-.---- ...-- _.L I_---_-_-
<br />D
<br />E
<br />T
<br />L
<br />MENUBOARD
<br />THREE 1" CONDUITS,
<br />PROVIDE ONE I" CONDUIT WITH PULL WIRE TO TIME
<br />GLOGK/GONTAGTOR PANEL. SEE "TIME
<br />CLOCK/GONTACTOR PANEL" NOTE THIS SHEET. (1) I"
<br />WITH PULL WIRE STUBBED UP AT ELECTRIC, PANEL
<br />FOR FUTURE, AS A SPARE, AND (1) 1" WITH PULL WIRE '�! �100
<br />TO CONTINUOUS TO TELEPHONE BOARD. II j
<br />CONCRETE FOOTING BY
<br />LANDLORD. COORDINATE WITH
<br />STRUCTURAL DRAWINGS FOR
<br />ADDITIONAL INFORMATION
<br />NOTE: SEE 51TE PLAN FOR LOCATION AND ORIENTATION. THIS DETAIL 15
<br />PROVIDED TO SHOW ELECTRICAL REQUIREMENT5 ONLY.
<br />PREMENU BOARD
<br />Del
<br />E
<br />/
<br />I- III COATS. 30°i
<br />ONE I" CONDUIT WITH PULL WIRE'
<br />T
<br />TO TIME CLOLK/GONTAGTOR ' "T`'Y;
<br />/�
<br />PANEL. 5EE "TIME
<br />GLOCK/GONTAGTOR PANEL" NOTE
<br />1""'t
<br />- -
<br />- -
<br />THI5 SHEET FOR POWER. AL50
<br />PROVIDE (1) In CONDUIT TO PANEL
<br />L_
<br />LOCATION AS A SPARE, AND (1) 1" '�---
<br />WITH PULL WIRE TO CONTINUOUS
<br />TO TELEPHONE BOARD.
<br />CONCRETE FOOTING BY
<br />LANDLORD. COORDINATE
<br />NOTE: SEE 51TE PLAN FOR LOCATION AND
<br />WITH STRUCTURAL DRAWIN65
<br />FOR ADDITIONAL
<br />2
<br />ORIENTATION. TH15 DETAIL 15 PROVIDED TO SHOW
<br />INFORMATION
<br />ELECTRICAL REQUIREMENTS ONLY.
<br />GL-EARANGE BAR
<br />D
<br />IF CLEARANCE BAR 15 ILLUMINATED,
<br />ELECTRICAL CONTRACTOR 5HALL PROVIDE
<br />T
<br />ONE I" CONDUIT WITH PULL WIRE ROUTED BACK
<br />TO ELECTRICAL PANEL IN TENANT SPACE
<br />A
<br />I
<br />CONCRETE FOOTING BY LANDLORD.
<br />COORDINATE WITH STRUCTURAL PRAWIN65
<br />L-
<br />FOR ADDITIONAL INFORMATION
<br />---{-----.....
<br />('I�
<br />CLEARANCE BAR
<br />NOTE: SEE 51TE PLAN FOR LOCATION AND ORIENTATION. TH15 DETAIL 15
<br />PROVIDED TO SHOW ELECTRICAL RE61UIREMENT5 ONLY.
<br />05G/5PEAKER BOAFRD
<br />NOTE:
<br />E
<br />PROVIDE PULL WIRE IN ALL EMPTY
<br />CONDUITS.
<br />V !
<br /><
<br />DRIVE THRU LANE
<br />, ,E
<br />. ,I
<br />"� +
<br />AI
<br />I: i
<br />3
<br />L_
<br />r '
<br />..
<br />j�11
<br />1.
<br />I ;
<br />FIA CONDUITS:
<br />DETECTOR LOOP CENTERED ON�'I
<br />DIGITAL ORDER SCREEN 2"
<br />BELOW FINAL GRADE IN CONDUIT
<br />I,
<br />OR 5AWC.UT. PROVIDE ONE I"
<br />r:~ r _ ^
<br />II
<br />I CONDUIT FROM
<br />CONDUIT FOR DETECTOR LOOP
<br />I I
<br />CANOPY UPLI644T
<br />TO DIGITAL CONTROL BOX.
<br />g i i
<br />TO TIME CLOCK/CONTACTOR
<br />PANEL. SEE "TIME
<br />CLOCK/CONTACTOR PANEL"
<br />NOTE TH15 SHEET.
<br />TWO 1-1/2" CONDUITS FROM
<br />05C/5PEAKER BOARD TO
<br />41
<br />LOCATION AT THE DRIVE
<br />-- *'
<br />THRU WINDOW. AND ONE I"
<br />CONDUIT TO ELECTRICAL
<br />_ _ , J-,_
<br />'_
<br />_ _ _ _ _ _'----- _ _
<br />FBI
<br />PANEL FOR POWER.
