SPECIFICATIONS <br />I. GENERAL REQUIREMENTS <br />ti A. THE PLANS AND SPECIFICATIONS ARE INTENDED TO GIVE A DESCRIPTION OF THE WORK. NO <br />DEVIATION FROM THE PLANS AND SPECIFICATIONS SHALL BE MADE WITHOUT THE WRITTEN <br />CONSENT OF EXCEL ENGINEERING, INC. THE CONTRACTOR IS TO CLARIFY .ANY DISCREPANCIES <br />WITH EXCEL ENGINEERING, INC. PRIOR TO BEGINNING WORK. THE CONTRACTOR SHALL VISIT <br />THE SITE TO VERIFY EXISTING CONDITIONS AND ACCESS TO THE WORK AREA. <br />B. THE CONTRACTOR HAS THE SOLE RESPONSIBILITY FOR AND SHALL HAVE CONTROL OF <br />CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES, AND SAFETY PRECAUTIONS AND <br />PROCEDURES USED TO CONSTRUCT THE WORK. <br />C. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIAL (INCLUDING TAXES) AND EQUIPMENT <br />AS NECESSARY TO COMPLETE THE WORK. PERMITS SHALL BE OBTAINED AND PAID FOR BY THE <br />RESPECTIVE CONTRACTOR, INCLUDING TEMPORARY OCCUPANCY PERMIT IF REQUIRED. <br />D. THE CONTRACTOR SHALL FURNISH TEMPORARY BRACING OF ALL BUILDING ELEMENTS DURING <br />CONSTRUCTION. TEMPORARY BRACING SYSTEMS SHALL BE DESIGNED TO WITHSTAND CODE <br />DESIGN LOADS. CONTRACTOR SHALL RETAIN SERVICES OF A PROFESSIONAL ENGINEER TO <br />DESIGN AND SUPERVISE BRACING INSTALLATION IF THEY DO NOT HAVE THE EXPERTISE <br />REQUIRED. <br />E. ALL APPLICABLE FEDERAL, STATE, AND LOCAL CODES, ORDINANCES AND REGULATIONS, <br />INCLUDING THE REQUIREMENTS OF THE AMERIC AN WITH DISABILITIES ACT (A.D.A.) ARE MADE <br />PART OF THESE SPECIFICATIONS AND SHALL BE COMPLIED WITH AS FAR AS THEY APPLY TO <br />WORK UNDER THIS CONTRACT. <br />F. IN AS MUCH AS THE SPECIFICATIONS ARE BRIEF, THE CONTRACTOR SHALL PROVIDE <br />WORKMANSHIP THAT IS NEAT, SECURE AND OF THE BEST QUALITY WITH THE BEST POSSIBLE <br />APPEARANCE AND UTILITY. FAULTY WORK SHALL BE REPAIRED OR REPLACED AT NO COST TO <br />THE OWNER. INDUSTRY STANDARDS SHALL BE USED AS THE GUIDE FOR QUALITY OF <br />MATERIALS AND WORKMANSHIP. <br />G. REFERENCE TO MATERIALS OR SYSTEMS HEREIN BY NAME, MAKE OR CATALOG NUMBER IS <br />INTENDED TO ESTABLISH A QUALITY STANDARD, AND NOT TO LIMIT COMPETITION. THE WORDS <br />"OR APPROVED EQUIVALENT" ARE IMPLIED FOLLOWING EACH BRAND NAME/MODEL NUMBER <br />UNLESS STATED OTHERWISE. "OR APPROVED EQUIVALENT" MATERIALS SHALL BE APPROVED <br />BY EXCEL ENGINEERING, INC. PRIOR TO BIDS BEING ACCEPTED AND ACCEPTANCE FOR USE. <br />PROVIDE A LETTER FROM THE MANUFACTURER CERTIFYING THAT THE PRODUCT MEETS OR <br />EXCEEDS THE SPECIFIED PRODUCT. <br />H. SUBMIT FIVE (5) COPIES OF STRUCTURAL (HVAC, PLUMBING, FIRE PROTECTION AND <br />ELECTRICAL IF PART OF THIS PLAN) SHOP DRAWINGS TO EXCEL ENGINEERING, INC. FOR <br />APPROVAL PRIOR TO FABRICATION AND INSTALLATION. SHOP DRAWINGS SHALL BE REVIEWED <br />AND STAMPED BY THE CONTRACTOR PRIOR TO SUBMITTING FOR APPROVAL SHOP DRAWING <br />SUBMITTALS MUST BE 100% COMPLETE AND IN ONE (1) PACKAGE FOR THE ITEM BEING <br />SUBMITTED. NON -COMPLETE SHOP DRAWINGS OR PARTIAL ITEM SHOP DRAWINGS WILL BE <br />RETURNED TO THE CONTRACTOR WITHOUT COMMENT AND STAMPED °REJECTED -RESUBMIT." <br />CONTRACTORS WHO KNOWINGLY WANT TO SUBMIT NON -COMPLETE SHOP DRAWINGS OR <br />BREAK SINGLE ITEM SHOP DRAWINGS INTO MULTIPLE SUBMITTALS WILL BE RESPONSIBLE TO <br />MAKE ARRANGEMENTS WITH EXCEL ENGINEERING, PRIOR TO SUBMITTING THE SHOP <br />DR.AWING(S), TO COMPENSATE EXCEL ENGINEERING FOR THE EXTRA WORK INVOLVED. NON- <br />STRUCTURAL ITEMS AND SAMPLES FOR FINISHES ARE TO BE SUBMITTED TO EXCEL <br />ENGINEERING, INC. FOR APPROVAL PRIOR TO INSTALLATION. <br />I. PRIOR TO COMMENCEMENT OF WORK, THE CONTRACTOR SHALL SUBMIT TO THE OWNER A <br />CERTIFICATE OF INSURANCE FOR NOT LESS THAN THE FOLLOWING LIMITS: <br />1. WORKER'S COMPENSATION AND EMPLOYERS LIABILITY <br />A. PER STATUTORY LIMITS <br />2. COMMERCIAL GENERAL LIABILITY <br />A. GENERAL AGGREGATE: $2,000,000 <br />B. PRODUCTS AND COMPLETED OPERATIONS AGGREGATE: $2,000,000 <br />C. PERSONAL AND ADVERTISING