2
<br />3
<br />4
<br />E
<br />Col
<br />C
<br />B
<br />A
<br />L" ', t
<br />M�
<br />u�►
<br />N T N,OTt
<br />SYMBOL
<br />DESCRIPTION
<br />SYMBOL
<br />DESCRIPTION
<br />1. REFERENCE THE SPECIFICATIONS FOR MATERIAL AND EQUIPMENT INSTALLATION
<br />STANDARDS.
<br />CA - COMPRESSED AIR
<br />- -
<br />= - =AV= - - —
<br />- ACID VENT
<br />AFF
<br />-ABOVE FINISH FLOOR
<br />2. THE PLUMBING INSTALLATION SHALL COMPLY WITH ALL STATE AND LOCAL CODES.
<br />AW
<br />-ACID WASTE
<br />AVT_—
<br />- ACID WASTE
<br />AV
<br />- ACID VENT
<br />3. UTILITIES AND SERVICES INDICATED ARE TAKEN FROM VARIOUS OLD AND NEW
<br />—
<br />— _ —AW_- - - —
<br />- BELOW GROUND ACID WASTE
<br />CO2
<br />- CARBON DIOXIDE
<br />SURVEYS,
<br />AS -BUILT RECORDS AND FIELD INVESTIGATIONS, UNFORSEEN CONDITIONS
<br />— —
<br />—
<br />CO2
<br />- CARBON DIOXIDE
<br />CB
<br />CD
<br />- CATCH BASIN
<br />- CONDENSATE DRAIN
<br />PROBABLY
<br />EXIST AND NEW WORK MAY NOT BE FIELD LOCATED EXACTLY AS SHOWN ON
<br />CFH
<br />- CUBIC FEET PER HOUR
<br />DRAWINGS.
<br />COOPERATION WITH OTHER TRADES IN ROUTING AND BURIAL DEPTHS, AS
<br />CA—___—_—_
<br />- COMPRESSED AIR
<br />CO
<br />-CLEANOUT
<br />DETERMINED
<br />DURING CONSTRUCTION, WILL BE NECESSARY.
<br />CD
<br />- ABOVE GROUND CONDENSATE DRAIN
<br />CONT
<br />- CONTINUATION
<br />4. FIELD
<br />VERIFY EXISTING INSTALLATIONS. MODIFY EXISTING PLUMBING SYSTEMS, WHICH
<br />_ -
<br />- - -CD— - = —
<br />-BELOW GROUND CONDENSATE DRAIN
<br />CW
<br />DI
<br />- DOMESTIC COLD WATER
<br />- DEIONIZED WATER
<br />ARE TO REMAIN ACTIVE, TO FACILITATE RECONNECTION AND EXTENSION OF THE NEW
<br />DA
<br />- DENTAL AIR
<br />DN
<br />- DOWN
<br />WORK.
<br />DI
<br />- DEIONIZED WATER
<br />DS
<br />DWG
<br />- DOWNSPOUT
<br />- DRAWING
<br />5. NOTIFY
<br />OWNER AT LEAST 72 HOURS PRIOR TO INTERRUPTING EXISTING SERVICE.
<br />DV
<br />-DENTAL VACUUM
<br />EXIST
<br />-EXISTING
<br />SCHEDULE DISCONNECTION AND TIE-INS TO MINIMIZE DISRUPTION OF SERVICES.
<br />OF
<br />- DEGREE FAHRENHEIT
<br />SERVICES
<br />ARE NOT TO BE LEFT DISRUPTED DURING NON -NORMAL CONTRACTOR
<br />DOMESTIC COLD WATER
<br />WORKING HOURS.
<br />FCO
<br />- FLOOR CLEANOUT
<br />DOMESTIC HOT WATER
<br />FD
<br />- FLOOR DRAIN
<br />FOF
<br />-FUEL OIL FILL
<br />6. PLANS
<br />ARE NOT COMPLETELY TO SCALE. PIPE ROUTING SHOWN IS SCHEMATIC AND IS
<br />DOMESTIC HOT WATER RETURN
<br />FOG
<br />- FUEL OIL GAGE
<br />NOT
<br />INTENDED TO INDICATE EXACT ROUTING. CONTRACTOR SHALL PROVIDE ANY
<br />FOF
<br />- FUEL OIL FILL
<br />FOR
<br />- FUEL OIL RETURN
<br />ADDITIONAL OFFSETS AND FITTINGS REQUIRED FOR PROPER INSTALLATION AND TO
<br />FO
<br />FUEL OIL GAGE
<br />FOS
<br />- FUEL OIL SUPPLY
<br />MAINTAIN CLEARANCES. VERIFY STRUCTURAL, MECHANICAL AND ELECTRICAL
<br />FOV
<br />- FUEL OIL VENT
<br />INSTALLATIONS
<br />AND OTHER POTENTIAL OBSTRUCTIONS AND ROUTE PIPING TO AVOID
<br />FOR
<br />- FUEL OIL RETURN
<br />FS
<br />- FLOOR SINK
<br />INTERFERENCES.