<br />DIGITAL CONTROL BOX
<br />WITH YXY CLEARANCE
<br />AROUND IT.
<br />NOTE: CONCRETE FOOTING BY
<br />5EE 51TE PLAN FOR LOCATION AND LANDLORD. COORDINATE WITH
<br />ORIENTATION. TH15 DETAIL 15 PROVIDED TO STRUCTURAL DRAWIN66 FOR
<br />SHOW ELECTRICAL REQUIREMENT5 ONLY. ADDITIONAL INFORMATION.
<br />KEY NOTE5
<br />5
<br />CLEARANCE BAR. SEE DETAIL #3 THIS SHEET.
<br />I
<br />O PROP05FD 5TARSUCKS PANEL LOCATIONS.
<br />T
<br />U3 PROVIDE ONE I" CONDUIT WITH PULLWIRE FROM
<br />WEATHERPROOF JUNCTION BOX AT PROPOSED 516N
<br />E
<br />LOCATION AND RUN UNDERGROUND BACK TO "TIME
<br />GLOCK/GONTACTOR PANEL" PROPOSED LOCATION
<br />IN THE SPACE. SEE "TIME CLOCK/CONTACTOR,
<br />PANEL" NOTE THIS SHEET.
<br />® ELECTRICAL SERVICE LOCATION. SEE POWER RISER
<br />DIAGRAM ON SHEET E3.0.
<br />0 5EGONDARY POWER CONDUITS, FURN15HE0 AND
<br />INSTALLED BY ELECTRICAL CONTRACTOR. SEE
<br />POWER R15ER DIAGRAM ON SHEET E3.0.
<br />TWO 2" GONDUIT5 WITH PULLWIRE BY ELECTRICAL
<br />CONTRACTOR FOR TELEPHONE SERVICE. CONDUIT
<br />TO BE STUBBED UP IN SPACE AT A LOCATION
<br />IDENTIFIED BY TENANT.
<br />O ONE 2" CONDUIT WITH PULLWIRE BY ELECTRICAL
<br />CONTRACTOR FOR GABLE T.V. SERVICE. CONDUIT
<br />TO BE STUBBED UP IN 5PAGE AT A LOCATION
<br />IDENTIFIED BY TENANT.
<br />�8 EXI5TIN6 POLE TO BE MODIFIED WITH 3-PH.,
<br />120/208V., POLE MOUNTED TRANSFORMERS BY
<br />UTILITY COMPANY. REFER TO POWER RISER
<br />DIAGRAM ON SHEET E3.0 FOR ADDITIONAL
<br />DETAILS. VERIFY EXACT LOCATION AND
<br />REOUIREMENT5 WITH OUG, SEE CONTACT
<br />INFORMATION BELOW.
<br />PRE MENU BOARD. SEE DETAIL #2 TH15 SHEET.
<br />10 SPEAKER P05T ORDER CONFIRMATION SYSTEM
<br />WITH DETECTABLE LOOP. SEE DETAIL #4 TH15
<br />SHEET.
<br />II MENU BOARD SEE DETAIL #1 TH15 SHEET.
<br />12 TERMINATE TELEPHONE CONDUITS AT PROPERTY
<br />LINE. COORDINATE WITH AT4T PHONE COMPANY
<br />REPRESENTATIVE,
<br />13 TERMINATE GABLE CONDUITS AT PROPERTY LINE.
<br />COORDINATE WITH UTILITY COMPANY
<br />REPRESENTATIVE.
<br />14 TELE/DATA STUB -UP PROP05ED LOCATION. SEE
<br />SHEET E2.0 FOR LOCATION.
<br />la 4 - #6, 1 - #5 E.G. IN 1-1/4" CONDUIT.
<br />I6 OPTIG5 ORIENTATION FOR THE 51TE LIGHT FIXTURE.
<br />17 FIXTURE 15 PROVIDED WITH DUAL SWITCHING
<br />OPTION (D5) SEE FIXTURE SCHEDULE.
<br />18 51TE POLE AND FIXTURE, SEE LIGHTING FIXTURE
<br />SCHEDULE ON TH15 SHEET AND SHEET ELI FOR POLE
<br />DETAIL.
<br />Iq ONE CIRCUIT CONTROLLED VIA PHOTOCELL ON
<br />TIMECLOGK OFF AND ONE CIRCUIT CONTROLLED
<br />VIA PHOTOCELL 'ON', PHOTOCELL 'OFF'.
<br />PATIO RECEPTACLE. EGIUAL TO INTERMATIC
<br />WP-2000 WITH CFI, WEATHER RE515TANCE 20AMP
<br />OUTLET. FIELD VERIFY EXACT LOCATION PRIOR TO
<br />ROUGH -IN. INSTALLATION SHALL BE PER
<br />MANUFACTURER RECOMMENDATION/IN5TRUGTIONS.