INJURY: $1,000,000 <br />D. EACH OCCURRENCE: $1,000,000 <br />3. COMPREHENSIVE AUTOMOBILE LIABILITY <br />A. COMBINED SINGLE LIMIT BODILY INJURY AND PROPERTY DAMAGE: $1,000,000 <br />B. NON -OWNED AND HIRED AUTOMOBILE: $1,000,000 <br />J. THE CONTRACTOR SHALL OBTAIN THE OWNER'S APPROVAL OF THE CONSTRUCTION SCHEDULE <br />PRIOR TO PROCEEDING WITH THE WORK. <br />r K. THE CONTRACTOR SHALL FURNISH TEMPORARY OFFICE, TOILET FACILITIES, WORKING <br />TELEPHONE, ELECTRICITY, HEAT, WATER AND FIRE EXTINGUISHERS AS REQUIRED FOR <br />COMPLETION OF THE WORK UNLESS THE OWNER HAS AGREED IN WRITING TO FURNISH OR <br />WAIVE ANY OF THE ABOVE ITEMS. <br />L. THE CONTRACTOR SHALL PROVIDE ALL LAYOUT AS REQUIRED, COMPETENT ON SITE <br />SUPERVISION, AND BROOM CLEANING OF CONSTRUCTION SITE INCLUDING DUMPSTERS FOR <br />REFUSE DISPOSAL. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SAFETY ON SITE AND <br />PROTECTION OF SITE PER LOCAL, STATE AND FEDERAL REQUIREMENTS. <br />M. NOTIFY ARCHITECT ONE WEEK IN ADVANCE TO SCHEDULE FINAL COMPLIANCE WALK-THRU. <br />PRIOR TO THIS WALK THRU, PROVIDE THE ARCHITECT WITH THE FIRE PROTECTION SYSTEM <br />TEST REPORT AND A COPY OF THE ELEVATOR INSPECTION REPORT AS APPLICABLE. ALL <br />COMPONENT SUBMITTALS SHOULD BE FILED AND AVAILABLE FOR REVIEW AT THE WALK THRU. <br />THE BUILDING SHALL BE COMPLETE AND ALL SYSTEMS OPERATIONAL AT THE TIME OF THE <br />WALK THRU. IF THE ARCHITECT IS REQUIRED TO MAKE ADDITIONAL VISITS DUE TO NON- <br />COMPLIANCE, THEY WILL BE CHARGED TO THE REQUESTING CONTRACTOR. <br />N. THE CONTRACTOR SHALL GUARANTEE ALL WORKMANSHIP AND MATERIALS FOR A PERIOD OF <br />ONE YEAR AFTER SUBSTANTIAL COMPLETION OF THE PROJECT. FURNISH MANUFACTURER'S <br />WRITTEN WARRANTIES FOR SPECIFIED EQUIPMENT STATING EFFECTIVE WARRANTY DATE. <br />0. THE CONTRACTOR SHALL FURNISH "AS -BUILT" DRAWINGS REFLECTING ALL CHANGES DURING <br />CONSTRUCTION. PROVIDE TWO (2) COPIES OF OPERATING AND MAINTENANCE MANUALS TO <br />OWNER FOR ALL FURNISHED EQUIPMENT. <br />II. CONCRETE <br />A. DESIGN AND CONSTRUCTION OF ALL CAST -IN -PLACE CONCRETE WORK SHALL CONFORM TO ACI <br />318 BUILDING CODE AND CRSI MANUAL OF STANDARD PRACTICE. <br />B. CONCRETE SLAB CONSTRUCTION TO BE PROVIDED PER MORE STRINGENT REQUIREMENTS OF <br />GEOTECHNICA_ REPORT OR CONSTRUCTION DOCUMENTS. <br />C. DESIGN MIXES SHALL BE IN ACCORDANCE WITH ASTM C94. <br />1_ STRENGTH TO BE MIN. 3,000 PSI AT 28 DAYS FOR FOOTINGS AND WALLS. <br />2. STRENGTH TO BE MIN. 3,500 PSI AT 28 DAYS FOR SLABS ON GRADE. <br />3. STRENGTH TO BE MIN. 4,000 PSI AT 28 DAYS FOR COLUMNS, BEAMS, EXTERIOR CONCRETE, <br />STRUCTURAL SLABS, CONCRETE FILLED METAL DECK AND PRECAST TOPPINGS. <br />4. SLUMP SHALL NOT EXCEED 4". <br />5. ALL CONCRETE EXPOSED TO WEATHER SHALL BE AIR -ENTRAINED WITH 4-7% AIR CONTENT. <br />NO OTHER ADMIXTURES SHALL BE USED WITHOUT APPROVAL OF EXCEL ENGINEERING, <br />INC. CALCIUM CHLORIDE SHALL NOT BE USED. <br />6. MAXIMUM AGGREGATE SIZE FOR FOOTING TO BE 1 1/2" AND MAXIMUM AGGREGATE SIZE <br />FOR ALL OTHER WORK TO BE 3/4" <br />D. PLACE SLABS ON GRADE WITH CONSTRUCTION JOINT OR SAW JOINT AS INDICATED ON THE <br />PLANS. SAW CUT TO BE DONE AS SOON AS POSSIBLE, BUT NO LATER THAN 24 HOURS AFTER <br />CONCRETE IS PLACED. ALL INTERIOR SLABS TO HAVE A TROWEL FINISH AND ALL EXTERIOR <br />SLABS TO HAVE A LIGHT BROOM FINISH UNLESS NOTED OTHERWISE. MAINTAIN FLOOR LEVEL <br />AT WALLS AND PITCH SURFACES UNIFORMLY TO DRAINS. ALL CONCRETE IS TO BE CURED FOR <br />7 DAYS. FLOORS TO BE STAINED, TO RECEIVE AN ASHFORD SEALER, OR TO RECEIVE ANOTHER <br />FINISH THAT IS NOT COMPATIBLE WITH CURING COMPOUNDS ARE TO BE WET CURED OR CURED <br />WITH AN ARMORLON TRANSGUARD 4000 WET CURE COVER PER MANUFACTURER'S <br />SPECIFICATION. EXTERIOR SLABS SHALL BE SEPARATED FROM BUILDINGS WITH CONTINUOUS <br />1/2" FIBER EXPANSION JOINT AND/OR 1/4" FIBER EXPANSION JOINT AT DECORATIVE MASONRY <br />UNITS. INTERIOR SLABS SHALL BE SEPARATED FROM FOUNDATION WALLS AND PIERS WITH <br />FORM RELEASE AGENT. 