<br />FOS
<br />- FUEL OIL SUPPLY
<br />G
<br />-GAS
<br />7. PROVIDE
<br />ALL OFFSETS AND FITTINGS AND MAKE CONNECTION TO SITE UTILITIES.
<br />GPH
<br />- GALLONS PER HOUR
<br />�FOV-" - - -
<br />-FUEL OIL VENT
<br />GPM
<br />- GALLONS PER MINUTE
<br />G
<br />-GAS
<br />GR
<br />- KITCHEN WASTE (GREASE)
<br />8. CONCEAL
<br />PIPING ABOVE CEILINGS, WITHIN WALLS OR CHASES EXCEPT IN MECHANICAL
<br />HB
<br />- HOSE BIBB
<br />ROOMS
<br />OR AS SPECIFICALLY NOTED.
<br />GR
<br />- KITCHEN WASTE (GREASE)
<br />HD
<br />- HUB DRAIN
<br />MA
<br />- MEDICAL COMPRESSED AIR
<br />HW
<br />- DOMESTIC HOT WATER
<br />9- PROVIDE
<br />ACCESS PANELS FOR ALL VALVES CONCEALED IN WAILS OR ABOVE NOW
<br />HWR
<br />- DOMESTIC HOT WATER RETICULATING
<br />ACCESSIBLE CEILINGS.
<br />MV
<br />- MEDICAL VACUUM
<br />IE
<br />- INVERT ELEVATION
<br />NI
<br />-NITROGEN
<br />IW
<br />-INDIRECT WASTE
<br />10. SLEEVE AND/OR FIRESTOP ALL PENETRATIONS THROUGH RATED WALLS, CEILINGS, AND
<br />KW
<br />KW
<br />-KILOWATT
<br />FLOORS WITH U/L LISTED ASSEMBLIES, FIRESTOP ASSEMBLIES SHALL BE EQUAL TO OR
<br />N20
<br />- NITROUS OXIDE
<br />LBSOX
<br />- POUNDS
<br />EXCEED THE RATING OF THE WALL, CEILING OR FLOOR. SEE ARCHITECTURAL DRAWINGS
<br />-OXYGEN
<br />MA
<br />- MEDICAL AIR
<br />FOR FINAL FINISHES.
<br />S
<br />- ABOVE GROUND SANITARY
<br />MV
<br />MH
<br />- MEDICAL VACUUM
<br />-MANHOLE
<br />11, FLASH AND COUNTER -FLASH ROOF PENETRATIONS. SEE ARCHITECTURAL DRAWINGS
<br />-S- - - = w
<br />-BELOW GROUND SANITARY
<br />NI
<br />- NITROGEN
<br />FOR DETAILS.
<br />_
<br />- - - - - - - -
<br />- SANITARY VENT
<br />N20
<br />- NITROUS OXIDE
<br />12. WHEN BEAM SLEEVE PENETRATIONS ARE NECESSARY, COORDINATE PENETRATIONS
<br />NC
<br />- NORMALLY CLOSED
<br />WITH ALL TRADES, THE ARCHITECT AND THE STRUCTURAL ENGINEER.
<br />ST
<br />- ABOVE GROUND STORM
<br />NIC
<br />- NOT IN CONTRACT
<br />- -
<br />- - =ST= - - -
<br />- BELOW GROUND STORM
<br />NO
<br />- NORMALLY OPEN
<br />13. PROVIDE
<br />FOUNDATION PAD PENETRATION SLEEVES, ALLOW 1" MINIMUM CLEARANCE
<br />STO
<br />- OVERFLOW STORM DRAIN
<br />NP
<br />NTS
<br />- NON -POTABLE WATER
<br />- NOT TO SCALE
<br />BETWEEN
<br />SLEEVE INSIDE SURFACE AND PIPE EXTERIOR.
<br />- - -STO- - - -
<br />- BELOW GROUND OVERFLOW STORM
<br />OD
<br />OX
<br />- OUTSIDE DIAMETER
<br />-OXYGEN
<br />14. SEE
<br />ARCHITECTURAL DRAWINGS FOR FIXTURE LOCATIONS AND MOUNTING HEIGHTS.
<br />= SV=_
<br />- SOFT COLD WATER
<br />PRV
<br />- PRESSURE REDUCING VALVE
<br />15. PROVIDE
<br />AUTOMATIC TRAP PRIMERS FOR FLOOR DRAIN TRAP SEALS.
