PULL WIRE AND INSULATING
<br />BU5HIN6 STUBBED INTO CEILING SPACE. MOUNT BOX lap
<br />�
<br />TELEPHONE BACKBOARD WITH #'6 CU. GROUND (SIZE AS NOTED)
<br />A.F.F. UA.N
<br />®
<br />2TT/46OV, 5-PH PANEL.BOARD
<br />V
<br />TELEPHONE/ VOICE WALL OUTLET, PROVIDE 4" 50. BOX WITH
<br />I-6AN6 MUD RING, AND 3/4' CONDUIT WITH PULL WIRE AND
<br />w
<br />LIGHTING OR POWER PANELBOARD
<br />IN5UL.ATIN6 BUSHII& 5TUBL�EO INTO CEILIN& SPACE. MOUNT
<br />BOX I5" A.F.F. U.O.N.
<br />$!
<br />FLOOR MOUNTED TELEPHONE RECEPTACLE
<br />DATA WALL OUTLET, PROVIDE 4' 50. BOX WITH I-6A1e MUD
<br />SPLIT CONTROLLED DUPLEX RECEPTACLE WITH (1) OUTLET
<br />RING, AND 3/4" CONDUIT WITH PULL WIRE AND IN5UL ATIN&
<br />CPS
<br />CONTROLLED AND (1) OUTLET CONSTANT HOT. LEVITON #5362-IP
<br />BUSIi1149 STUBBED INTO CEILII46 5PACE. MOUNT BOX AT 16"
<br />(W/COLOR TO MATCH OTHER DEVICES IN THE AREA),
<br />A.F.F. U.O.N.
<br />*c4;v
<br />QUAD CONTROLLED RECEPTACLE KITH (1) DUPLEX RECEPTACLE
<br />CONTROLLED AND (1) DUPLEX RECEPTACLE CONSTANT HOT.
<br />LEVITON 0.5362-2P (W/COL.OR TO MATCH OTHER DEVICES- IN
<br />AREA).
<br />.&M69.1LId't'IQW
<br />E.O. i GIUIPMERT GROUND EPC ELECTRIC, HATTER COOLER
<br />N.L.
<br />N16W L16MT AF.0. A50VE FINISH FADE
<br />I.6. ISOLATED 64ROUND E/F-EF EXHAUST FAN
<br />PC
<br />PULL CHAIN U.O.N. UNLE56 OTHERWISE NOTED
<br />WP WEATHI37PROOP A/H-AHU AIR HANDLING UNIT
<br />C.T.
<br />CURRENT TRANSFORMER N T5. NOT TO 5CALI---
<br />EC EMPTY CONDUIT ACC-CU CONDEN51146 UNIT
<br />EX
<br />EXISTIN& DEVICE N.I.C. NOT IN CONTRACT
<br />EHH ELECTRIC WATER HEATER R U ROOF TOP UNIT
<br />ER
<br />EXISTING TO BE RELOCATED A.FF. ABOVE FINISH FLOOR
<br />6FI/6F0I GROUND FAMT CIRCUIT
<br />INTERRUPTER
<br />NOTE: MOUNTING HEI60T5 NOTED ARE
<br />TO CENTERLINE OF DEVICE SHOWN. U.O.N.
<br />01
<br />NOTES
<br />I. IT IS THE CONTRACTOR'S RE5PON5151LITY TO REVIEW ALL DRAHIN65
<br />O
<br />AND SPECIFICATIONS, INCLUDING BUT NOT LIMITED TO ARCHITECTURAL,
<br />STRUCTURAL, MECHANICAL, PLUM311,16, AND ELECTRICAL PRIOR TO
<br />N
<br />5UBMITTIN6 A BID.
<br />T
<br />2. REPORT ANY 015CREPANGIE5 TO ARCHITECT OR ENGINEER. PRIOR TO
<br />BID.
<br />3. BIDDERS ARE TO V151T THE SITE AND FAMILIARIZE THEM5PLVE5 HITH
<br />//��
<br />EXI5TINC7 CONDITIONS AND SATISFY THEMSELVES AS TO THE NATURE
<br />1/"""-�
<br />AND SCOPE OF THE HOW.
<br />4. IT 15 THE CONTRACTOR-5 RESPONSIBILITY TO VERIFY ALL EXI5TINe 51TE
<br />T
<br />CONDITIONS INCLUDING BUT NOT LIMITED TO, SERVICE LOCATION,
<br />SERVICE LAYOUTS, AND TELEPHONE LOCATION., ETC.
<br />0
<br />5. THE 5U5MI5510N OF A BID WILL 13E EVIDENCE THAT 5UCH AN
<br />EXAMINATION HAS BEEN MADE. LATER CLAIMS FOR LABOR, EQUIPMENT,
<br />OR MATERIALS REQUIRED, OR FOR ANY DIFFICULTIES ENCOUNTERED
<br />HHIGH COULD HAVE BEEN FORESEEN HAD AN EXAMINATION BEEN MADE,
<br />WILL NOT BE ALLOWED.
<br />6. IT 15 THE RESPONSIBILITY OF THE CONTRACTOR TO NOTIFY THE
<br />ARCHITECT OF ANY DISCREPANCIES ENCOUNTERED ON THE PLANS OR IN
<br />EXISTING 51TE CONDITIONS PRIOR TO 505MI55ION OF BID.
<br />-f. COORDINATE WITH OTHER TRADES FOR ITEMS IN THEIR SCOPE OF WORK
<br />HHICH HOULD REQUIRE ELECTRICAL WORK (DISCONNECTION,
<br />RECONNECTION, ETC) AND ARE NOT INDICATED ON ELECTRICAL
<br />DRAWIN66.
<br />THESE NOTES APPLY TO ALL ELECTRICAL SHEETS.
<br />N35
<br />M2A
<br />INDEX
<br />EO.0 :
<br />ELECTRICAL PROJECT NOTES AND LEGEND
<br />H
<br />ELO
<br />ELECTRICAL SITE PLAN
<br />E
<br />EH
<br />PHOTOMETRIC 51TE PLAN
<br />E
<br />E1.2
<br />FIXTURE INFORMATION
<br />T
<br />E2.0 :
<br />LIGHTING AND POWER PLANS
<br />E3.0 :
<br />POHER R151 R DIACRAM
<br />E4.0 :
<br />ELECTRICAL SPECIFICATIONS
<br />CHEHAYE.B & ASSOCIATES, INC.
<br />CONSULTING PROFESSIONAL ENGINEERS
<br />ct
<br />3702 AZEELE ST. (813) 876-1415
<br />TAMPA, FL 33609 (fax) 876-0913
<br />LIC. #49521 SOUHEI M AYEB,, CERT. #7340