15 LB. FELT OR AS DETAILED ON PLANS. <br />E. THE SLAB -ON -GRADE FLOOR FLATNESS/LEVELNESS SHALL MEET TO THE FOLLOWING CRITERIA: <br />1. TOP OF FLOOR ELEVATION SHALL BE WITHIN 3/4" OF DESIGN ELEVATION IN ACCORDANCE <br />TO ACI 117 TOLERANCES. <br />2. THE SPECIFIED OVERALL VALUE FOR THE FLOOR FLATNESS/LEVELNESS IS AS FOLLOWS: <br />A. NONCRITICAL MECHANICAL ROOMS, NONPUBLIC AREAS, AND PARKING - FF20 / FL.15. <br />B. CARPETED AREAS IN COMMERCIAL OFFICE, INDUSTRIAL BUILDING - FF25 / FL20. <br />C. THIN -SET FLOORING, WAREHOUSE - FF35 / FL25. <br />D. WAREHOUSE WITH AIR -PALLET USE, ICE RINKS - FF45 / FL35. <br />E. CRITICAL AREAS AS INDICATED ON PLAN - >FF50 / >FL50. <br />3. THE MINIMUM LOCAL VALUE FOR THE FLOOR FLATNESS/LEVELNESS SHALL NOT BE LESS <br />THAN 67% OF THE SPECIFIED OVERALL VALUE. <br />4. CONTRACTOR SHALL REPLACE AREAS THAT DO NOT MEET THESE CRITERIA. <br />F. ALL REINFORCING BARS SHALL BE ASTM A615 GRADE 60. THICKNESS OF CONCRETE COVER <br />OVER REINFORCEMENT SHALL BE NOT LESS THAN 3" WHERE CONCRETE IS DEPOSITED <br />AGAINST THE GROUND WITHOUT THE USE OF FORMS AND NOT LESS THAN 1 1/2" IN ALL OTHER <br />LOCATIONS. ALL REINFORCING SHALL BE LAPPED 36 DIAMETERS FOR UP TO #6 BARS, 60 <br />DIAMETERS FOR #7 TO #10 BARS OR AS NOTED ON THE DRAWINGS AND EXTENDED AROUND <br />CORNERS WITH CORNER BARS. PLACING AND DETAILING OF STEEL REINFORCING AND <br />REINFORCING SUPPORTS SHALL BE IN ACCORDANCE WITH CRSI AND ACI MANUAL AND <br />STANDARD PRACTICES. THE REINFORCEMENT SHALL NOT BE PAINTED AND MUST BE FREE OF <br />GREASE/OIL, DIRT OR DEEP RUST WHEN PLACED IN THE WORK. ALL WELDED WIRE FABRIC <br />SHALL MEET THE REQUIREMENTS OF ASTM A185. WELDED WIRE FABRIC SHALL BE PLACED 2" <br />FROM TOP OF SLAB, UNLESS INDICATED OTHERWISE. <br />G. CONTRACTOR SHALL ENGAGE A QUALIFIED INDEPENDENT TESTING AND INSPECTING AGENCY <br />TO SAMPLE MATERIALS, PERFORM TESTS, AND SUBMIT TEST REPORTS DURING CONCRETE <br />PLACEMENT. TESTS WILL BE PERFORMED ACCORDING TO ACI 301. CAST AND LABORATORY <br />CURE ONE SET OF FOUR STANDARD CYLINDERS FOR EACH COMPOSITE SAMPLE FOR EACH <br />DAY'S POUR OF EACH CONCRETE MIX EXCEEDING 5 CU. YD., BUT LESS THAN 25 -CU. YD., PLUS <br />ONE SET FOR EACH ADDITIONAL 50 CU. YD. OR FRACTION THEREOF. PERFORM COMPRESSIVE - <br />STRENGTH TESTS ACCORDING TO ASTM C 39. TEST TWO SPECIMENS AT 7 DAYS AND TWO <br />SPECIMENS AT 28 DAYS. PERFORM SLUMP TESTING ACCORDING TO ASTM C 143. PROVIDE ONE <br />TEST AT .POINT OF PLACEMENT FOR EACH COMPOSITE SAMPLE, BUT NOT LESS THAN ONE TEST <br />FOR EACH DAY'S POUR OF EACH CONCRETE MIX. PERFORM ADDITIONAL TESTS WHEN <br />CONCRETE CONSISTENCY APPEARS TO CHANGE. <br />H. PROTECT FRESHLY PLACED CONCRETE FROM PREMATURE DRYING AND EXCESSIVE COLD OR <br />HOT TEMPERATURES. IN HOT, DRY, AND WINDY WEATHER, APPLY AN EVAPORATION -CONTROL <br />COMPOUND ACCORDING TO MANUFACTURER'S INSTRUCTIONS AFTER SCREEDING AND BULL <br />FLOATING, BUT BEFORE POWER FLOATING AND TROWELLING. <br />I. LIMIT MAXIMUM WATER-CEMENTITIOUS RATIO OF CONCRETE EXPOSED TO FREEZING, THAWING <br />AND DEICING SALTS TO 0.45. <br />J. APPLY TROWEL FINISH TO MONOLITHIC SLAB SURFACES TO BE EXPOSED TO VIEW AND SLAB <br />SURFACES TO BE COVERED WITH RESILIENT FLOORING, CARPET, PAINT, OR OTHER THIN FILM - <br />FINISH COATING SYSTEM. APPLY NONSLIP BROOM FINISH TO EXTERIOR CONCRETE <br />PLATFORMS, STEPS, AND RAMPS, AND ELSEWHERE AS INDICATED. <br />K. TEST RESULTS WILL BE REPORTED IN WRITING TO ARCHITECT, READY -MIX PRODUCER, AND <br />CONTRACTOR WITHIN 24 HOURS AFTER TESTS. REPORTS OF COMPRESSIVE STRENGTH TESTS <br />SHALL CONTAIN THE PROJECT IDENTIFICATION NAME AND NUMBER, DATE OF CONCRETE <br />PLACEMENT, NAME OF CONCRETE TESTING SERVICE, CONCRETE TYPE AND CLASS, LOCATION <br />OF CONCRETE BATCH IN STRUCTURE, DESIGN COMPRESSIVE STRENGTH AT 28 DAYS, <br />CONCRETE MIX PROPORTIONS AND MATERIALS, COMPRESSIVE BREAKING