<br />Mom-
<br />-WATER METER
<br />PSI
<br />- POUNDS PER SQUARE INCH
<br />PVC
<br />- POLYVINYL CHLORIDE PIPE
<br />16. PROVIDE
<br />AN AIR GAP, WHEN REQUIRED BY CODE, SERVING INDIVIDUAL FIXTURES,
<br />'�--
<br />— —
<br />- HOSE BIBB OR WALL HYDRANT
<br />RD
<br />- ROOF DRAIN
<br />DEVICES,
<br />APPLIANCES AND APPARATUS.
<br />RPBP
<br />- REDUCED PRESSURE BACKFLOW PREVENTE
<br />COI
<br />—
<br />- CLEAN OUT PLUG
<br />S
<br />- SANITARY
<br />SF
<br />- SQUARE FEET
<br />17. ALL EXPOSED PIPE: AND FITTINGS IN FINISHED AREAS SHALL BE CHROME PLATED.
<br />CO (i—
<br />- WALL CLEANOUT
<br />SH
<br />- SHEET
<br />18. MOUNT HOSE BIBBS 24" ABOVE FINISHED GRADE, UNLESS OTHERWISE NOTED.
<br />Coll
<br />- WALL CLEANOUT
<br />ST
<br />- STORM
<br />Co
<br />�
<br />- FLOOR CLEAN OUT
<br />STO
<br />SW
<br />- OVERFLOW STORM DRAIN
<br />- SOFT COLD WATER
<br />19. PROVIDE
<br />CLEANOUTS IN ACCORDANCE WITH ALL STATE AND LOCAL CODES. INSTALL
<br />V
<br />-VENT
<br />CLEANOUT
<br />WITH COVER FLUSH TO FINISH SURFACE.
<br />FD
<br />913FD OC
<br />- FLOOR DRAIN
<br />VC
<br />-VACUUM CLEANING
<br />(0")-
<br />ROOF DRAIN
<br />VTR
<br />-VENT THRU ROOF
<br />20. COORDINATE EXACT FLOOR DRAIN LOCATIONS WITH ARCHITECTURAL DRAWINGS. SET
<br />WCO
<br />-WALL CLEANOUT
<br />FLOOR
<br />DRAINS BELOW FINISHED FLOOR TO ALLOW FOR FLOOR SLOPING TO THE DRAIN.
<br />FS M
<br />- FLOOR SINK
<br />WTR
<br />- WATER
<br />21. COORDINATE
<br />PIPING WITH ALL ELECTRICAL EQUIPMENT (PANELS, TRANSFORMERS,
<br />-SHUT-OFF VALVE IN VALVE BOX
<br />ETC.) PRIOR TO ANY INSTALLATION. DO NOT ROUTE ANY PIPING OVER ANY ELECTRICAL
<br />PANELS UNDER ANY CIRCUMSTANCES. ANY PIPING RUN OVER PANELS SHALL BE RE-
<br />DS ' CO DE
<br />- SHUTOFF VALVE
<br />ROUTED AT NO ADDITIONAL COST.
<br />BALL VALVE'
<br />22. ALL
<br />WALL MOUNTED LAVATORIES SHALL BE ATTACHED TO FLOOR MOUNTED CARRIER
<br />-w--
<br />-CALIBRATED BALANCING VALVE
<br />DESIGNED
<br />TO WITHSTAND A VERTICAL LOAD OF 250 POUNDS ON THE FRONT OF THE
<br />• FLORIDA BUILDING CODE 6TH EDITION - 2017 EDITION
<br />FIXTURE.
<br />- CHECK VALVE (SWING)
<br />NFPA #99,
<br />HEALTHCARE FACILITIES CODE - 2015
<br />PRESSURE REDUCING VALVE
<br />EDITION.
<br />23. PROVIDE
<br />SANITARY WASTE, VENT, DOMESTIC WATER, ETC. ROUGH -IN AND MAKE FINAL
<br />• GUIDELINES FOR DESIGN AND CONSTRUCTION.
<br />CONNECTIONS (TO INCLUDE PROVIDING ALL NECESSARY RELATED STOPS, VALVES,
<br />SOLENOID OPERATED VALVE
<br />FLORIDA HEALTHCARE FACILITIES - 2014 EDITION.
<br />TRAPS,
<br />ETC. AND MAKE READY FOR USE) TO ALL EQUIPMENT, WHETHER FURNISHED BY
<br />—
<br />- REDUCED PRESSURE BACKFLOW PREVENTER
<br />ALL LOCAL CODES - LATEST EDITION.
<br />THIS CONTRACTOR OR FURNISHED BY OTHERS.
<br />- RELIEF OR SAFETY VALVE
<br />24. PROVIDE
<br />CERTIFIED COPY OF MEDICAL GAS TEST REPORT AT FINAL A.H.C.A.
<br />INSPECTION.
<br />---- DFI — —
<br />- GAS COCK
<br />�,u ""
<br />----
<br />- GAS PRESSURE REGULATOR.'
