Laserfiche WebLink
-.---- ...-- _.L I_---_-_- <br />D <br />E <br />T <br />L <br />MENUBOARD <br />THREE 1" CONDUITS, <br />PROVIDE ONE I" CONDUIT WITH PULL WIRE TO TIME <br />GLOGK/GONTAGTOR PANEL. SEE "TIME <br />CLOCK/GONTACTOR PANEL" NOTE THIS SHEET. (1) I" <br />WITH PULL WIRE STUBBED UP AT ELECTRIC, PANEL <br />FOR FUTURE, AS A SPARE, AND (1) 1" WITH PULL WIRE '�! �100 <br />TO CONTINUOUS TO TELEPHONE BOARD. II j <br />CONCRETE FOOTING BY <br />LANDLORD. COORDINATE WITH <br />STRUCTURAL DRAWINGS FOR <br />ADDITIONAL INFORMATION <br />NOTE: SEE 51TE PLAN FOR LOCATION AND ORIENTATION. THIS DETAIL 15 <br />PROVIDED TO SHOW ELECTRICAL REQUIREMENT5 ONLY. <br />PREMENU BOARD <br />Del <br />E <br />/ <br />I- III COATS. 30°i <br />ONE I" CONDUIT WITH PULL WIRE' <br />T <br />TO TIME CLOLK/GONTAGTOR ' "T`'Y; <br />/� <br />PANEL. 5EE "TIME <br />GLOCK/GONTAGTOR PANEL" NOTE <br />1""'t <br />- - <br />- - <br />THI5 SHEET FOR POWER. AL50 <br />PROVIDE (1) In CONDUIT TO PANEL <br />L_ <br />LOCATION AS A SPARE, AND (1) 1" '�--- <br />WITH PULL WIRE TO CONTINUOUS <br />TO TELEPHONE BOARD. <br />CONCRETE FOOTING BY <br />LANDLORD. COORDINATE <br />NOTE: SEE 51TE PLAN FOR LOCATION AND <br />WITH STRUCTURAL DRAWIN65 <br />FOR ADDITIONAL <br />2 <br />ORIENTATION. TH15 DETAIL 15 PROVIDED TO SHOW <br />INFORMATION <br />ELECTRICAL REQUIREMENTS ONLY. <br />GL-EARANGE BAR <br />D <br />IF CLEARANCE BAR 15 ILLUMINATED, <br />ELECTRICAL CONTRACTOR 5HALL PROVIDE <br />T <br />ONE I" CONDUIT WITH PULL WIRE ROUTED BACK <br />TO ELECTRICAL PANEL IN TENANT SPACE <br />A <br />I <br />CONCRETE FOOTING BY LANDLORD. <br />COORDINATE WITH STRUCTURAL PRAWIN65 <br />L- <br />FOR ADDITIONAL INFORMATION <br />---{-----..... <br />('I� <br />CLEARANCE BAR <br />NOTE: SEE 51TE PLAN FOR LOCATION AND ORIENTATION. TH15 DETAIL 15 <br />PROVIDED TO SHOW ELECTRICAL RE61UIREMENT5 ONLY. <br />05G/5PEAKER BOAFRD <br />NOTE: <br />E <br />PROVIDE PULL WIRE IN ALL EMPTY <br />CONDUITS. <br />V ! <br />< <br />DRIVE THRU LANE <br />, ,E <br />. ,I <br />"� + <br />AI <br />I: i <br />3 <br />L_ <br />r ' <br />.. <br />j�11 <br />1. <br />I ; <br />FIA CONDUITS: <br />DETECTOR LOOP CENTERED ON�'I <br />DIGITAL ORDER SCREEN 2" <br />BELOW FINAL GRADE IN CONDUIT <br />I, <br />OR 5AWC.UT. PROVIDE ONE I" <br />r:~ r _ ^ <br />II <br />I CONDUIT FROM <br />CONDUIT FOR DETECTOR LOOP <br />I I <br />CANOPY UPLI644T <br />TO DIGITAL CONTROL BOX. <br />g i i <br />TO TIME CLOCK/CONTACTOR <br />PANEL. SEE "TIME <br />CLOCK/CONTACTOR PANEL" <br />NOTE TH15 SHEET. <br />TWO 1-1/2" CONDUITS FROM <br />05C/5PEAKER BOARD TO <br />41 <br />LOCATION AT THE DRIVE <br />-- *' <br />THRU WINDOW. AND ONE I" <br />CONDUIT TO ELECTRICAL <br />_ _ , J-,_ <br />'_ <br />_ _ _ _ _ _'----- _ _ <br />FBI <br />PANEL FOR POWER. <br />DIGITAL CONTROL BOX <br />WITH YXY CLEARANCE <br />AROUND IT. <br />NOTE: CONCRETE FOOTING BY <br />5EE 51TE PLAN FOR LOCATION AND LANDLORD. COORDINATE WITH <br />ORIENTATION. TH15 DETAIL 15 PROVIDED TO STRUCTURAL DRAWIN66 FOR <br />SHOW ELECTRICAL REQUIREMENT5 ONLY. ADDITIONAL INFORMATION. <br />KEY NOTE5 <br />5 <br />CLEARANCE BAR. SEE DETAIL #3 THIS SHEET. <br />I <br />O PROP05FD 5TARSUCKS PANEL LOCATIONS. <br />T <br />U3 PROVIDE ONE I" CONDUIT WITH PULLWIRE FROM <br />WEATHERPROOF JUNCTION BOX AT PROPOSED 516N <br />E <br />LOCATION AND RUN UNDERGROUND BACK TO "TIME <br />GLOCK/GONTACTOR PANEL" PROPOSED LOCATION <br />IN THE SPACE. SEE "TIME CLOCK/CONTACTOR, <br />PANEL" NOTE THIS SHEET. <br />® ELECTRICAL SERVICE LOCATION. SEE POWER RISER <br />DIAGRAM ON SHEET E3.0. <br />0 5EGONDARY POWER CONDUITS, FURN15HE0 AND <br />INSTALLED BY ELECTRICAL CONTRACTOR. SEE <br />POWER R15ER DIAGRAM ON SHEET E3.0. <br />TWO 2" GONDUIT5 WITH PULLWIRE BY ELECTRICAL <br />CONTRACTOR FOR TELEPHONE SERVICE. CONDUIT <br />TO BE STUBBED UP IN SPACE AT A LOCATION <br />IDENTIFIED BY TENANT. <br />O ONE 2" CONDUIT WITH PULLWIRE BY ELECTRICAL <br />CONTRACTOR FOR GABLE T.V. SERVICE. CONDUIT <br />TO BE STUBBED UP IN 5PAGE AT A LOCATION <br />IDENTIFIED BY TENANT. <br />�8 EXI5TIN6 POLE TO BE MODIFIED WITH 3-PH., <br />120/208V., POLE MOUNTED TRANSFORMERS BY <br />UTILITY COMPANY. REFER TO POWER RISER <br />DIAGRAM ON SHEET E3.0 FOR ADDITIONAL <br />DETAILS. VERIFY EXACT LOCATION AND <br />REOUIREMENT5 WITH OUG, SEE CONTACT <br />INFORMATION BELOW. <br />PRE MENU BOARD. SEE DETAIL #2 TH15 SHEET. <br />10 SPEAKER P05T ORDER CONFIRMATION SYSTEM <br />WITH DETECTABLE LOOP. SEE DETAIL #4 TH15 <br />SHEET. <br />II MENU BOARD SEE DETAIL #1 TH15 SHEET. <br />12 TERMINATE TELEPHONE CONDUITS AT PROPERTY <br />LINE. COORDINATE WITH AT4T PHONE COMPANY <br />REPRESENTATIVE, <br />13 TERMINATE GABLE CONDUITS AT PROPERTY LINE. <br />COORDINATE WITH UTILITY COMPANY <br />REPRESENTATIVE. <br />14 TELE/DATA STUB -UP PROP05ED LOCATION. SEE <br />SHEET E2.0 FOR LOCATION. <br />la 4 - #6, 1 - #5 E.G. IN 1-1/4" CONDUIT. <br />I6 OPTIG5 ORIENTATION FOR THE 51TE LIGHT FIXTURE. <br />17 FIXTURE 15 PROVIDED WITH DUAL SWITCHING <br />OPTION (D5) SEE FIXTURE SCHEDULE. <br />18 51TE POLE AND FIXTURE, SEE LIGHTING FIXTURE <br />SCHEDULE ON TH15 SHEET AND SHEET ELI FOR POLE <br />DETAIL. <br />Iq ONE CIRCUIT CONTROLLED VIA PHOTOCELL ON <br />TIMECLOGK OFF AND ONE CIRCUIT CONTROLLED <br />VIA PHOTOCELL 'ON', PHOTOCELL 'OFF'. <br />PATIO RECEPTACLE. EGIUAL TO INTERMATIC <br />WP-2000 WITH CFI, WEATHER RE515TANCE 20AMP <br />OUTLET. FIELD VERIFY EXACT LOCATION PRIOR TO <br />ROUGH -IN. INSTALLATION SHALL BE PER <br />MANUFACTURER RECOMMENDATION/IN5TRUGTIONS. <br />NOTES <br />cv I. CONDUIT RUN BELOW 6RADE SHALL BE PVG SCHEDULE 40. ELBOWS 2" AND <br />E LARGER SHALL BE 6ALVANIZED R1610 CONDUIT(5). RISERS SHALL BE RIGID <br />STEEL CONDUIT(5) "ERE EXP05ED TO OUTSIDE ELEMENTS. REFER TO <br />N SPECIFICATIONS. <br />E 2. ALL UNDER6ROUND 51TE CONDUIT SHALL BE BURIED A MINIMUM OF 36 INCHES <br />DEEP BELOW FIN15HED 6RADE TO TOP OF CONDUIT UNLE55 OTHERWISE NOTED. <br />3. PROVIDE COLOR TAPE FOR IDENTIFICATION AT 15 INCHES DEEP (ABOVE <br />A SERVICE CONDUIT RUNS) PER N.E.G. 300-5 (D) (3). <br />L_ 4. ALL TURNS SHALL BE MADE WITH LONG 5WEEP ELLS. <br />5. CONTRACTOR SHALL PROVIDE ALL EXCAVATING, AND BACK FILLING REQUIRED <br />FOR ALL NEW WORK IN�LUDIN6 FILL, COMPACTION, SURFACE, ETC. TO MEET ALL <br />REQUIREMENTS AS APPLICABLE FOR THE AREA. <br />6. PRIOR TO THE START OF CON5TRUGTION, CONTRACTOR SHALL DETERMINE THE <br />PRESENCE AND LOCATION OF ANY UNDERGROUND RACEWAYS 5001-1 AS <br />T TELEPHONE, ELECTRIC POWER, WATER, 6A5, 5EWA6E LINES, ETC. WHETHER <br />PREVIOUSLY EXI5TIN6 OR A5 INSTALLED BY OTHER TRADES, TO AVOID <br />E INTERFERENCE WITH ANY 5UGH 5Y5TEM. <br />�f. ALL 5PARE, EMPTY CONDUITS SHALL BE LABELED AS TO THEIR FUNCTION. <br />6. CONTRACTOR SHALL MAINTAIN AN A5-51JILT DIMENSIONAL DRAWING ON SITE <br />5HOWIN6 ALL UNDERGROUND SERVICE ROUTING AND TERMINATION POINT5. <br />q. CONTRACTOR SHALL MEET ON 51TE WITH REPRESENTATIVES OF THE UTILITY <br />COMPANIES INGLUDIN6, POWER, TELEPHONE, AND GABLE TO DETERMINE THE <br />FOLLOWING: (PRIOR TO BID AND PRIOR TO ROUGH IN). <br />POWER COMPANY: <br />A - VERIFY EXALT TRAN5FORMER(5) LOCATION PRIOR TO BID. <br />B - VERIFY PRIMARY CONDUIT WORK REQUIRED AND RE51PON50LITY PRIOR TO <br />BID. <br />C - VERIFY METERINS METHOD AND REQUIREMENTS, IF DIFFERENT <br />FROM WHAT 15 SHOWN ON THE DRAWIN65, NOTIFY ENGINEER IMMEDIATELY. <br />TELEPHPNE�Q21TANY: <br />A - OR16INIATION AND TERMINATION OF THE SERVICE CONDUITS. <br />B - INSTALLATION 5PECIFICATION5, 51ZE AND QUANTITY REQUIRED. HOWEVER; <br />MAINTAIN QUANTITY AND 51ZE5 SHOWN ON PLANS, IF IN EXCESS OF UTILITY <br />REQUIREMENT5. <br />RATE: <br />CONTRAGTOR5 FAILURE TO COMPLY WITH THESE COORDINATION PROCEDURES WILL <br />CONSTITUTE THE CONTRACTOR ASSUMING ALL COSTS ASSOCIATED WITH REPLACING <br />ANY AND ALL WORK ALREADY IN PLACE TO MEET UTILITY COMPANIES' RULES AND <br />REQUIREMENTS. <br />N8}3 <br />UTILITY COORDINATION: <br />TO THE BEST OF OUR ABILITY THE SERVICE HAS BEEN <br />COORDINATED WITH THE UTILITY COMPANY REPRESENTATIVE(5) FOR: <br />I - TRAN5FORMER(5) LOCATION. <br />2 - CUSTOMER RESPONSIBILITY. <br />3 - REQUESTED VOLTAGE * AVAILABILITY. <br />IT 15 THE CONTRACTOR RESPONSIBILITY TO REV151T THESE ITEMS WITH <br />UTILITY PROJECT ENGINEER TO VERIFY THAT THE CURRENT DE516N