STRENGTH, AND <br />TYPE OF BREAK FOR BOTH 7-DAY TESTS AND 28-DAY TESTS. <br />1. INCLUDE THIS SET OF PLANS WITH THE PROJECT AS -BUILT PLANS. <br />III. LUMBER <br />A. LUMBER SHALL BE GRADED AND STAMPED WITH MINIMUM STRUCTURAL DESIGN VALUES AS <br />LISTED BELOW. <br />1. #1/#2 DOUG FIR 850 PSI FB, 95 PSI FV, 1600 KS! E (BEAMS, LINTELS & HEADERS, UNLESS <br />NOTED) <br />2. #1/#2 S.P.F. 875 PSI FB, 1150 PSI FC, 1400 KSI E (ALL STUDS & PLATES, UNLESS NOTED) <br />3. LVL @ 1800 KSI E OR MICRO -LAM @ 1900 KSI E 2600 PSI FB, 285 PSI FV (OR AS NOTED ON <br />THE PLANS) <br />4. WOOD HEADER MATERIAL SHALL BE FREE OF ALL SPLITS, SHAKES AND CHECKS. <br />B. MISCELLANEOUS LUMBER: PROVIDE NO. 3 OR STANDARD GRADE LUMBER OF ANY SPECIES FOR <br />SUPPORT OR ATTACHMENT OF OTHER CONSTRUCTION, INCLUDING ROOFTOP EQUIPMENT <br />CURBS AND SUPPORT BASES, CANT STRIPS, BUCKS, NAILERS, BLOCKING, AND SIMILAR <br />MEMBERS. <br />C. PROTECTION AGAINST DECAY WITH PRESERVATIVE -TREATED WOOD SHALL BE REQUIRED IN <br />THE FOLLOWING AREAS: <br />1. ALL WOOD SILL PLATES, FRAMING, AND FURRING STRIPS ATTACHED TO EXTERIOR BELOW <br />GRADE MASONRY AND CONCRETE WALLS. <br />2. ALL WOOD PLATES, BLOCKING, FRAMING AND FURRING STRIPS ATTACHED TO EXTERIOR, <br />SINGLE-WYTHE MASONRY WALLS. <br />3. ALL WOOD CAP FLASHING BLOCKING ATTACHED TO MASONRY OR CONCRETE PARAPETS. <br />4. ALL WOOD SLEEPERS AND SILL PLATES ON CONCRETE SLABS IN DIRECT CONTACT WITH <br />EARTH. <br />A. EXCEPTION: WOOD SILL PLATES ON CONCRETE SLABS SEPARATED FROM DIRECT <br />CONTACT TO THE EARTH WITH A 10 MIL POLYETHYLENE VAPOR RETARDANT WILL NOT <br />REQUIRE PRESERVATIVE -TREATMENT. <br />5. ALL WOOD IN CONTACT WITH GROUND OR EXPOSED TO THE WEATHER. <br />D. FINISHES FOR FASTENERS AND HARDWARE IN CONTACT WITH PRESERVATIVE -TREATED WOOD <br />ARE BASED ON THE FOLLOWING ASSUMPTIONS: <br />1. ALL INTERIOR TREATED WOOD SHALL USE AN ACQ-C, ACQ-D (CARBONATE), CBA-A, OR CA-B <br />TREATMENT WITH RETENTION LEVELS LESS THAN OR EQUAL TO 0.40 PCF, 0.40 PCF, 0.41 <br />PCF, AND 0.21 PCF RESPECTIVELY. <br />2. ALL CONNECTION HARDWARE AND FASTENERS IN DIRECT CONTACT WITH INTERIOR <br />TREATED WOOD SHALL BE HOT -DIPPED GALVANIZED, MECHANICALLY GALVANIZED, OR <br />STAINLESS STEEL. <br />3. ALL CONNECTION HARDWARE AND FASTENERS IN DIRECT CONTACT WITH EXPOSED <br />EXTERIOR TREATED WOOD OR UNKNOWN TREATMENTS SHALL BE STAINLESS STEEL. <br />4. USE TAPCON CLIMASEAL FASTENERS TO CONNECT ACQ-TREATED WOOD BLOCKING TO <br />MASONRY OR CONCRETE PARAPETS. <br />E. SHOP DRAWINGS FOR PRESERVATIVE -TREATED WOOD, HARDWARE, AND FASTENERS: <br />1. THE CONTRACTOR SHALL FURNISH MATERIAL CERTIFICATES FOR ALL PRESERVATIVE - <br />IV. EXTERIORNAME OF THE TREATING COMPANY, THE <br />PRESERVATIVE USED, THE LEVEL OF TREATMENT (0.10, 0.25, 0.40, ETC.), THE INTENDED USE <br />(ABOVE GROUND, GROUND CONTACT, ETC.), AND A REFERENCE TO THE APPROPRIATE <br />AWPA STANDARD, <br />2. THE CONTRACTOR SHALL FURNISH MATERIAL DA-A SHEETS FOR HARDWARE AND <br />FASTENERS IN CONTACT WITH PRESERVATIVE -TREATED WOOD. <br />A. ALL EIFS MATERIALS AND INSTALLATION SHALL COMPLY WITH LOCAL AND STATE CODES AND <br />TO EIMA GUIDELINE SPECIFICATIONS FOR EXTERIOR INSULATION AND FINISH SYSTEMS, CLASS <br />PB WITH MOISTURE DRAINAGE. <br />B. SUBMIT THE FOLLOWING ITEMS. <br />1. PRODUCT DATA: PRODUCT DATA SHEETS DESCRIBING PRODUCTS TO BE USED ON <br />PROJEC T. <br />2. SAMPLES: SAMPLES FOR EACH FINISH, TEXTURE, AND COLOR TO BE USED ON PROJECT. <br />3. QUALITY ASSURANCE/CONTROL SUBMITTALS: MANUFACTURERS INSTALLATION <br />INSTRUCTIONS. <br />C. FOLLOW MANUFACTURERS INSTRUCTIONS ON PRODUCT STORAGE AND HANDLING. <br />D. STORE MOISTURE SENSITIVE MATERIALS IN WEATHER PROTECTED ENCLOSURES. <br />E. PROVIDE A COMPLETE EXTERIOR INSULATION AND FINISH SYSTEM ,CLASS PB, CONSISTING OF, <br />BUT NOT LIMITED TO, A AIR & MOISTURE BARRIER, AN ADHESIVE, EXPANDED POLYSTYRENE <br />INSULATION BOARD, BASE COAT, REINFORCING MESH(ES)AND