<br />E C
<br />- SHUTOFF VALVE ON RISER
<br />SHEET
<br />DESCRIPTION
<br />ISSUED
<br />r-C
<br />- GAS COCK ON RISER
<br />Pool
<br />GENERAL PLUMBING INFORMATION
<br />Yes
<br />�r---
<br />- CONNECTION, TOP
<br />P100
<br />DEMOLITION PLAN - PLUMBING
<br />Yes
<br />P101
<br />DEMOLITION PLAN - MEDICAL GAS
<br />Yes
<br />`r
<br />- CONNECTION, BOTTOM
<br />P102
<br />NEW CONSTRUCTION PLAN - GRAVITY
<br />Yes
<br />P103
<br />NEW CONSTRUCTION PLAN - GRAVITY ALT.
<br />Yes
<br />C - ELBOW, TURNED DOWN
<br />- ELBOW, TURNED UP
<br />P104
<br />NEW CONSTRUCTION PLAN - PRESSURE
<br />Yes
<br />P105
<br />NEW CONSTRUCTION PLAN - PRESSURE ALT.
<br />Yes
<br />- TEE, TURNED UP
<br />P106
<br />NEW CONSTRUCTION PLAN - MEDICAL GAS
<br />Yes
<br />- TEE, TURNED DOWN
<br />P107
<br />NEW CONSTRUCTION PLAN - MEDICAL GAS ALT.
<br />Yes
<br />P201
<br />PLUMBING DETAILS
<br />Yes
<br />C
<br />-CAP
<br />P202
<br />PLUMBING DETAILS
<br />Yes
<br />- DIRECTION OF FLOW
<br />P301
<br />PLUMBING RISER DIAGRAMS
<br />Yes
<br />om AP XX - ALARM PANEL
<br />MAP-XX
<br />- MASTER ALARM PANEL
<br />l MGO-XX
<br />- MEDICAL GAS OUTLET
<br />CIXIXI1tx
<br />MGV-XX
<br />- MEDICAL GAS VALVE BOX
<br />-----.-
<br />- CONNECT TO EXISTING
<br />Q--a.-
<br />- DEMOLISH TO POINT INDICATED
<br />Q-
<br />REVISION REFERENCE
<br />1
<br />- DETAIL REFERENCE: TOP -DETAIL#,
<br />P2.01
<br />BOTTOM -DRAWING# SHOWN ON
<br />NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT
<br />PERTAIN TO THIS PROJECT
<br />I Ste- -I SINK
<br />SINGLE COMPARTMENT SELF RIMMING SINK CONSTRUCTED OF TYPE 30218-8 STAINLESS STEEL, 22"
<br />X 19" X 7-1/2" DEEP. INTERIOR AND TOP SURFACES SHALL BE POLISHED TO A HIGH LUSTER FINISH,
<br />PROVIDE SINK WITH STAINLESS STEEL CRUMB CUP STRAINER, PROVIDE FIXTURE PUNCHED FOR
<br />3-HOLE FAUCET INSTALLATION ON 4-INCH CENTERS.
<br />8-INCH WIDESPREAD COMBINATION CHROME PLATED BRASS FAUCET, WITH RIGID GOOSENECK (5-3/8"
<br />WIDE) SPOUT AND 2.0 GPM LAMINAR FLOW REGULATOR, VANDAL RESISTANT 4-INCH WRIST BLADE
<br />HANDLES WITH COLOR CODED INDEXES AND RENEWABLE SEATS IN MONEL, OUTLET OF SPOUT TO BE
<br />MINIMUM OF 5- INCHES ABOVE RIM OF FIXTURE.
<br />3/8 INCH I.P.S. CHROME PLATED ANGLE SUPPLY, LOOSE KEY STOP, REDUCER, WROUGHT BRASS
<br />DEEP BELL FLANGE ESCUTCHEON AND 112" CHROME PLATED COPPER EXTENSION TUBE WITH SWEAT
<br />CONNECTION.
<br />CHROME PLATED 17 GAUGE 1-1/2 X 1-1/2 P-TRAP WITH CLEANOUT.
<br />BASIS OF DESIGN
<br />SINK - ELKAY 1_11-22191K-99
<br />FAUCET - CHICAGO-786-E29VP
<br />SUPPLIES - MCGUIRE - H17OLK
<br />TRAP - MCGUIRE - 8912
<br />F CO I CLEANOUTS
<br />GENERAL(ALL FLOOR CLEANOUTS): DURO-COATED CAST IRON CLEANOUT WITH MEMBRANE FLANGE
<br />WITH CADMIUM PLATED CAST IRON COUNTERSUNK PLUG. CLEANOUT CAN BE ADJUSTED TO FINISH
<br />FLOOR LEVEL AFTER CONCRETE HAS SET,
<br />FLOOR: HEAVY DUTY ROUND SCORIATED NICKEL BRONZE TOP
<br />CARPETED FLOOR: HEAVY DUTY ROUND NICKEL BRONZE TOP RECESSED FOR CARPET.