SHOWN <br />ON THE GON5TRUGTION DOCUMENT(5) ARE STILL IN COMPLIANCE WITH THE <br />UTILITY PLANS TO SERVICE TH15 SITE. <br />ANY C05T ASSOCIATED WITH UTILITY FEES SHALL BE THE RESPONSIBILITY <br />OF THE CONTRACTOR TO ADDRE55 WITH THE DEVELOPER, <br />TH15 COORDINATION SHALL BE A PART OF 51TE MEETIN6 TO BE SCHEDULED <br />BY THE CONTRACTOR WITH THE UTILITY PER50NNEL PRIOR TO THE START <br />OF THE PROJECT. <br />COORDINATION SHALL AL50 BE MADE WITH TELEPHONE AND GABLE <br />SERVICE REPRE5ENTATIVE(5) FOR VERIFICATION OF THEIR REG2UIREMENT5 <br />INGLUDIN6 POINT OF CONNECTION AND TERMINATION POINTS. <br />N55 <br />L_ I ONTI NO FIXTURE SGHEDUL_E <br />I <br />TYPE <br />MANUF. <br />CATALOG NO. <br />VOLT <br />LAMPS <br />L <br />MOUNTING <br />T <br />5A <br />LITHONIA <br />D5XI-LED-P&-4OK- <br />206 <br />LED <br />201 <br />T4M-MVOLT-VS-H5 <br />SB <br />LITHONIA <br />D5XI-LED414-4OK-- <br />208 <br />LED <br />241 <br />CONCRETE POLE <br />B0LT-D5 <br />25'-0" A.F.G. SEE <br />SHEET ELI <br />50 <br />LITHONIA <br />D5A-LED-PS-40K- <br />206 <br />LED <br />20-1 <br />FOR POLE DETAIL <br />BLL-MVOLT-05 <br />5D <br />LITHONIA <br />D5XI-LED-PI3-4OK- <br />208 <br />LED <br />231 <br />T5W-MV0L..T-D5-H5-Lg0 <br />GENERAL NOTES: <br />I. PROVIDE NECESSARY MOUNTING HARDWARE AND <br />4. FUSES SHALL BE INSTALLED AT THE BASE <br />ACCESSORIES FOR ALL FIXTURE-5. <br />OF POLE. <br />2. PROVIDE FUSES FOR ALL 51TE L16HTINI6 FIXTURES. <br />5. FIXTURE AND POLE FIN15H COLOR AS <br />5EL.ECTED BY ARCHITECT. <br />3. ALL FIXTURE SUBSTITUTIONS MUST BE SUBMITTED FOR <br />APPROVAL (E6lUAL5 ONLY). <br />NORTH E.LEGTR I GAL_ <br />51TE PLAN, <br />50ALE: I" = 20'-0" <br />5T6i38UC.K.S INTERIOR BUILD -OUT DOCU NT5: <br />COORDINATE WITH 5TARBUGK5 PROJECT MANAGER FOR <br />EXACT LOCATION OF THE TIME CLOCK/GONTAGTOR PANEL. <br />PROJECT SCOPE: <br />THE WORK SHOWN ON THESE DOCUMENTS REPRESENT THE <br />LANDLORD SCOPE OF WORK (MODIFIED SHELL DOCUMENT). <br />ALL INTERIOR WORK INGLUDIN6 INTERIOR LI6HTIN6, <br />ADDITIONAL PANELS, WIRIN6, ETC... IS PART OF TENANT <br />IMPROVEMENT DOCUMENT, THAT 15 DESIGNED AND <br />PERMITTED SEPARATELY. <br />UTILITY GONTAGTS <br />QWER COQMPANY: DUKE ENERGY <br />NAME: DARRYL F05HEE <br />PHONE No.: (721) 85q-4002 <br />EMAIL: DARRYL.F05HEE®DUKE-ENERGY.GOM <br />JELEPHONE COMPANY; FRONTIER <br />NAME: THOMAS FAULKNER <br />PHONE No.: 013) 348-3624 <br />EMAIL: THOMA5.FAULKNEROFTR.COM <br />CONTRACTOR SHALL NOTIFY EACH UTILITY COMPANY <br />REPRESENTATIVE LISTED ABOVE OF THE <br />PRE-GON5TRUGTION MEETING SCHEDULE. <br />CHEHAY,EB & ASSOCIATES, INC. <br />CONSULTING PROFESSIONAL EWINEERS <br />3702 AZEELE ST. <br />TAMPA, FL 33609 <br />LIC. #49521 <br />(813) 876-1415 <br />(fax) 876-091S <br />CERT. #7340 <br />