FINISH. <br />F. INSTALL EIFS IN ACCORDANCE WITH MANUFACTURERS INSTALLATION INSTRUCTIONS AND AS <br />SHOWN ON PLANS. <br />G. ALL SURROUNDING AREAS, WHERE THE EIFS HAS BEEN INSTALLED, SHALL BE LEFT FREE OF <br />DEBRIS AND FOREIGN SUBSTANCES RESULTING FROM THE WORK. <br />H. PROTECT FINISHED WORK FROM INCLEMENT WEATHER UNTIL DRY AND PERMANENT <br />PROTECTION IN THE FORM OF FLASHINGS, SEALANTS, ETC. ARE INSTALLED. <br />L PROTECT FINISHED WORK FROM DAMAGE DURING REMAINDER OF CONSTRUCTION PERIOD: <br />V. AIR AND MOISTURE <br />A. ALL AIR AND MOISTURE BARRIER MATERIALS AND INSTALLATION SHALL COMPLY WITH LOCAL <br />AND STATE CODES. <br />B. SUBMIT THE FOLLOWING ITEMS. <br />1. PRODUCT DATA: MANUFACTURERS TECHNICAL BULLETINS. <br />C. FOLLOW MANUFACTURERS INSTRUCTIONS ON PRODUCT STORAGE AND HANDLING. <br />D. STORE MOISTURE SENSITIVE MATERIALS IN WEATHER PROTECTED ENCLOSURES. <br />E. PROVIDE A COMPLETE AIR AND MOISTURE BARRIER SYSTEM USING A FLUID APPLIED THREE- <br />PART SYSTEM. THE SYSTEM CONSISTS OF ADHESIVE MESH TAPE AND LIQUID FILL AND SPRAY <br />WRAP. <br />1. ACCEPTABLE PRODUCT: PROSOCO R-GUARD OR EQUAL. <br />F. INSTALL AIR AND MOISTURE BARRIER IN ACCORDANCE WITH MANUFACTURERS INSTALLATION <br />INSTRUCTIONS AND AS SHOWN ON PLANS. <br />1. APPLY R-GUARD TAPE OVER SHEATHING JOINTS AND SEAMS. FOLD AND APPLY R-GUARD <br />TAPE TO ROUGH OPENINGS, INSIDE AND OUTSIDE CORNERS. USE A SEAM ROLLER OR <br />OTHER BLUNT TOOL TO FIRMLY ADHERE TAPE TO SHEATHING. <br />2. UNIFORMLY COVER TAPE AND ABOUT 4 INCHES OF SHEATHING ON EITHER SIDE OF THE <br />TAPE WITH R-GUARD FILL USING A TROWEL OR TEXTURE SPRAYER. TROWEL SMOOTH. <br />SPOT FILL FASTENERS AND SURFACE DEFECTS WITH R-GUARD FILL. LET DRY. <br />3. SPRAY OR ROLLER APPLY R-GUARD SPRAY WRAP TO THE ENTIRE SURFACE -INCLUDING <br />AREAS COVERED BY R-GUARD TAPE AND R-GUARD FILL TO A UNIFORM WET MIL THICKNESS <br />(10 MILS). LET DRY. ON MASONRY CONSTRUCTION, WHEN SPRAY APPLYING, B AC KROLL TO <br />CLOSE PINHOLES AND ENSURE EVEN COVERAGE. APPLY NUMBER OF COATS AS REQUIRED <br />BY MANUFACTURERS SPECIFICATIONS. <br />G. ALL SURROUNDING AREAS, WHERE THE AIR AND MOISTURE BARRIER HAS BEEN INSTALLED, <br />SHALL BE LEFT FREE OF DEBRIS AND FOREIGN SUBSTANCES RESULTING FROM THE WORK. <br />H. PROTECT FINISHED WORK FROM DAMAGE DURING REMAINDER OF CONSTRUCTION PERIOD. <br />VI. INSULATION <br />A. ALL INSULATION MATERIALS AND INSTALLATION SHALL COMPLY WITH LOCAL AND STATE <br />CODES. <br />B. PRODUCT: FIBERGLASS INSULATION TO BE FIBERGLASS BATT OR ROLL COMPLYING WITH ASTM <br />C665 AND NONCOMBUSTIBLE PER ASTM E136. THICKNESS OR R VALUE AS INDICATED ON PLANS. <br />IF THICKNESS IS NOT SHOWN ON PLANS, THICKNESS TO BE THE DEPTH OF THE WALL OR <br />RAFTER SYSTEM. <br />1. MANUFACTURER: CERTAINTEED OR OWENS CORNING. <br />C. PRODUCT: VAPOR RETARDER TO BE MEMBRANE VAPOR RETARDER INSTALLED ON WARM SIDE <br />(NORMALLY INSIDE) FACE OF THE INSULATION. <br />1. MANUFACTURER: CERTAINTEED. <br />D. PRODUCT: ACOUSTICAL WALL INSULATION TO BE NOISE REDUCER SOUND CONTROL BATTS IN <br />WOOD FRAME CONSTRUCTION. WALL INSULATION TO BE CERT.ASOUND SOUND ATTENUATION <br />BATTS IN METAL FRAMED WALLS AND CEILINGS. ACOUSTICAL CEILING BATTS TO BE <br />CERTASOUND. <br />1. MANUFACTURER: CERTAINTEED. <br />E. FOLLOW MANUFACTURERS INSTRUCTIONS ON PRODUCT STORAGE AND HANDLING. <br />F. INSTALL INSULATION IN ACCORDANCE WITH MANUFACTURERS INSTALLATION INSTRUCTIONS <br />AND AS SHOWN ON PLANS. <br />VII. SEALANTS <br />A. CAULK AROUND ALL WINDOWS, DOORS, VENT OPENINGS, WHERE DIFFERENT MATERIALS MEET, <br />ROOF OPENINGS, EAVES, SOFFITS, JOINTS, COUNTERTOPS, DOOR FRAMES, ETC. AND AS <br />REQUIRED FOR A WATERTIGHT CONNECTION. PROVIDE SONNEBORN SONOLASTIC NP2 FOR <br />ALL CMU CONTROL JOINTS. PROVIDE "TREMCO DYMERIC 240 FC" AT ALL NON -FINISH INTERIOR <br />& EXTERIOR LOCATIONS. SEE FLOOR PLAN. CAULK TO BE INSTALLED AFTER FINISH IS APPLIED <br />TO SURFACES PER MANUFACTURER. <br />VIII. DOORS, WINDOWS AND FRAMES <br />A. REQUIREMENTS <br />1. FURNISH AND INSTALL ALL DOORS AND WINDOW ASSEMBLIES AS INDICATED ON THE PLANS <br />ALONG WITH ALL HARDWARE INDICATED AND THAT MAY BE REQUIRED FOR A COMPLETE <br />JOB. <br />2. ALL DOORS AND WINDOWS SHALL OPERATE SMOOTHLY WITHOUT BIND AND BE INSTALLED <br />PLUMB AND TRUE. <br />3. ALL HARDWARE SHALL FIT PROPERLY AND BE ADJUSTED AS REQUIRED. <br />4. PROVIDE INSECT SCREENS ON ALL OPERABLE WINDOW UNITS. <br />IX. HARDWARE <br />A. REQUIREMENTS <br />1. ALL LOCKSETS SHALL BE LEVER TYPE AS REQUIRED TO MEET REQUIREMENTS OF A.D.A. <br />2. ALL OTHER HARDWARE SHALL CONFORM TO THE REQUIREMENTS OF A.D.A. <br />3. ALL EXIT DOORS SHALL BE EQUIPPED WITH LEVER TYPE OR PANIC TYPE EXIT HARDWARE <br />OPENABLE FROM THE INSIDE WITHOUT THE USE OF A LATCH, KEY OR BOLT. <br />4. CONTRACTOR TO COORDINATE KEYING SCHEDULE WITH OWNER. <br />X. SAFETY GLAZING <br />A. PROVIDE SAFETY GLASS IN ALL GLAZING AS LISTED BELOW UNLESS NOTED OTHERWISE: <br />1. WHERE REQUIRED BY FEDERAL, STATE AND LOCAL CODES. <br />B. SAFETY GLASS REQUIREMENTS <br />1. SAFETY GLASS SHALL BE, BUT NOT LIMITED TO <br />A. TEMPERED GLASS <br />B. LAMINATED GLASS <br />C. SAFETY PLASTIC <br />D. SAFETY INSULATING UNITS WHICH MEET THE TEST REQUIREMENTS OF ANSI Z97.1, AND <br />WHICH ARE CONSTRUCTED, TREATED, OR COMBINED WITH OTHER MATERIALS SO AS <br />TO MINIMIZE THE LIKELIHOOD OF CUTTING AND PIERCING INJURIES RESULTING FROM <br />HUMAN IMPACT WITH THE GLAZING MATERIAL. <br />2. ALL SAFETY GLAZING MATERIAL SHALL BE LABELED PER LOCAL, STATE, AND FEDERAL <br />REQUIREMENTS. <br />XL DRYWALL STUDS (INTERIOR NON -BEARING) <br />A. REQUIREMENTS <br />1. STUDS SHALL BE SECURED TO TOP AND BOTTOM TRACK WITH (1) #8ML SCREW IN EACH <br />FLANGE (UNLESS A SLIP TRACK IS REQUIRED AT THE TOP OF THE WALL). <br />2. PROVIDE SLIP TRACK AT TOP OF FULL HEIGHT PARTITIONS. <br />3. STUDS SHALL BE INSTALLED PER "GYPSUM CONSTRUCTION HANDBOOK" AS PUBLISHED BY <br />UNITED STATES GYPSUM COMPANY LATEST EDITION. <br />4. DRYWALL STUDS SHALL BE INDICATED ON THE PLANS. <br />XII. DRYWALL <br />A. DRYWALL SHALL BE INSTALLED PER THE LATEST EDITIONS OF "RECOMMENDED <br />SPECIFICATIONS FOR THE APPLICATION AND FINISHING OF GYPSUM BOARD" GA-216 AS <br />PUBLISHED BY THE GYPSUM ASSOCIATION AND THE "GYPSUM CONSTRUCTION HANDBOOK" AS <br />PUBLISHED BY UNITED STATES GYPSUM COMPANY. <br />1. PROVIDE CONTROL JOINTS PER THESE REQUIREMENTS. <br />2. PROVIDE M.R. DRYWALL AT ALL FRP, CERAMIC WALL TILE, PORCELAIN WALL TILE, COOLER <br />PANEL, FREEZER PANEL AND DAMP/WET LOCATIONS. <br />B. DRYWALL FINISHES SHALL BE INSTALLED PER THE LATEST EDITION OF "RECOMMENDED LEVELS <br />OF GYPSUM BOARD FINISH" GA-214-96 AS PUBLISHED BY THE AWCI, PAINTING AND DECORATING <br />CONTRACTORS OF AMERICA, GYPSUM ASSOCIATION AND CISCA. PROVIDE A LEVEL 1 FINISH AT <br />ALL UNEXPOSED AREAS OR AS NOTED ON PLANS. <br />C. LEVELS OF FINISH: <br />1. LEVEL 4 JOINTS AND INTERIOR ANGLES HAVE TAPE EMBEDDED IN JOINT COMPOUND AND <br />TWO SEPARATE COATS OF JOINT COMPOUND APPLIED OVER ALL FLAT JOINTS AND ONE <br />SEPARATE COAT APPLIED OVER INTERIOR ANGLES; FASTENER HEADS AND ACCESSORIES <br />ARE COVERED WITH THREE (3) SEPARATE COATS OF JOINT COMPOUND; NO TOOL MARKS <br />OR RIDGES. <br />XIII. FINISHES <br />A. REQUIREMENTS <br />1. PROVIDE AND INSTALL ALL FINISHES AS INDICATED ON PLANS. <br />2. INSTALL ALL MATERIALS PER MANUFACTURER'S RECOMMENDATIONS AND SPECIFICATIONS. <br />3. "FINISH" INSTALLER INSPECT SUBSURFACE AND PREPARE AS PER MANUFACTURER'S <br />SPECIFICATIONS PRIOR TO INSTALLATION OF PRODUCT. <br />4. ALL FINISHES TO MEET ALL CODE REQUIREMENTS AND REGULATIONS INCLUDING FLAME <br />SPREAD AND SMOKE DEVELOPMENT. <br />XV. SIGNAGE <br />A. REQUIREMENTS <br />1. CONTRACTOR TO FURNISH AND INSTALL SIGNAGE PER LOCAL, STATE, AND FEDERAL CODES <br />AND PER ROOM FINISH SCHEDULE. <br />2. ALL SIGNAGE SHALL MEET THE REQUIREMENTS OF THE A.D.A. AND