<br />TILE FLOOR: HEAVY DUTY ROUND NICKEL BRONZE TOP RECESSED FOR TILE.
<br />EXTERIOR: HEAVY DUTY ROUND SCORIATED NICKEL BRONZE TOP, PROVIDE WITH 18" X 4" THICK
<br />CONCRETE COLLAR, SEE DETAIL.
<br />WALL: CAST IRON CLEANOUT TEE, CADMIUM PLATED CAST IRON COUNTERSUNK PLUG, SMOOTH
<br />SQUARE NICKEL BRONZE WALL ACCESS COVER AND FRAME.
<br />PLUG: DURA-COATED CAST IRON FERRULE AND CADMIUM PLATED CAST IRON COUNTERSUNK PLUG.
<br />BASIS OF DESIGN
<br />FLOOR - ZURN - ZN-1405
<br />CARPETED FLOOR - ZURN - ZN-1405-4
<br />TILE FLOOR - ZURN - ZN-1405-4
<br />EXTERIOR FLOOR - ZURN - ZN-1406
<br />WALL - ZURN-1445-4
<br />PLUG - ZURN - Z-1440
<br />SURGEONS SCRUB SINK
<br />KNEE ACTIVATED DOUBLE COMPARTMENT WALL HUNG SRUB SINK. STAINLESS STEEL CONSTRUCTION
<br />WITH WELDED COMPARTMENTS AND COVED CORNERS, HANDS -FREE WATER CONTROL, KNEE ACTIVATED
<br />PANEL TURNS WATER ON AND OFF, STANDARD ROSE SPRAY FAUCET PRODUCING A SHOWERHEAD TYPE
<br />PATTERN WITHOUT AERATING THE WATER
<br />3/8 INCH I.P.S. CHROME PLATED ANGLE SUPPLY, LOOSE KEY STOP, REDUCER, WROUGHT BRASS
<br />DEEP BELL FLANGE ESCUTCHEON AND 1/2" CHROME PLATED COPPER EXTENSION TUBE WITH SWEAT
<br />CONNECTION.
<br />CHROME PLATED CAST BRASS GRID STRAINER & 1.1/4" O.D, TAILPIECE, CHROME PLATED 17 GAUGE
<br />1-1/4" X 1-1/2" P-TRAP WITH CLEANOUT PLUG,
<br />FULLY ADJUSTABLE FLOOR MOUNTED SCRUB SINK CARRIER ADJUSTED TO A HEIGHT AS
<br />RECOMMENDED BY SCRUB SINK MANUFACTURER,
<br />BASIS OF DESIGN
<br />SURGEONS SINK - AMSCO FLEXMATIC SCRUB SINK (2-STATION)
<br />STRAINER/TRAP - MCGUIRE-155A18902
<br />SUPPLY - MCGUIRE - H170LK
<br />CARRIER - ZURN ZR-1224-75-1
<br />AP-11 ALARM PANEL & MASTER ALARM PANEL
<br />I MP-1 I
<br />THE AREA ALARM PANEL SHALL BE AN AUDIO VISUAL, MICROPROCESSOR CONTROLLED, CLOSED
<br />CIRCUIT, SELF MONITORING TYPE. THE ALARM SHALL BE DESIGNED TO MONITOR THE PRESSURE IN
<br />OXYGEN, NITROUS OXIDE, AIR, NITROGEN, AND VACUUM PIPING SYSTEMS. THE ALARM SHALL BE
<br />DESIGNED FOR RECESSED WALL MOUNTING AND ACCOMMODATE A MAXIMUM OF SIX GAS SERVICES.
<br />THE ENTIRE ASSEMBLY SHALLBE SELF CONTAINED, CONSISTING OF A ROUGH -IN BOX AND FINISHING
<br />ASSEMBLY. ALL GAS AND ELECTRIC CONNECTIONS BETWEEN THE ROUGHING -IN AND FINISHING
<br />ASSEMBLIES SHALL BE PLUGIN
<br />THE ROUGHING -IN BOX SHALL BE FABRICATED OF ALUMINUM AND CONTAIN FACTORY ASSEMBLED
<br />8-INCH LONG, 1/4-INCH NOMINAL I.D. TYPE K COPPER INLET TUBE EXTENSIONS FOR EACH GAS
<br />SERVICE; A POWER SUPPLY BOARD; A 120114 V,60 HERTZ, 25 W TRANSFORMER FOR CONNECTION TO
<br />THE EMERGENCY ELECTRICAL SYSTEM; AND A PROTECTIVE PLASTIC SHIELD, ALL LOW VOLTAGE
<br />CIRCUITRY SHALL BE 14 V OR LESS, AND SHALL BE PREWIRED.`** ALARM PANEL TO BE MODULAR IN
<br />DESIGN WITH EACH GAS/VACUUM MONITORED TO HAVE A LCD (LIQUID CRYSTAL DISPLAY) TO
<br />CONTINUOUSLY INDICATE PRESSURE FROM EACH PRESSUREIVACUUM SWITCH (SENSOR) MOUNTED
<br />IN LOCATIONS INDICATED ON PLANS. WIRING FOR SIGNAL BETWEEN SWITCHES AND ALARM PANEL
<br />BY ELECTRICAL TRADE, COORDINATE LOCATION AS REQUIRED.