<br />NOTES
<br />cv I. CONDUIT RUN BELOW 6RADE SHALL BE PVG SCHEDULE 40. ELBOWS 2" AND
<br />E LARGER SHALL BE 6ALVANIZED R1610 CONDUIT(5). RISERS SHALL BE RIGID
<br />STEEL CONDUIT(5) "ERE EXP05ED TO OUTSIDE ELEMENTS. REFER TO
<br />N SPECIFICATIONS.
<br />E 2. ALL UNDER6ROUND 51TE CONDUIT SHALL BE BURIED A MINIMUM OF 36 INCHES
<br />DEEP BELOW FIN15HED 6RADE TO TOP OF CONDUIT UNLE55 OTHERWISE NOTED.
<br />3. PROVIDE COLOR TAPE FOR IDENTIFICATION AT 15 INCHES DEEP (ABOVE
<br />A SERVICE CONDUIT RUNS) PER N.E.G. 300-5 (D) (3).
<br />L_ 4. ALL TURNS SHALL BE MADE WITH LONG 5WEEP ELLS.
<br />5. CONTRACTOR SHALL PROVIDE ALL EXCAVATING, AND BACK FILLING REQUIRED
<br />FOR ALL NEW WORK IN�LUDIN6 FILL, COMPACTION, SURFACE, ETC. TO MEET ALL
<br />REQUIREMENTS AS APPLICABLE FOR THE AREA.
<br />6. PRIOR TO THE START OF CON5TRUGTION, CONTRACTOR SHALL DETERMINE THE
<br />PRESENCE AND LOCATION OF ANY UNDERGROUND RACEWAYS 5001-1 AS
<br />T TELEPHONE, ELECTRIC POWER, WATER, 6A5, 5EWA6E LINES, ETC. WHETHER
<br />PREVIOUSLY EXI5TIN6 OR A5 INSTALLED BY OTHER TRADES, TO AVOID
<br />E INTERFERENCE WITH ANY 5UGH 5Y5TEM.
<br />�f. ALL 5PARE, EMPTY CONDUITS SHALL BE LABELED AS TO THEIR FUNCTION.
<br />6. CONTRACTOR SHALL MAINTAIN AN A5-51JILT DIMENSIONAL DRAWING ON SITE
<br />5HOWIN6 ALL UNDERGROUND SERVICE ROUTING AND TERMINATION POINT5.
<br />q. CONTRACTOR SHALL MEET ON 51TE WITH REPRESENTATIVES OF THE UTILITY
<br />COMPANIES INGLUDIN6, POWER, TELEPHONE, AND GABLE TO DETERMINE THE
<br />FOLLOWING: (PRIOR TO BID AND PRIOR TO ROUGH IN).
<br />POWER COMPANY:
<br />A - VERIFY EXALT TRAN5FORMER(5) LOCATION PRIOR TO BID.
<br />B - VERIFY PRIMARY CONDUIT WORK REQUIRED AND RE51PON50LITY PRIOR TO
<br />BID.
<br />C - VERIFY METERINS METHOD AND REQUIREMENTS, IF DIFFERENT
<br />FROM WHAT 15 SHOWN ON THE DRAWIN65, NOTIFY ENGINEER IMMEDIATELY.
<br />TELEPHPNE�Q21TANY:
<br />A - OR16INIATION AND TERMINATION OF THE SERVICE CONDUITS.
<br />B - INSTALLATION 5PECIFICATION5, 51ZE AND QUANTITY REQUIRED. HOWEVER;
<br />MAINTAIN QUANTITY AND 51ZE5 SHOWN ON PLANS, IF IN EXCESS OF UTILITY
<br />REQUIREMENT5.
<br />RATE:
<br />CONTRAGTOR5 FAILURE TO COMPLY WITH THESE COORDINATION PROCEDURES WILL
<br />CONSTITUTE THE CONTRACTOR ASSUMING ALL COSTS ASSOCIATED WITH REPLACING
<br />ANY AND ALL WORK ALREADY IN PLACE TO MEET UTILITY COMPANIES' RULES AND
<br />REQUIREMENTS.
<br />N8}3
<br />UTILITY COORDINATION:
<br />TO THE BEST OF OUR ABILITY THE SERVICE HAS BEEN
<br />COORDINATED WITH THE UTILITY COMPANY REPRESENTATIVE(5) FOR:
<br />I - TRAN5FORMER(5) LOCATION.
<br />2 - CUSTOMER RESPONSIBILITY.
<br />3 - REQUESTED VOLTAGE * AVAILABILITY.