ANSI. <br />3. WHERE PERMANENT IDENTIFICATION IS PROVIDED FOR ROOMS AND SPACES, SIGNS SHALL <br />BE INSTALLED ON THE WALL ADJACENT TO THE LATCH SIDE OF THE DOOR. WHERE THERE <br />IS NO WALL SPACE TO THE LATCH SIDE OF THE DOOR, INCLUDING AT DOUBLE LEAF DOORS, <br />SIGNS SHALL BE PLACED ON THE NEAREST ADJACENT WALL. <br />4. MOUNTING HEIGHT SHALL BE 60" ABOVE FINISH FLOOR TO THE CENTERLINE OF THE SIGN <br />UNLESS INDICATED OTHERWISE. <br />5. PROVIDE HANDICAP PARKING SIGNS_ AS INDICATED ON PLANS AND AS REQUIRED BY LOCAL, <br />STATE, AND FEDERAL CODES. <br />XVI. FIRE EXTINGUISHERS <br />A. REQUIREMENTS <br />1. CONTRACTOR TO FURNISH AND INSTALL EXTINGUISHERS PER LOCAL, STATE, AND FEDERAL <br />CODES, AND N.F.P.A. NO.10-1978. <br />2. MOUNT FIRE EXTINGUISHER NOT HIGHER THAN 48" ABOVE FINISH FLOOR UNLESS LOCAL <br />REGULATIONS REQUIRE DIFFERENT HEIGHT. <br />3. ALL FIRE EXTINGUISHERS AND CABINETS TO MEET THE REQUIREMENTS OF THE A.D.A. AND <br />ANSI A117.1. <br />XVII. TOILET ROOMS <br />A. A.D.A./ANSI A117.1 APPROVED SIGNAGE SHALL BE PROVIDED FOR EACH TOILET ROOM TO <br />DESIGNATE MEN, WOMEN, OR UNISEX. <br />XVIII. FIRE PROTECTION WORK <br />A. SEE FIRE PROTECTION PLANS FOR SPECIFICATIONS. <br />XIV. PAINTING XIX. PLUMBING WORK <br />A. FURNISH ALL LABOR, MATERIALS, TOOLS, EQUIPMENT AND SCAFFOLDING REQUIRED FOR <br />COMPLETING SURFACE PREPARATION, PAINTING, FINISHING AND RELATED ITEMS. A. SEE PLUMBING PLANS FOR SPECIFICATIONS <br />B. EXCESS MATERIALS, CONTAINERS AND OTHER ITEMS NECESSARY FOR THE COMPLETION OF <br />THE WORK MUST BE DISPOSED OF IN A MANNER THAT MEETS OR EXCEEDS THE STRICTEST XX. HEATING AND VENTILATION WORK <br />LAWS GOVERNING THE PROJECTS MUNICIPALITY AND/OR STATE. THE PAINTING CONTRACTOR <br />IS RESPONSIBLE FOR COMPLETE ADHERENCE TO ALL DISPOSAL REGULATIONS. A. SEE HVAC PLANS FOR SPECIFICATIONS. <br />C. PAINT ALL EXPOSED MISCELLANOUS ITEMS, FINISHED OR UNFINISHED (EX. H.V.A.C. RETURN AIR XXI. ELECTRICAL WORK <br />GRILLES, CONDUIT, ETC.) TO MATCH ADJOINING WALL SURFACES. <br />A. SEE ELECTRICAL PLANS FOR SPECIFICATIONS. <br />D. CONTRACTOR TO VERIFY THAT PAINT IS COMPATIBLE WITH PRIMER OF SHOP PRIMED <br />SURFACES. NOTIFY EXCEL ENGINEERING IF THERE ARE ANY COMPATIBILITY ISSUES. <br />E. THE CONTRACTOR SHALL KEEP EMPTY CONTAINERS ON THE PROJECT SITE UNTIL ALL <br />PRODUCTS ARE VERIFIED AS TO COLOR AND/OR SHEEN. THE CONTRACTOR SHALL LEAVE WITH <br />THE OWNER ALL OPENED PAINT CONTAINERS. <br />F. EXTERIOR ITEMS: <br />1. FERROUS METAL (PRIMED): STRUCTURAL STEEL, MISCELLANEOUS IRON, HANDRAILS, <br />HOLLOW METAL DOORS AND FRAMES, ROOF STRUCTURE, EXPOSED ROOF PIPING, ETC.: <br />A. ALKYD SHOP PRIMER ON METAL <br />2. 1 COAT S-W KEM BOND HS UNIVERSAL METAL PRIMER B50 SERIES. <br />3. 2 COATS METALATEX SEMI -GLOSS COATING B42 SERIES. <br />4. GALVANIZED: <br />A. 2 COATS S-W METALATEX SEMI -GLOSS COATING B42 SERIES. <br />5. CONCRETE: <br />A. 1 COAT S-W LOXON XP A24W300 SERIES (8 MILS WET, 3.2 MILS DRY). <br />B. 2 COAT S-W A-100 EXTERIOR LATEX SATIN A83 SERIES (4 MILS WET, 1.4 MILS DRY). <br />G. INTERIOR ITEMS: <br />1. DRYWALL FINISH: EG-SHEL <br />A. 1 COAT S-W PREPRITE 200 LATEX PRIMER B28 SERIES (4 MILS WET, 1.2 MILS DRY). <br />B. 2 COATS S-W PROMAR 200 INTERIOR LATEX EG-SHEL B20 SERIES (4 MILS WET, 1.5 MILS <br />DRY/C OAT). <br />2. DRYWALL FINISH: FLAT <br />A. 1 COAT S-W PREPRITE 200 LATEX PRIMER B28 SERIES (4 MILS WET, 1.2 MILS DRY). <br />B. 2 COATS S-W PROMAR 200 INTERIOR LATEX FLAT B30 SERIES (4 MILS WET, 1.4 MILS <br />DRY/C OAT). <br />3. DRYWALL FINISH: SATIN <br />A. 1 COAT S-W PREPRITE 200 LATEX PRIMER B28 SERIES (4 MILS WET, 1.2 MILS DRY). <br />B. 2 COATS S-W DURATION HOME LATEX SATIN B97 SERIES (4 MILS WET, 1.5 MILS <br />DRY/COAT)- <br />4. DRYWALL FINISH: SEMI -GLOSS <br />A. 1 COAT S-W PREPRITE 200 LATEX PRIMER B28 SERIES (4 MILS WET, 1.2 MILS DRY). <br />B. 2 COATS S-W PROMAR 200 INTERIOR LATEX SEMI -GLOSS B31 SERIES (4 MILS WET, 1.3 <br />MILS DRY/COAT). <br />5. DRYWALL FINISH: EPDXY SYSTEM SEMI -GLOSS <br />A. 1 COAT S-W PREPRITE CLASSIC LATEX PRIMER 628 SERIES (4 MILS WET, 1.2 MILS DRY). <br />B. 2 COATS S-W WATER BASED CATALYZED EPDXY B 70 SERIES (2.5 3 MILS DRY/COAT). <br />6. NEW WOOD, STAINED: <br />A. 1 COAT S-W WOOD CLASSICS INTERIOR OIL STAIN A49 SERIES. <br />B. 1 COAT S-W WOOD CLASSICS POLYURETHANE GLOSS VARNISH A67V1. <br />C. 1 COAT S-W WOOD CLASSICS POLYURETHAN SATIN VARNISH A67 SERIES (4 MILS WET, <br />1.4 MILS DRY/COAT). <br />7. NEW WOOD, PAINTED: <br />A. 1 COAT S-W PREPRITED CLASSIC INTERIOR LATEX PRIMER B28 SERIES (4 MILS WET, 1.6 <br />MILS DRY). <br />B. 2 COATS S-W DURATION HOME LATEX SATIN B97 SERIES (4 MILS WET, 1.5 MILS <br />DRY/C OAT). <br />8. FERROUS METAL (PRIMED, BRUSH/ROLLER) DOORS, FRAMES, HANDRAILS, MISC. METALS, <br />ETC.: AC RYLIC <br />A. 1 COAT S-W DTM ACRYLIC PRIMER/FINISH 366W1 (2.5 4 MILS DRY/COAT). <br />B. 2 COATS S-W DTM ACRYLIC PRIMER/FINISH B66W1 (2.5 4 MILS DRY/COAT). <br />9. FERROUS METAL (PRIMER, SPRAYED), ALL EXPOSED STRUCTURAL STEEL AND EXPOSED <br />MECHANICAL/ELECTRICAL ITEMS: ACRYLIC <br />A. 1 COAT S-W DTM ACRYLIC PRIMER/FINISH 366W1 (2.5 4 MILS DRY/COAT). <br />B. 1-2 COATS S-W SUPER SAVE-LITE HI-TEC DRYFALL. B48 SERIES (6 MILS WET, 3 MILS DRY). <br />10. GALVANIZED: <br />A. BRUSH/ROLLER: 2 COATS S-W DTM ACRYLIC COATING SEMI -GLOSS B66 SERIES (2 MILS <br />DRY/COAT). <br />B. SPRAYED: 1 COAT S-W GALVITE HS B50WZ30 (5 MILS WET, 3 MILS DRY) AND 2 COATS S- <br />W SUPER SAVE-LITE HI-TEC DRYFALL B48 SERIES (4 MILS WET, 2 MILS DRY). <br />11. ALUMINUM: <br />A. 2 COATS S-W METALATEX SEMI -GLOSS COATING B42 SERIES (4 MILS WET, 1.5 MILS <br />DRY/C OAT). <br />H. REMOVE AND/OR PROTECT ALL HARDWARE, HARDWARE ACCESSORIES, MACHINED SURFACES, <br />PLATES, LIGHTING FIXTURES, SPRINKLER HEADS AND SIMILAR ITEMS THAT ARE NOT TO BE <br />PAINTED, BUT REQUIRE PROTECTION FROM THE PAINTING PROCESS. RE -INSTALL SAME AFTER <br />COMPLETION OF PAINTING. MASK OFF ALL NAMEPLATES, EQUIPMENT IDENTIFICATION AND <br />SIMILAR ITEMS. REMOVAL AND REINSTALL OF ITEMS IS TO BE DONE BY CONTRACTOR SKILLED <br />IN SUCH WORK. <br />I. SEAL TOPS, BOTTOMS AND CUTOUTS OF UNPRIMED WOOD DOORS WITH A HEAVY COAT OF <br />SEALER IMMEDIATELY UPON DELIVERY TO THE PROJECT. <br />J. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROPER PREPARATION OF ALL SURFACES <br />PRIOR TO THE PAINTING INSTALLATION. <br />K. THE FINISH PRODUCT SHALL HAVE A CONSISTENT, SMOOTH APPEARANCE OF THE SPECIFIED <br />LUSTER. <br />L. APPLY PAINT PER MANUFACTURERS TEMPERATURE AND HUMIDITY REQUIREMENTS- <br />M. COMPLETED WORK SHALL BE FREE FROM DEFECTS AND FLAWS. <br />N. PROVIDE A YELLOW STRIPED AREA, 3 DEEP BY THE WIDTH OF THE ELECTRICAL PANELS, ON <br />THE CONCRETE FLOOR IN FRONT OF THE ELECTRICAL PANELS AND SWITCHGEAR IN THE <br />RECEIVING AREA. AT THE- SWITCHGEAR, PAINT- THE EXPOSED PORTION OF THE CONCRETE <br />HOUSEKEEPING PAD YELLOW. <br />.. <br />ExCEL <br />ENGINEERING;. <br />Lo <br />CD <br />z <br />� <br />� <br />W <br />Q <br />O <br />W <br />IZ <br />0 <br />a <br />Z <br />Q <br />LdLd <br />Lj <br />z <br />ry <br />U <br />Ld <br />acne <br />U) <br />[-- <br />•• z <br />ly- <br />Ld <br />U <br />Q <br />��• <br />LLJ LL Q <br />C) <br />� <br />W <br />Q <br />cn <br />Z <br />Z w <br />V) <br />0- 'T-- C/) <br />cf) 00 Q <br />O Q N w <br />0 <br />N <br />W <br />W <br />D <br />V) <br />Z <br />w <br />*0 <br />U <br />� <br />0 > <br />m <br />Ln <br />W <br />M <br />a- <br />D <br />__j <br />J <br />.. <br />_j <br />Q <br />Q <br />0 <br />z <br />CO <br />J <br />U <br />W <br />J <br />W <br />OW <br />a_ <br />0 <br />(2- <br />L'J <br />O <br />I� <br />12- <br />W <br />n <br />a <br />N <br />rl_ <br />N <br />■ <br />DATE: <br />NOV. 23, 2009 <br />Z <br />IS JOBNUMBER: <br />914790 <br />W <br />W <br />z SHEET <br />W <br />J <br />W <br />U <br />X T 2 <br />W <br />o <br />