<br />ALARM PANEL TO HAVE A 90 DBA AUDIBLE WARNING DEVICE, AND AN INTEGRATED CIRCUIT BOARD
<br />SHALL BE INCLUDED IN THE FINISH ASSEMBLY. THE INTEGRATED CIRCUIT BOARD SHALL INCLUDE
<br />THE MICROPROCESSOR; A MOMENTARY CONTACT SWITCH TO SILENCE THE AUDIBLE ALARM; A
<br />MOMENTARY CONTACT SWITCH TO TEST THE UNIT FOR PROPER OPERATION OF THE AUDIBLE AND
<br />VISUAL FUNCTIONS, AND THE INTEGRITY OF LOW VOLTAGE SOLID STATE CIRCUITRY; A GREEN LED,
<br />LABELED NORMAL, TO INDICATE THE UNIT IS ELECTRICALLY ENERGIZED AND ALL SYSTEM
<br />PRESSURES ARE NORMAL; AND A NON -CANCELABLE RED LED WARNING SIGNAL FOR EACH SYSTEM
<br />SHOULD THE LINE PRESSURE VARY 20% +A FROM NORMAL, IF AN ABNORMAL LINE PRESSURE
<br />CONDITION IS SENSED IN ANY SYSTEM(S) THE GREEN NORMAL SIGNAL SHALL GO OUT AND THE RED
<br />WARNING SIGNAL(S) SHALL GLOW UNTIL THE SYSTEM PRESSURE RETURNS TO NORMAL. WHEN ALL
<br />SYSTEM PRESSURES RETURN TO NORMAL THE GREEN NORMAL SIGNAL LED WILL AGAIN GLOW.
<br />THE MICROPROCESSOR SHALL BE PROGRAMMED TO PROVIDE CONTINUOUS SELF ANALYSIS OF THE
<br />INTEGRATED CIRCUIT COMPONENTS. SHOULD A FAILURE OCCUR, AN INTERMITTENT "CHIRP"
<br />WARNING SIGNAL SHALL ACTIVATE.
<br />THE ALARM PANEL SHALL BE EQUIPPED WITH A RELAY HAVING SELECTABLE NONC DRY CONTACTS
<br />FOR EACH ABNORMAL SIGNAL TO ENABLE WARNING SIGNALS TO BE MONITORED AT REMOTE
<br />LOCATIONS. CONTACTS SHALL BE RATED AT 250 MA 0 24 VOLTS AC OR DC. CONNECTIONS SHALL BE
<br />MADE BY A PLUG-IN TERMINAL BLOCK TO THE CIRCUIT BOARD.
<br />BASIS OF DESIGN
<br />BEACON MEDAES
<br />3-MODULES AREA ALARM PANEL - A2AL - E - VOA
<br />5-MODULES AREA ALARM PANEL - A2AL - E - VOAN2
<br />30 FUNCTION MASTER ALARM PANEL - A2MISO - E - 30
<br />I-119-TI FLOOR SINK
<br />12" X 12" X 6" DEEP, CAST IRON BODY WITH WHITE ACID RESISTING PORCELAIN ENAMEL INTERIOR,
<br />ALUMINUM ANTI -SPLASH INTERIOR BOTTOM DOME STRAINER AND NICKEL BRONZE TOP.
<br />BASIS OF DESIGN
<br />ZURN - Z-1900-T
<br />13`A�-I SHOCK ARRESTER
<br />PISTON OPERATED, TYPE "K" COPPER BARREL WITH BRASS THREADED ADAPTOR. ALL JOINTS SHALL
<br />BE MADE WITH 95-5 LEAD FREE SOLDER. THE PISTON SHALL BE EQUIPPED WITH TWO (2) "0" RINGS TO
<br />PROVIDE A PERMANENT MECHANICAL BARRIER BETWEEN FLUID AND PRE -LOAD AIR CHARGE.
<br />ARRESTORS MAY BE INSTALLED IN VERTICAL AND HORIZONTAL POSITION.
<br />THE ARRESTOR SHALL BE FULLY GUARANTEED FOR ENTIRE SYSTEM LIFE.