<br />IT 15 THE CONTRACTOR RESPONSIBILITY TO REV151T THESE ITEMS WITH
<br />UTILITY PROJECT ENGINEER TO VERIFY THAT THE CURRENT DE516N SHOWN
<br />ON THE GON5TRUGTION DOCUMENT(5) ARE STILL IN COMPLIANCE WITH THE
<br />UTILITY PLANS TO SERVICE TH15 SITE.
<br />ANY C05T ASSOCIATED WITH UTILITY FEES SHALL BE THE RESPONSIBILITY
<br />OF THE CONTRACTOR TO ADDRE55 WITH THE DEVELOPER,
<br />TH15 COORDINATION SHALL BE A PART OF 51TE MEETIN6 TO BE SCHEDULED
<br />BY THE CONTRACTOR WITH THE UTILITY PER50NNEL PRIOR TO THE START
<br />OF THE PROJECT.
<br />COORDINATION SHALL AL50 BE MADE WITH TELEPHONE AND GABLE
<br />SERVICE REPRE5ENTATIVE(5) FOR VERIFICATION OF THEIR REG2UIREMENT5
<br />INGLUDIN6 POINT OF CONNECTION AND TERMINATION POINTS.
<br />N55
<br />L_ I ONTI NO FIXTURE SGHEDUL_E
<br />I
<br />TYPE
<br />MANUF.
<br />CATALOG NO.
<br />VOLT
<br />LAMPS
<br />L
<br />MOUNTING
<br />T
<br />5A
<br />LITHONIA
<br />D5XI-LED-P&-4OK-
<br />206
<br />LED
<br />201
<br />T4M-MVOLT-VS-H5
<br />SB
<br />LITHONIA
<br />D5XI-LED414-4OK--
<br />208
<br />LED
<br />241
<br />CONCRETE POLE
<br />B0LT-D5
<br />25'-0" A.F.G. SEE
<br />SHEET ELI
<br />50
<br />LITHONIA
<br />D5A-LED-PS-40K-
<br />206
<br />LED
<br />20-1
<br />FOR POLE DETAIL
<br />BLL-MVOLT-05
<br />5D
<br />LITHONIA
<br />D5XI-LED-PI3-4OK-
<br />208
<br />LED
<br />231
<br />T5W-MV0L..T-D5-H5-Lg0
<br />GENERAL NOTES:
<br />I. PROVIDE NECESSARY MOUNTING HARDWARE AND
<br />4. FUSES SHALL BE INSTALLED AT THE BASE
<br />ACCESSORIES FOR ALL FIXTURE-5.
<br />OF POLE.
<br />2. PROVIDE FUSES FOR ALL 51TE L16HTINI6 FIXTURES.
<br />5. FIXTURE AND POLE FIN15H COLOR AS
<br />5EL.ECTED BY ARCHITECT.
<br />3. ALL FIXTURE SUBSTITUTIONS MUST BE SUBMITTED FOR
<br />APPROVAL (E6lUAL5 ONLY).
<br />NORTH E.LEGTR I GAL_
<br />51TE PLAN,
<br />50ALE: I" = 20'-0"
<br />5T6i38UC.K.S INTERIOR BUILD -OUT DOCU NT5:
<br />COORDINATE WITH 5TARBUGK5 PROJECT MANAGER FOR
<br />EXACT LOCATION OF THE TIME CLOCK/GONTAGTOR PANEL.
<br />PROJECT SCOPE:
<br />THE WORK SHOWN ON THESE DOCUMENTS REPRESENT THE
<br />LANDLORD SCOPE OF WORK (MODIFIED SHELL DOCUMENT).
<br />ALL INTERIOR WORK INGLUDIN6 INTERIOR LI6HTIN6,
<br />ADDITIONAL PANELS, WIRIN6, ETC... IS PART OF TENANT
<br />IMPROVEMENT DOCUMENT, THAT 15 DESIGNED AND
<br />PERMITTED SEPARATELY.
<br />UTILITY GONTAGTS
<br />QWER COQMPANY: DUKE ENERGY
<br />NAME: DARRYL F05HEE
<br />PHONE No.: (721) 85q-4002
<br />EMAIL: DARRYL.F05HEE®DUKE-ENERGY.GOM
<br />JELEPHONE COMPANY; FRONTIER
<br />NAME: THOMAS FAULKNER
<br />PHONE No.: 013) 348-3624
<br />EMAIL: THOMA5.FAULKNEROFTR.COM
<br />CONTRACTOR SHALL NOTIFY EACH UTILITY COMPANY
<br />REPRESENTATIVE LISTED ABOVE OF THE
<br />PRE-GON5TRUGTION MEETING SCHEDULE.
<br />CHEHAY,EB & ASSOCIATES, INC.