<br />NOTE:
<br />SHOCK ARRESTORS SHALL BE PROVIDED AT ALL FIXTURES AND BATTERIES OF FIXTURES WHETHER
<br />OR NOT THEY ARE SHOWN ON THE DRAWINGS.
<br />BASIS OF DESIGN
<br />PRECISION PLUMBING PRODUCTS - SC SERIES
<br />11�I AUTOMATIC TRAP PRIMER VALVE
<br />MACHINED OF CORROSION RESISTANT BRASS SHALL NOT CONTAIN SPRINGS OR DIAPHRAMS, "0"
<br />RING SEALS TESTED FOR RELIABILITY BETWEEN 40 TO 4500 F. INLET OPENING SHALL BE 112-INCH
<br />MALE NPT, OUTLET SHALL BE 1/2-INCH FEMALE NPT.
<br />TRAP PRIMER OPERATES VIA LINE PRESSURE DROP AND DOES NOT NEED TO BE PLACED NEAR A
<br />FIXTURE.
<br />BASIS OF DESIGN
<br />PRECISION PLUMBING PRODUCTS
<br />I140V-11 MEDICAL_ GAS VALVE BOX
<br />THE VALVE BOX SHALL BE CONSTRUCTED OF EXTRUDED ALUMINUM WITH A 112" PLASTER FLANGE ON
<br />ALL FOUR SIDES. A TEMPORARY PLASTER GUARD SHALL PREVENT DEBRIS FROM ENTERING THE BOX
<br />DURING INSTALLATION. A LABEL HOLDER AND LABEL FOR IDENTIFYING THE GAS AND AREA THE
<br />VALVE CONTROLS SHALL BE PROVIDED FOR THE CONTRACTOR TO INSTALL.
<br />THE FINISH FRAME SHALL BE CONSTRUCTED OF EXTRUDED, ETCHED, AND ANODIZED ALUMINUM.
<br />CONCEALED MOUNTING SCREWS SHALL SECURE THE FINISH FRAME TO THE VALVE BOX. THE TINTED,
<br />TRANSPARENT WINDOW SHALL BE EASILY REMOVED OR REPLACED WITHOUT THE AIDS OF TOOLS.
<br />THE BALL TYPE VALVE SHALL HAVE A CAST BRONZE BODY WITH A BRASS OR BRONZE BALL. THE
<br />BOLTED UNION SHALL ALLOW THE VALVE TO SWING OUT FOR EASY SERVICE OR INSTALLATION. THE
<br />VALVE IS DESIGNED FOR A WORKING PRESSURE OF 400 P.S.L. THE VINYL -COATED HANDLE SHALL
<br />ONLY REQUIRE ONE QUARTER OF A TURN TO COMPLETELY OPEN OR CLOSE THE VALVE. THE VALVE
<br />WITH TUBING EXTENSIONS SHALL BE FACTORY BRAZED, PRESSURE TESTED, CLEANED FOR OXYGEN
<br />SERVICE AND CAPPED. A LABEL SHALL BE AFFIXED TO EACH VALVE AND BOTH TUBE EXTENSIONS
<br />IDENTIFYING THE GAS BY NAME AND COLOR. A 1-1/2-INCH DIAMETER LINE PRESSURE MONITORING
<br />GAUGE SHALL BE SUPPLIED FOR INSTALLATION DOWNSTREAM OF THE SHUT-OFF VALVE.
<br />PRESSURENACUUM GAUGE(S) TO BE PROVIDED FOR EACH GAS: 0, A, & N20 (0-100 PSIG FOR 0, A &
<br />N20), N (0-300 PSIG FOR N) AND VAC (0-30 INCHES HG)
<br />SEE PLAN FOR VALVE SIZES REQUIRED.
<br />BASIS OF DESIGN
<br />BEACON MEDAES SERIES
<br />IMGO-11 MEDICAL_ GAS WALL OUTLET
<br />THE QUICK CONNECT RECESSED OUTLETS SHALL BE SUITABLE FOR THE SERVICES LISTED BELOW.
<br />OUTLETS SHALL CONSIST OF A ROUGHING IN ASSEMBLY AND A FINISHED ASSEMBLY.
<br />THE ROUGHING IN ASSEMBLY SHALL CONSIST OF A DIE-CAST BACK PLATE WITH MOUNTING FLANGES
<br />ON ALL FOUR SIDES, A RAISED PLASTER STRIKE, AND A NON - REMOVABLE POSITIVE PIN -KEYING
<br />ARRANGEMENT FOR EACH SPECIFIC GAS SERVICE. IDENTIFICATION OF EACH GAS SERVICE SHALL BE
<br />PERMANENTLY CAST INTO THE BACK PLATE AND CAN BE READ THROUGH A TRANSPARENT PLASTIC
<br />PLASTER GUARD.
<br />MOUNTED TO THE BACK PLATE IS A FULLY ASSEMBLED BRASS SECONDARY CHECK THAT IS
<br />COMPLETELY SERVICEABLE FROM THE FRONT. THE CHECK PREVENTS A GAS FLOW WHEN THE
<br />FINISHING ASSEMBLY IS REMOVED FOR MAINTENANCE OR SERVICE. THE SECONDARY CHECK VALVE
<br />INCLUDES TINCHES OF 3/8-INCH O.D. TYPE K COPPER INLET TUBE WITH A LABEL IDENTIFYING THE
<br />SPECIFIC GAS BY NAME AND COLOR AND A PLASTIC DUST CAP. ROTATION OF THE INLET TUBE SHALL
<br />ALLOW GAS CONNECTION FROM THE TOP OR BOTTOM.
<br />THE FINISH ASSEMBLY SHALL CONSIST OF A STAINLESS STEEL FINISH PLATE, A DIE-CAST CHROME
<br />PLATED COVER PLATE, A MACHINED BRASS HOUSING FOR THE PRIMARY CHECK VALVE, THE
<br />SECONDARY CHECK VALVE, AND POSITIVE PIN -KEYING DEVICES TO PREVENT ACCIDENTAL
<br />INSTALLATION INTO A ROUGHING -IN ASSEMBLY OF A DISSIMILAR GAS. THE FINISHING ASSEMBLY
<br />SHALL INCORPORATE A DOUBLE SEAL WHICH AUTOMATICALLY ENGAGES WHEN A HOSE ADAPTER OR
<br />PATIENT TREATMENT DEVICE IS REMOVED FROM THE OUTLET,
<br />THE FINISHING ASSEMBLY SHALL BE DESIGNED IN ACCORDANCE WITH CGA V-5 STANDARD FOR
<br />DIAMETER INDEX SAFETY SYSTEM. THE EXPOSED PORTION OF QUICK CONNECT OUTLET
<br />CONNECTION SHALL BE POLISHED CHROME PLATE.
<br />GAS SERVICE COMPLETE ASSEMBLY
<br />BASIS OF DESIGN
<br />BEACON MEDAES (CHEMETRON COMPATIBLE)
<br />OXYGEN - O-CHWAL-U-OXY - 0-CHWAL-U-AIR
<br />VACUUM - 0-CHWAL-U-VAC
<br />VACUUM SLIDE - O-WALSLIDE
<br />NITROUS OXIDE - 0-CHWAL-U-N20
<br />NITROGEN - O-DISWAL-E-NIT
<br />301 E. Pine Street, Suite 350
<br />Orlando, Florida 32801
<br />407-893-5800 Fax 407-264-6624
<br />www.rsandh.com
<br />FL Cert. Nos. AAC001886 * IB26MO956
<br />5620 * LCC000210 * GB238
<br />ENGINEERING
<br />TLC
<br />S O L U T I O N
<br />®Copyright 2019
<br />255 S. Orange Avenue
<br />Suite 1600
<br />Orlando, FL 32801
<br />COA 15
<br />P 407.841.9050
<br />wwy.Oc-engineers.com
<br />TLC No.:119469
<br />THINK. LISTEN.
<br />CREATE.
<br />PROJECT TITLE:
<br />AdventHealth - ZEPHYRHILLS
<br />OPERATING ROOMS BUILT OUT
<br />PROJECT ADDRESS:
<br />7050 GALL BLVD,
<br />ZEPHYRHILLS, FL, 33541
<br />Aaron Lee Johnson, P.E.
<br />Florida License #71576
<br />``��►�r�rrrrrii
<br />.0� LEE ,10& ! .
<br />. th • '" G•E•N S �d
<br />No 71576
<br />:1 STATE OF 4U
<br />dLU
<br />�iFs•COR�p. �;
<br />o
<br />,ON
<br />W
<br />J
<br />t�
<br />v
<br />REVISIONS
<br />NO. DESCRIPTION DATE
<br />DATE ISSUED: 12/1112019
<br />REVIEWED BY: ALJ
<br />DRAWN BY, BJL
<br />DESIGNED BY: BJL
<br />PROJECT NUMBER:
<br />504-0253-000
<br />0 2019 RS&H, INC.
<br />SHEET TITLE:
<br />GENERAL PLUMBING
<br />INFORMATION
<br />SHEET ID:
<br />BLDG. ID
<br />PROJECT STATUS:
<br />CONSTRUCTION
<br />DOCUMENTS
<br />Copyright @ 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the
<br />expressed written consent of this corporation is prohibited. All rights reserved.
<br />3" SCALE 0 3" 6" 1'
<br />1 1/2" SCALE 0 6" 1' 2'
<br />3/8" SCALE 3' 0 18" 3' 6'
<br />1 /4" SCALE 4' 0 2' 4' 8'
<br />1/8" SCALE 8' 0 4' 8' 16'
<br />
|